ABB ACS355 series general machinery drive, 0.37 كيلوواط / 0.5 HP, single-phase 200–240 V input, IP20 protection, rated output current 2.4 أ. Suitable for speed control and energy-saving operation of small machinery.
1 Model Code Explanation
| Code Part | معنى |
| ACS355 | ABB general machinery drive series |
| 01ه | Protection class IP20, for installation in enclosed electrical cabinets |
| 02A4 | Rated output current 2.4 أ |
| 2 | Single-phase 200–240 V AC (±10%), 50/60 Hz input |
2 Key Technical Data
| غرض | قيمة |
| Rated power | 0.37 كيلوواط (0.5 HP) |
| Rated output current | 2.4 أ (at 40°C) |
| Input voltage / تكرار | Single-phase 200–240 V AC (±10%), 50/60 هرتز |
| Output voltage / تكرار | Three-phase 0–240 V AC, 0–500 Hz |
| Protection class | IP20 (indoor cabinet installation) |
| Control method | Scalar control (V/f), built-in application macros |
| Overload capability | 150% of rated current for 60 s; 180% for 2 s |
| Cooling method | Natural cooling |
| أبعاد (W×H×D) | 169×70×135 mm |
| وزن | تقريبا. 1.2 كجم |
| Order code | 3AUA0000058166 |
| EMC performance | Built-in EMC filter, compliant with EN 61800-3 |
3 Key Features
3.1 Flexible Control
Predefined application macros: constant torque, fan/pump, PID control, إلخ.
Local/remote control switching via keypad, terminals or fieldbus
Built-in PID controller for closed-loop flow, ضغط, إلخ.
3.2 Reliable Protection
Overcurrent, الزائد, overvoltage, undervoltage, ارتفاع درجة الحرارة, phase loss protection
Motor over-temperature protection (requires external PTC)
Short-circuit and earth-fault protection
3.3 Easy Operation
Compatible control panel with ACS350/510/550 series
Parameter copy function for fast commissioning
MTBF > 100,000 hours for continuous operation
4 التطبيقات النموذجية
Small conveyors, packaging machinery
Fans, مضخات (small HVAC systems)
Mixers, centrifuges and small processing machines
Automatic doors, roller shutters
Medical equipment, laboratory instruments
Textile, printing and other light industrial machinery
5 تثبيت & Commissioning Guidelines
5.1 متطلبات التثبيت
Must be installed in an enclosed electrical cabinet
Ambient temperature: 0–40°C (derate 10% at 40–50°C)
Mount vertically, keep ≥ 100 mm clearance above and below for cooling
Avoid dust, oil, corrosive gases
Input protection: 10 A MCCB (C-curve) or fuse recommended
5.2 Basic Commissioning Steps
- Pre-power check: Verify wiring (L1/N input, U/V/W output), terminal torque, proper earthing
- Parameter initialization
Group 99: set motor rated voltage, حاضِر, power, speed
Select application macro (معيار, PID, إلخ.)
- Control configuration
Local control: via control panel
Remote control: via DI terminals or optional Modbus RTU
- Operation test
No-load test: run at 5–10 Hz, check rotation and stability
Load test: gradually apply load, verify current and temperature
Adjust acceleration/deceleration time (1–10 s recommended)
6 Cross-Brand Replacement Options (0.37 كيلوواط, 1-مرحلة 220 V, IP20)
| ماركة | نموذج | Key Matching Points |
| شنايدر | ATV12HU04M2 | 0.37 كيلوواط, 1-مرحلة 220 V, IP20, similar size |
| سيمنز | V20 6SL3210-5BB12-5UV1 | 0.37 كيلوواط, 1-مرحلة 220 V, IP20, integrated EMC |
| شينت | NVF2-0.37/2 | 0.37 كيلوواط, 1-مرحلة 220 V, IP20, economical alternative |
| ABB alternative | ACS150-01E-02A4-2 | Same power range, more compact design |
7 Selection & Maintenance Tips
7.1 Recommended Options
Braking function: optional braking resistor (75 أوه / 50 W recommended)
Communication: add RS485 module
Enhanced EMC: additional input EMC filter
7.2 Maintenance
Clean cooling channels every 6 شهور
Check terminal torque annually
Avoid frequent starts/stops (≥ 20 times per day)
Storage temperature: -25درجة مئوية إلى +60 درجة مئوية, dry environment
ABB ACS355-01E-02A4-2
Installation and Commissioning Manual
Overview: This manual provides complete instructions for safety, installation, wiring, parameter setting and commissioning of the ACS355-01E-02A4-2 drive (0.37 كيلوواط / 0.5 HP, single-phase 200–240 V) for general machinery speed control and energy saving.
