A9L612301 is a pluggable Type T1+T2 Surge Protection Device (เอสพีดี) of the iPRF1 12.5r 3P model under ชไนเดอร์‘s Acti9 series. It features both Class I and Class II test classifications with 3 เสา, making it suitable for lightning and surge protection in three-phase distribution systems. It supports remote status indication and enables convenient installation and maintenance. Below is a detailed explanation of its core parameters, installation key points, replacement selection, and troubleshooting:
| รายการพารามิเตอร์ | ค่า |
| Product Model | iPRF1 12.5r 3P |
| Test Classification | Class I + Class II (T1+T2) |
| Impulse Current (Iimp) | 12.5ที่ (common mode L – วิชาพลศึกษา) |
| Nominal Discharge Current (In) | 20ที่ |
| Maximum Discharge Current (Imax) | 50ที่ |
| Maximum Continuous Operating Voltage (Uc) | 350วีและ |
| จัดอันดับแรงดันไฟฟ้าที่ใช้งาน (Ue) | 230/400วีและ (±10%), 50/60เฮิรตซ์ |
| Voltage Protection Level (Up) | ≤1.5kV |
| หมายเลขขั้วโลก | 3ป |
| Remote Indication | 1 Changeover Contact (1C/O) |
| วิธีการติดตั้ง | 35mm standard DIN rail |
| Width Dimension | 3 โมดูล (27มม) |
คุณสมบัติผลิตภัณฑ์ & สถานการณ์การใช้งาน
- คุณสมบัติผลิตภัณฑ์
Integrated Protection: T1+T2 composite protection eliminates the need for additional graded SPDs, saving space and cost.
Pluggable Design: The module supports hot plugging and unplugging under live conditions, enabling quick replacement in case of failure without affecting the power supply of the main circuit.
Visual Status Indication: Built-in remote indication contact can be connected to the monitoring system to feed back the operating status of the SPD in real time, facilitating operation and maintenance.
Safe and Reliable: Built-in thermal trip and overcurrent protection prevent short-circuit risks caused by SPD faults.
- สถานการณ์การใช้งาน
It is applicable to the incoming ends of three-phase distribution systems or the front ends of important equipment in industrial plants, commercial buildings, data centers, ฯลฯ, protecting electrical equipment from damage caused by direct lightning strikes, induced lightning, and operating overvoltage.
Key Installation & Wiring Points
- Installation Preparation
Confirm the installation position on a 35mm standard DIN rail, reserve sufficient heat dissipation space, and avoid close proximity to heating elements.
Verify the matching of system voltage, frequency and SPD parameters; Uc shall be higher than the maximum operating voltage of the system.
- ข้อมูลจำเพาะของสายไฟ
The incoming end is connected to the power supply side, and the outgoing end to the load side; L1, L2 and L3 correspond to the three-phase live wires, and PE shall be reliably earthed.
The wire diameter of the connecting conductor shall be no less than 16mm² copper core wire, and the length shall be as short as possible (≤50cm) to reduce the impact of wire resistance on protection performance.
The remote indication contact is connected to the monitoring circuit, with the rated current not exceeding AC 12 6A/240V and DC 12 2A/48V.
- หมายเหตุ
It shall be used in conjunction with a backup protection circuit breaker; the rated current of the circuit breaker is recommended to be 16A 32A to avoid selective tripping caused by SPD faults.
การแก้ไขปัญหา & Maintenance
| Fault Phenomenon | Possible Cause | Troubleshooting Method |
| Remote indication contact actuation | SPD module damage | Replace the iPRF1 12.5r 3P module after power off |
| Severe heating of SPD | Loose wiring or poor contact | Check the wiring terminals, retighten them to ensure reliable connection |
| Unable to plug or unplug the module | Damaged DIN rail buckle | Replace the DIN rail or repair the buckle; avoid forced plugging/unplugging to prevent module damage |
Cross-brand Replacement Selection
For replacement of this model, the following products of the same grade can be referred to. Ensure the consistency of key parameters during replacement:
- เอบีบี: OVR T1+T2 20 350 3ป, In=20kA, Imax=50kA, Uc=350V, 3ป, with remote indication.
- ซีเมนส์: 5SD7432 0, Type T1+T2, In=20kA, Imax=50kA, Uc=350V, 3ป, suitable for standard DIN rail.
- Schneider same-series replacement: A9L16633 (iPRF1 12.5r 3P, with remote indication), which is completely consistent in function with A9L612301 and can be directly interchanged.
Selection & Procurement Suggestions
- Confirm that the system is a three-phase distribution system; for a 3P+N system, A9L16634 (iPRF1 12.5r 3P+N) is optional.
- Check the product batch number and anti-counterfeiting mark during procurement to ensure genuine Schneider original products and avoid the impact of counterfeit products on protection performance.
- For bulk procurement, consult authorized Schneider distributors to obtain better prices and technical support.
