T6V 800 PR221DS|ABB Tmax T6 Series High Performance Moulded Case Circuit Breaker (เอ็มซีซีบี)
Full Model: T6V 800 PR221DS-LS/I In=800 (Common Order Codes: 1SDA069432R1, 1SDA069429R1, 3P/4P selectable)
ยี่ห้อ: เอบีบี (SACE Tmax Series)
- Detailed Model Interpretation
| ส่วนโมเดล | ความหมาย | Key Description |
| T6 | Series Designation | Tmax T6 series, frame current 800A, suitable for medium and high voltage power distribution systems |
| วี | Breaking Capacity Class | Class V, ultra-high breaking capacity: 120kA at 400V, 200kA at 220V |
| 800 | จัดอันดับปัจจุบัน | 800ก (same as frame current) |
| PR221DS | ประเภทหน่วยการเดินทาง | Electronic intelligent trip unit with LS/I protection (Long-time delay L, Short-time delay S, Instantaneous I) |
| LS/I | Protection Configuration | Standard three-stage protection; earth fault protection optional (extra configuration required) |
| F F | Mounting / Connection | First F: Fixed mounting; Second F: Front connection |
- พารามิเตอร์ทางเทคนิคหลัก
| Item | ข้อมูลจำเพาะ | หมายเหตุ |
| แรงดันไฟฟ้าที่ได้รับการจัดอันดับ (อือ) | 690วีและ | Suitable for industrial high-voltage power distribution systems |
| จัดอันดับแรงดันไฟฟ้าของฉนวน (อุ้ย) | 1000วีและ | Higher than rated operating voltage, large safety margin |
| Ultimate Breaking Capacity (ห้องไอซียู) | 120kA@400V, 200kA@220V | Highest Class V, suitable for harsh industrial environments |
| Rated Operational Current (In) | 800ก | Maximum continuous operating current |
| Poles | 3P/4P selectable | 3P for three-phase circuits, 4P includes neutral protection |
| Trip Characteristic | LS/I three-stage protection | Long-time delay inverse time, short-time / instantaneous definite time |
| Mounting Type | ที่ตายตัว | Draw-out type also available (special model required) |
| Connection Type | Front connection | Compatible with cables or busbars |
| Degree of Protection | IP30 | Standard switchgear installation protection |
| Applicable Standard | ไออีซี 60947-2 | International standard for low-voltage switchgear |
- Key Features & Applications
ข้อดีหลัก
- Ultra-high breaking capacity: Class V can withstand severe short-circuit faults and ensure system safety
- Intelligent protection: PR221DS trip unit provides accurate overload and short-circuit protection with adjustable parameters
- Reliable and durable: ABB Tmax series design, suitable for frequent operation and harsh industrial environments
- Flexible extension: Supports various accessories (ผู้ติดต่อเสริม, alarm contacts, การปล่อยแรงดันตก, ฯลฯ)
การใช้งานทั่วไป
Main power distribution systems in large industrial plants
690V high-voltage Motor Control Centers (MCC)
Power supply for data centers and critical infrastructure
Combiner box protection for new energy power systems (PV, wind power)
Marine and offshore platform power distribution systems
- Reference Replacement Models
Same-brand Upgrades / Replacements
| แบบอย่าง | ทำลายความจุ | Trip Type | Application |
| T6V 800 PR222DS-LSIG | 120kA@400V | With earth fault protection (ช) | Systems requiring earth fault detection |
| T6V 800 PR223DS | 120kA@400V | Advanced intelligent trip unit | Applications requiring remote monitoring and communication |
| T6S 800 PR221DS | 70kA@400V | Standard breaking capacity | General industrial power distribution, ต้นทุนที่ต่ำกว่า |
Cross-brand Alternatives
| ยี่ห้อ | แบบอย่าง | Key Matching Parameters |
| ชไนเดอร์ | Masterpact MT25H1 800A | 800ก, 120kA breaking, three-stage protection |
| ซีเมนส์ | 3WL1210-3BB36-4GA4 | 800ก, 100kA breaking, intelligent trip unit |
| Mitsubishi | NF800-SEW | 800ก, 100kA breaking, electronic trip unit |
- Selection Notes
- Breaking capacity matching: Select V/S/H/N/L classes based on system short-circuit current calculation
- Protection function selection: Basic LS/I meets most needs; choose LSIG for earth fault protection
- Mounting type: Fixed for standard switchgear, draw-out for easy maintenance and replacement
- Accessory configuration: Select auxiliary contacts, alarm contacts, motor operators, ฯลฯ, according to control requirements
- Voltage compatibility: T6V suitable for systems up to 690V; use dedicated 1000V series (เช่น, T6L) for higher voltages
คอนแทคเตอร์,เบรกเกอร์,อินเวอร์เตอร์พลังงานแสงอาทิตย์,มิเตอร์ไฟฟ้า,แบตเตอรี่พลังงานแสงอาทิตย์