Selective Coordination Parameter Table for Siemens 3WT2M40 ETU35WT F-4P and Lower-level Molded Case Circuit Breakers

Coordination Standard: МЭК 60947-2

Core Principle: The short-time delay protection time of the upper-level air circuit breaker (3WT) > the instantaneous trip time of the lower-level molded case circuit breaker, realizing precise isolation of faulty branches and avoiding system over-tripping.

Application ScenarioParameters of Upper-level Air Circuit Breaker (3WT2M40 ETU35WT F-4P)Selection and Parameters of Lower-level Molded Case Circuit Breaker (Siemens 3VL Series)Coordination Effectiveness Judgment
High-power Motor CircuitOverload long-time delay: Ir = 1600A (1.0×In)Модель: 3VL2740-1AA33-0AA0Lower-level instantaneous trip current (3200А) < Upper-level short-time delay current (12800А)
(например, 160kW/380V motor, rated current ≈ 320A)Short-circuit short-time delay: Isd = 8×Ir = 12800AНоминальный ток: 400АLower-level instantaneous operating time (≤ 0.02s) < Upper-level short-time delay time (0.2с)
Short-time delay time: 0.2сOverload long-time delay: Ir = 320A✓ Full selective coordination
Instantaneous protection: Off (Ii = Off)Instantaneous trip: Ii = 10×Ir = 3200A
Trip type: TMD
General Power CircuitOverload long-time delay: Ir = 1600AМодель: 3VL2763-1AA33-0AA0Lower-level instantaneous current (4800А) < Upper-level short-time delay current (9600А)
(например, water pumps, фанаты, total current ≈ 600A)Short-circuit short-time delay: Isd = 6×Ir = 9600AНоминальный ток: 630АLower-level operating time < Upper-level short-time delay time
Short-time delay time: 0.3сOverload long-time delay: Ir = 600A✓ Full selective coordination
Instantaneous protection: OffInstantaneous trip: Ii = 8×Ir = 4800A
Trip type: TMD
Lighting/Socket Distribution CircuitOverload long-time delay: Ir = 1600AМодель: 3VL2732-1AA33-0AA0Lower-level instantaneous current (3000А) < Upper-level short-time delay current (8000А)
(Three-phase four-wire system, total current ≈ 250A)Short-circuit short-time delay: Isd = 5×Ir = 8000AНоминальный ток: 320АOperating time meets level difference
Short-time delay time: 0.2сOverload long-time delay: Ir = 250A✓ Full selective coordination
Instantaneous protection: OffInstantaneous trip: Ii = 12×Ir = 3000A
Trip type: TMD
Emergency Power Supply CircuitOverload long-time delay: Ir = 1600AМодель: 3VL2750-1AA33-0AA0Lower-level instantaneous current < Upper-level short-time delay current
(например, EPS/UPS output, current ≈ 400A)Short-circuit short-time delay: Isd = 7×Ir = 11200AНоминальный ток: 500АUpper-level instantaneous current (16000А) is much larger than that of the lower level; upper-level operates only in case of severe short circuit
Short-time delay time: 0.4сOverload long-time delay: Ir = 400A✓ Selective coordination + backup protection
Instantaneous protection: Ii = 10×In = 16000AInstantaneous trip: Ii = 10×Ir = 4000A
Trip type: TMD

Notes on Coordination Design

  1. Setting of Upper-level Instantaneous Protection: For branch short-circuit faults, it is recommended to turn off the instantaneous protection of 3WT (Ii = Off) and retain only the short-time delay protection; the instantaneous protection shall be enabled as backup only when bus short circuit occurs in the system (short-circuit current ≥ 12800A).
  2. Cable Cross-section Matching: The cable between the upper and lower-level circuit breakers shall meet theshort-circuit withstand capacityto prevent cable burnout before the circuit breaker operates.
  3. Ambient Temperature Correction: When the temperature inside the distribution cabinet exceeds 40℃, derating of the rated current of the circuit breaker is required (derating by 1% for every 1℃ rise) to ensure stable protection characteristics.
  4. Selection of Lower-level Trip Type: TMD trip unit (thermal-magnetic trip) is preferred for motor circuits, and MIC trip unit (electronic trip) can be selected for lighting circuits to improve protection accuracy.