Technical Specifications and Selection Guide for Schneider EZSS630F3630
EZSS630F3630 is a 3P 630A Moulded Case Circuit Breaker (MCCB) from Schneider Electric’s EasyPact EZS+ Series (Dunhuang Series). Its official order code is EZSS630F3630, with the full model description EZS-S630 36kA TM630D 3P3D, designed for power distribution protection.
- Model Code Explanation
| Модельный сегмент | Описание |
| EZS | EasyPact EZS+ Series MCCB |
| С | Стандартный тип |
| 630 | Frame current 630A |
| Ф | Класс отключающей способности, 36тот (415ВАК) |
| 3 | 3 столбы |
| 630 | Rated current 630A |
| TM630D | Thermal‑magnetic trip unit, rated 630A, D‑curve |
- Основные технические параметры
| Элемент | Спецификация |
| Тип продукта | Moulded Case Circuit Breaker (MCCB) |
| Номинальное напряжение | 400/415VAC 50/60Hz |
| Номинальный ток (В) | 630А |
| Ток кадра (Ю) | 630А |
| Количество полюсов | 3П3Д (3полюс, 3‑wire protection) |
| Максимальная отключающая способность (Ику) | 36тот (415ВАК) |
| Отключающая способность сервиса (Икс) | 36тот (100% Ику) |
| Trip Unit | Thermal‑magnetic trip (TM‑D), with long‑time overload and instantaneous short‑circuit protection |
| Монтаж | Зафиксированный (стандартный), plug‑in/withdrawable optional (with accessories) |
| Связь | Front connection (стандартный), rear/plug‑in connection optional |
| Защита от проникновения | IP30 (device body) |
| Ambient Conditions | Temperature ‑5℃~+40℃, высота ≤2000 м, pollution degree 2/3 |
| Standards | МЭК 60947-2, ГБ 14048.2 |
- Application Environment
- Main Applications
Main or branch switch in low-voltage distribution systems of industrial plants, commercial buildings and large public facilities
Secondary distribution, civil construction and electromechanical markets
Защитите двигатели, трансформаторы, generators and other electrical equipment against overload and short-circuit damage
- Экологические требования
Рабочая температура: -5℃~+40℃ (derating required above 40℃)
Относительная влажность: ≤95%, неконденсирующийся
Высота: ≤2000m (derating required above 2000m)
Installation location: Indoor, vertical mounting (inclination ≤5°)
Степень загрязнения: Степень 2 (стандартный), applicable to degree 3 окружающая среда (with special treatment)
- Cross-Brand Equivalent/Replacement Models
| Бренд | Запасная модель | Примечания |
| Шнайдер | CVS630F ETS2.3 630A 3P3D (LV563505) | Upgraded electronic trip unit with LSI protection |
| Шнайдер | NSX630F Micrologic 2.3 630A 3P3D (LV432876) | High‑performance flagship model, full electronic protection, communication optional |
| АББ | Tmax T6N630 TMD 630/3P | Equivalent thermal‑magnetic MCCB |
| Сименс | 3VA6300‑6EL32‑0AA0 | 630A 3P 36kA thermal‑magnetic MCCB |
| Чинт | NM1‑630S/3300 630A | Отечественная альтернатива, 36кА отключающая способность |
- Official Order Information
Official Order Code: EZSS630F3630
Common Accessories:
Вспомогательный контакт: LV429310 (1НО+1НЗ)
Шунтовая поездка: LV429410 (220ВАК)
Undervoltage release: LV429510 (220ВАК)
Plug-in base: LV429100 (for 630A)
Motor mechanism: LV420089 (24В постоянного тока)
- Complete Model List of This Series (630A Frame)
| Модель | Разрывная способность | поляки | Номинальный ток | Trip Unit |
| EZSS630E3630 | 25тот | 3П | 630А | TM‑D |
| EZSS630F3630 | 36тот | 3П | 630А | TM‑D |
| EZSS630N3630 | 50тот | 3П | 630А | TM‑D |
| EZSS630H3630 | 70тот | 3П | 630А | TM‑D |
| EZSS630F4630 | 36тот | 4П | 630А | TM‑D |
- Замечания по установке и техническому обслуживанию
- Меры предосторожности при установке
For fixed mounting, reserve sufficient operating space (handle space ≥120mm)
Tighten terminals to specified torque (recommended for copper conductors: 40N·m for M10 bolts)
Maintain spacing ≥20mm between side-by-side units for proper heat dissipation
- Рекомендации по техническому обслуживанию
Регулярный осмотр (at least once per year): появление, fasteners, operating mechanism flexibility
After short-circuit tripping, inspect contact condition and replace if necessary
Thermal-magnetic trip units are non-adjustable; replace with electronic trip models if parameter adjustment is needed
- Selection and Replacement Recommendations
- Selection Factors
System short-circuit current level (ensure Icu ≥ calculated value)
Load type (D-curve for distribution protection, motor-specific type for motor protection)
