A9F44204 is a 2-pole, 4A, C-curve miniature circuit breaker (MCB) from Schneider Electric’s Acti9 iC60N series. As part of the high-end Acti9 range, it provides overload and short-circuit protection for electrical circuits.
- Model Number Explanation
A9F: Acti9 iC60N series MCB
4: 2P (2-pole, dual-pole protection)
4: C-type tripping curve (distribution protection for general loads)
204: Rated current 4A
- Key Technical Specifications
Item Specification
Series Acti9 iC60N
Number of Poles (P) 2P (two-phase protection)
Rated Current (In) 4A
Tripping Curve C-type (instantaneous tripping at 5~10In)
Breaking Capacity (Icn) 6kA @ 400V (IEC 60898)
Rated Voltage (Ue) 230/400V AC
Insulation Voltage (Ui) 500V AC
Impulse Withstand Voltage (Uimp) 6kV
Protection Degree IP20 (front)
Mounting 35mm DIN rail
Width 4 modules (36mm)
Dimensions (W×H×D) 36 × 85 × 78.5 mm
Weight Approx. 0.25kg
Certifications IEC 60898-1 / GB 10963.1
- Main Features
VisiTrip visual trip indication: clearly shows tripping status via indicator window
VisiSafe safety window: green band indicates physical contact disconnection
Thermal-magnetic tripping: dual protection against overload and short-circuit
Can be combined with iC60 Vigi residual current modules for earth leakage protection
Applications: general loads such as lighting, sockets, small motors, control circuits, etc.
- Alternative / Similar Models
Same series, same current:
1P 4A C: A9F44104
4P 4A C: A9F44404
Higher breaking capacity (iC60H):
2P 4A C: A9F54204 (10kA)