Parameter Comparison Between A9L612301 and A9L16633 (Core Conclusion: Fully consistent in function, can be directly interchanged)
| รายการพารามิเตอร์ | A9L612301 | A9L16633 | Difference Description |
| Product Model | iPRF1 12.5r 3P | iPRF1 12.5r 3P | Identical |
| Test Classification | Class I + Class II (T1+T2) | Class I + Class II (T1+T2) | Identical |
| Impulse Current (Iimp) | 12.5ที่ (common mode L-PE) | 12.5ที่ (common mode L-PE) | Identical |
| Nominal Discharge Current (In) | 20ที่ | 20ที่ | Identical |
| Maximum Discharge Current (Imax) | 50ที่ | 50ที่ | Identical |
| Maximum Continuous Operating Voltage (Uc) | 350วีและ | 350วีและ | Identical |
| จัดอันดับแรงดันไฟฟ้าที่ใช้งาน (Ue) | 230/400วีและ (±10%), 50/60เฮิรตซ์ | 230/400วีและ (±10%), 50/60เฮิรตซ์ | Identical |
| Voltage Protection Level (Up) | ≤1.5kV | ≤1.5kV | Identical |
| หมายเลขขั้วโลก | 3ป | 3ป | Identical |
| Remote Indication | 1 Changeover Contact (1C/O) | 1 Changeover Contact (1C/O) | Identical |
| วิธีการติดตั้ง | 35mm standard DIN rail | 35mm standard DIN rail | Identical |
| Width Dimension | 3 โมดูล (27มม) | 3 โมดูล (27มม) | Identical |
| Technical Type | MOV+GDT composite technology | MOV+GDT composite technology | Identical |
| Status Indication | Green (normal)/Red (fault) | Green (normal)/Red (fault) | Identical |
| Certification Standard | ไออีซี 61643-11, กิกะไบต์ 18802.1 | ไออีซี 61643-11, กิกะไบต์ 18802.1 | Identical |
| Production Batch | Old batch | New batch | Only different in batch, no functional difference |
Same-series 3P+N Model Replacement Adaptation List (A9L612301 is 3P, the following are corresponding 3P+N models)
| แบบอย่าง | Product Name | พารามิเตอร์หลัก | Adaptation Scenario | Replacement Description |
| A9L16634 | iPRF1 12.5r 3P+N | Type T1+T2, Iimp=12.5kA, In=20kA, Imax=50kA, Uc=350V, 4 โมดูล (36มม), with remote indication | Three-phase four-wire (3พี+เอ็น) distribution system, TN-S/TT earthing system | 3P+N version of A9L612301 with an increased width of 1 module; confirm the distribution box space |
| A9L612302 | iPRF1 12.5r 3P+N | Identical to A9L16634 | Three-phase four-wire (3พี+เอ็น) distribution system | Old batch 3P+N version of A9L612301 |
Key Notes for Replacement Selection
- Selection of 3P and 3P+N: Select according to the system type; 3P is applicable to three-phase three-wire systems, and 3P+N is applicable to three-phase four-wire systems (TN-S/TT).
- Installation Space Confirmation: The width of the 3P model is 27mm (3 โมดูล), and that of the 3P+N model is 36mm (4 โมดูล). Ensure sufficient installation space in the distribution box during replacement.
- Backup Protection Coordination: The 3P+N model shall also be used with a 16A-32A circuit breaker to ensure protection coordination.
- Remote Indication Wiring: The remote indication contact of the 3P+N model is completely the same as that of the 3P model, and the original wiring can be directly reused.
- Earthing System Compatibility: The 3P+N model is applicable to TN-S and TT earthing systems, while the 3P model is applicable to all three-phase earthing systems.