Installation space and operation method
Future expansion (reserve 10%–20% margin)
- Альтернативные решения
For more precise protection and adjustable parameters, upgrade to CVS630F ETS2.3 electronic trip model
For communication and remote monitoring, select NSX630F series with intelligent trip units such as Micrologic 5.3A
For budget-limited projects, consider domestic alternatives including Chint NM1 and Delixi CDM3 series
Detailed Connection Methods for Schneider EZSS630F3630
The standard connection method of Schneider EZSS630F3630 (EZS-S630 36kA TM630D 3P3D) is fixed front connection, with multiple optional connection configurations as follows:
- Basic Connection Methods and Configuration Options
| Тип монтажа | Connection Direction | Supported | Примечания |
| Зафиксированный (Стандартный) | Front connection | ✓ Standard | Main circuit cables/busbars connected from front, easy operation, good heat dissipation |
| Зафиксированный | Заднее подключение | ✓ Optional | Special configuration required, suitable for compact panel space |
| Plug‑in (Необязательный) | Front connection | ✓ Optional | Requires plug‑in base (например. LV429100) for quick replacement and maintenance |
| Plug‑in | Заднее подключение | ✗ Not supported | Plug‑in rear connection not available for EZS+ 630A |
| Withdrawable | Any direction | ✗ Not supported | Withdrawable mounting not available for EZS+ series |
- Connection Technical Details
- Terminal Types
Главная цепь: Copper bolt terminals, suitable for cables or busbars
Схема управления (with auxiliary contacts, shunt/undervoltage releases): Plug-in terminals for easy secondary wiring
- Conductor Specifications
Suitable copper conductor cross-section: Up to 185mm² cable or equivalent busbar
Terminal tightening torque: 40N·m recommended for M10 bolts to ensure reliable connection
Supported connections: Direct cable connection, busbar connection (with dedicated clamps)
- Polarity and Phase Sequence
3P3D configuration: Подключить L1, Л2, L3 three-phase power; no neutral (Н) необходимый
Markings: Clear phase sequence labels (1, 2, 3 correspond to L1, Л2, L3) on the breaker body
- Connection Precautions and Specifications
- Pre-Installation Preparation
Ensure breaker is OFF, disconnect upstream power and verify voltage absence
Clean terminal surfaces and remove oxidation before connection
Select properly sized conductors to avoid overheating or improper fitting
- Wiring Standards
Maintain equal length for each phase in main circuit to avoid unbalanced stress
Route control circuit separately from main circuit to reduce electromagnetic interference
Check terminal tightness after wiring to prevent loose connections
Ensure no tools or debris inside the breaker after wiring; reinstall protective covers
- Special Environment Requirements
Vertical mounting: Must be installed vertically (inclination ≤5°) for proper arc extinction and mechanism operation
Derating: Derate accordingly when temperature >40℃ or altitude >2000м, adjust conductor size accordingly
Степень загрязнения 3: Additional protection required to prevent dust and moisture from affecting insulation
- Recommended Connection Accessories
The following accessories are available for extended functions or special installations:
| Аксессуар | Код заказа | Функция |
| Plug‑in base | LV429100 | For 630A, enables plug‑in mounting and front connection |
| Вспомогательный контакт | LV429310 | Provides 1NO+1NC signals for status indication or control |
| Шунтовая поездка | LV429410 | Remote tripping at 220VAC, requires control power |
| Undervoltage release | LV429510 | Undervoltage protection at 220VAC, trips on power loss |
| Busbar clamps | Dedicated | Secure busbar fixation for reliable connection |
- Selection and Application Advice
- Стандартная конфигурация: Fixed front connection preferred for general distribution, balancing cost and practicality
- Maintenance Convenience: Plug-in front connection recommended for frequent maintenance, reducing downtime
- Space Restrictions: Fixed rear connection can be used for limited cabinet depth, with sufficient operating space reserved
- Control Expansion: Reserve control wiring space and use suitable secondary accessories for remote control or monitoring
Контактор,автоматический выключатель,солнечный инвертор,электрический счетчик,солнечные батареи