1 Safety Instructions (Must Read)
1.1 Electrical Safety
Power-off procedure: Disconnect all power before installation, wiring or maintenance. Wait 5 minutes for internal capacitors to discharge.
Earthing: PE terminal must be reliably earthed (earth resistance ≤ 4 أوه)
حماية التيار الزائد: Install 10 A MCCB (C-curve) or fuse on input side
اختبار العزل: Only test motor cables; do NOT apply voltage to the drive itself
1.2 Mechanical Safety
Rotating parts (shaft, coupling, pulley) must be guarded
Mount vertically on solid surface to avoid vibration
Do not modify internal circuits or structures
1.3 Environmental Safety
درجة حرارة التشغيل: 0–40°C (derate 10% at 40–50°C)
رطوبة: 5–95% RH, غير التكثيف
IP20: must be installed in enclosed cabinet
2 Product Overview and Model Identification
2.1 شرح النموذج (ACS355-01E-02A4-2)
| Code | معنى |
| ACS355 | ABB general machinery drive series |
| 01ه | IP20, cabinet-mounted |
| 02A4 | Rated output current 2.4 أ (40°C) |
| 2 | Single-phase 200–240 V AC, 50/60 هرتز |
2.2 المواصفات الأساسية
| غرض | قيمة |
| Rated power | 0.37 كيلوواط (0.5 HP) |
| Input voltage | Single-phase 200–240 V AC (±10%) |
| Output voltage | Three-phase 0–240 V AC |
| Output frequency | 0–500 Hz |
| Overload capacity | 150% for 60 s, 180% for 2 s |
| Cooling | Natural cooling |
| أبعاد (W×H×D) | 169×70×135 mm |
| وزن | تقريبا. 1.2 كجم |
| Order code | 3AUA0000058166 |
3 Installation Procedure
3.1 Preparation
- Unpack and inspect drive for damage
- Choose well-ventilated, dust-free location inside cabinet
- Tools: Phillips screwdriver (PH2), متجرد الأسلاك, crimping tool, المتر المتعدد, insulation tape
3.2 Mounting
- Mount vertically on flat metal plate
- Keep ≥ 100 mm above/below, ≥ 50 mm left/right clearance
- Fix with M4 screws, tightening torque: 1.2–1.5 N·m
4 Electrical Wiring
4.1 Terminal Description (ACS355-01E Series)
| Section | صالة | وصف | Wiring |
| Power Circuit | L1/N | Single-phase 200–240 V input | 1.5–2.5 mm² copper |
| بي | Protective earth | ≥ 2.5 mm² copper | |
| U/V/W | 3-phase output to motor | 1.5–2.5 mm² copper | |
| دائرة التحكم | DI1–DI3 | Digital inputs | 0.5–1.5 mm², الأعلى 50 م |
| AI1/AI2 | Analog inputs (0–10 V / 0–20 mA) | Shielded twisted pair, الأعلى 100 م | |
| AO1 | Analog output (0–20 mA) | Shielded twisted pair, الأعلى 100 م | |
| +24V/GND | 24 V DC supply (الأعلى 100 أماه) | 0.5–1.5 mm² | |
| RS485+/– | Modbus RTU | Shielded twisted pair, الأعلى 1000 م |
4.2 خطوات الأسلاك
- Power wiring: L1/N to mains, PE to earth, U/V/W to motor
- Control wiring (Standard macro example):
DI1: Forward (FWD), DI2: Reverse (REV), DI3: Reset
AI1: Speed reference (0–10 V)
- Check torque, insulation, and phase sequence
5 Parameter Settings
5.1 Keypad Functions