Schneider A9L612301 (iPRF1 12.5r 3P) Cross-brand Model Comparison
Core Parameter Benchmark: T1+T2 composite protection, Iimp=12.5kA(10/350μs), In=20kA(8/20μs), Imax=50kA(8/20μs), Uc=350V, 3 เสา, with remote indication, pluggable design, 35mm DIN rail mounting
- International Mainstream Brand Comparison Table
| ยี่ห้อ | แบบอย่าง | พารามิเตอร์หลัก | คุณสมบัติผลิตภัณฑ์ | Replacement Notes |
| เอบีบี | OVR T1-T2 3L 20-350 P TS QS | T1+T2, Iimp=12.5kA, In=20kA, Imax=50kA, Uc=350V, 3ป, with remote indication (TS) | Pluggable module, green/red status indication, thermal trip protection, สอดคล้องกับ IEC 61643-11 | Installation width 27mm(3 โมดูล), completely consistent with Schneider; 16A-32A circuit breaker is recommended for backup protection |
| (Order No.: 2CTB815710R2800) | ||||
| ซีเมนส์ | 5SD7413-0 | T1+T2, Iimp=12.5kA, In=20kA, Imax=50kA, Uc=335V, 3ป, with remote indication | Compact design, zero leakage current technology, automatic disconnection from the main circuit in case of failure, all models are equipped with remote contacts | Uc=335V is slightly lower than Schneider’s 350V, applicable to 400V systems; installation width 27mm(3 โมดูล) |
| (SENTRON Series) | ||||
| Phoenix Contact | FLT-SEC-T1+T2-3S-350/25-FM | T1+T2, Iimp=12.5kA, In=25kA, Imax=62.5kA, Uc=350V, 3ป, with remote indication | Pluggable design, low residual voltage (≤1.5kV), anti-vibration locking device, compatible with CHECKMASTER testing tools | In=25kA is slightly higher than the benchmark with stronger protection capacity; installation width 36mm(4 โมดูล), confirm the distribution box space |
| (Order No.: 2905470) | ||||
| Phoenix Contact | VAL-MS-T1/T2 350/12.5/3+0 | T1+T2, Iimp=12.5kA, In=20kA, Imax=50kA, Uc=350V, 3ป, with remote indication | Varistor technology, support hot plugging and unplugging, floating remote contact, suitable for Class III-IV lightning protection buildings | Installation width 27mm(3 โมดูล), fully compatible with Schneider, support replacement under live conditions |
| (Order No.: 2800182) | ||||
| Hager | SPA931 | T1+T2, Iimp=12.5kA, In=20kA, Imax=50kA, Uc=350V, 3ป, with remote indication | การออกแบบโมดูลาร์, clear fault indication, compatible with all three-phase earthing systems, compliant with EN 61643-11 | Installation width 27mm(3 โมดูล), 16A-32A is recommended for backup protection, consistent with Schneider in protection coordination |
- Well-known Domestic Brand Comparison Table
ยี่ห้อ แบบอย่าง พารามิเตอร์หลัก คุณสมบัติผลิตภัณฑ์ Replacement Notes อร่อย CDYN-I+II 3P 20-350 T1+T2, Iimp=12.5kA, In=20kA, Imax=50kA, Uc=350V, 3ป, with remote indication Pluggable module, built-in thermal trip and overcurrent protection, compliant with GB 18802.1, cost-effective Installation width 27mm(3 โมดูล), completely consistent with Schneider, compatible with domestic distribution boxes (DZ47sY Series) ชินท์ NXU-I+II 3P 20-350 T1+T2, Iimp=12.5kA, In=20kA, Imax=50kA, Uc=350V, 3ป, with remote indication การออกแบบโมดูลาร์, green/red status indication, automatic disconnection in case of failure, compatible with TN-S/TT earthing systems Installation width 27mm(3 โมดูล), 16A-32A is recommended for backup protection, ประสิทธิภาพต้นทุนสูง (Kunlun Series) Nader NXU1-3P/20-350 T1+T2, Iimp=12.5kA, In=20kA, Imax=50kA, Uc=350V, 3ป, with remote indication Pluggable design, low residual voltage (≤1.5kV), good thermal stability, applicable to industrial and commercial buildings Installation width 27mm(3 โมดูล), compatible with Schneider products in dimension, equivalent protection performance (Surge Series) Key Notes for Replacement Selection
- Parameter Matching Priority
Must ensure: Uc≥maximum operating voltage of the system (350V is applicable to 400V systems)
Key matching: Test classification (T1+T2), Iimp, In, Imax, pole number are completely consistent
Functional matching: Remote indication contact type (1C/O), pluggable design
- Installation & Space Confirmation
The width of the standard 3P model is 27mm(3 โมดูล), and that of the 3P+N model is 36mm(4 โมดูล)
Check the DIN rail space and heat dissipation conditions of the distribution box during replacement, and avoid close proximity to heating elements
- Backup Protection Coordination
All models shall be used with a 16A-32A Type D circuit breaker to ensure protection coordination
The use of Type C circuit breakers is prohibited to avoid maloperation during lightning strikes
- Earthing System Compatibility
The 3P model is applicable to all three-phase earthing systems (TN-C/TN-S/TT)
The 3P+N model is only applicable to TN-S/TT systems, attention shall be paid to the system earthing type
- Recommended Priority for Brand Replacement
| Priority | ยี่ห้อ | แบบอย่าง | Recommended Reason |
| 1 | เอบีบี | OVR T1-T2 3L 20-350 P TS QS | Fully matched parameters, good brand compatibility, perfect global service network |
| 2 | ซีเมนส์ | 5SD7413-0 | Mature technology, zero leakage current design, consistent dimension with Schneider |
| 3 | Phoenix Contact | FLT-SEC-T1+T2-3S-350/25-FM | Slightly stronger protection capacity, supported by testing tools, widely used in industry |
| 4 | Delixi/Chint | CDYN-I+II 3P 20-350/NXU-I+II 3P 20-350 | High cost performance, first choice for domestic replacement, compatible with domestic projects |
คอนแทคเตอร์,เบรกเกอร์,อินเวอร์เตอร์พลังงานแสงอาทิตย์,มิเตอร์ไฟฟ้า,แบตเตอรี่พลังงานแสงอาทิตย์