▶/■: يبدأ / قف
▲/▼: Adjust value
ENTER: يتأكد
ESC: Back
LOC/REM: Local / Remote
5.2 Quick Motor Settings (Group 99)
| المعلمة | اسم | Setting | ملحوظة |
| 9901 | Language | Chinese / English | User choice |
| 9902 | Application macro | 1 (معيار) | General use |
| 9903 | Motor type | 1 (Asynchronous) | Standard induction motor |
| 9904 | Motor rated power | 0.37 كيلوواط | From nameplate |
| 9905 | Motor rated voltage | 220/230/240 V | From nameplate |
| 9906 | Motor rated current | Motor nominal | Typically ~2.1 A |
| 9907 | Motor rated frequency | 50/60 هرتز | From nameplate |
| 9908 | Motor rated speed | Motor nominal | ~1400–1450 rpm |
| 9909 | Number of motor poles | 4 | Standard for 0.37 كيلوواط |
| 9910 | Control mode | 1 (V/f) | Scalar control |
5.3 Common Application Parameters
| Group | المعلمة | اسم | Recommended Value |
| 10 | 1001 | Max frequency | 50/60 هرتز |
| 1002 | Min frequency | 0 هرتز | |
| 20 | 2001 | Acceleration time | 3–10 s |
| 2002 | Deceleration time | 3–10 s | |
| 21 | 2101 | Acc/dec type | 1 (Linear) |
| 40 | 4001 | DI1 function | 1 (FWD) |
| 4002 | DI2 function | 2 (REV) | |
| 4003 | DI3 function | 9 (RESET) | |
| 50 | 5001 | AI1 type | 1 (0–10 V) |
| 5002 | AI1 minimum | 0% | |
| 5003 | AI1 maximum | 100% | |
| 16 | 1607 | Save parameters | 1 |
6 Commissioning Flow
6.1 Pre-Power Check
Correct power and control wiring
Motor and drive area clear
Cabinet ventilation OK
Input voltage: 200–240 V single-phase
6.2 First Power-Up
Close MCCB, display shows REM or LOC
Check for fault codes
Verify Group 99 motor parameters
6.3 Motor Identification (خياري)
Set 9910 = 2 (ID Run)
Press ENTER; drive runs motor briefly
Completed when shown COMPLETE
6.4 No-Load Test
Switch to LOCAL
Run at 5 هرتز, check rotation
Increase to rated frequency, check noise and vibration
6.5 Load Test
Switch to REMOTE
Control speed via AI1
Check output current ≤ 2.4 أ
Adjust acc/dec to avoid overcurrent
Test protection functions
7 استكشاف الأخطاء وإصلاحها
7.1 Common Fault Codes
| Fault | وصف | Cause | Remedy |
| OVERCURRENT | Overcurrent | Motor overload, ماس كهربائى | Check load, محرك, parameters |
| OVERVOLTAGE | الجهد الزائد | High mains, fast deceleration | Check voltage, increase dec time |
| UNDERVOLTAGE | انخفاض الجهد | Low supply, اتصال فضفاض | Check mains and wiring |
| OVERTEMP | Overheating | High temp, blocked cooling | Improve ventilation, clean heatsink |
| MOTOR OVERLOAD | Motor overload | Excessive load | Check application, تقليل الحمل |
| FAULT RESET | Trip reset required | Fault occurred | Fix cause, reset via DI3 or keypad |
7.2 Typical Issues
| Symptom | Cause | حل |
| Motor does not start | Wrong LOC/REM, missing DI signal | Check mode, wiring and parameters |
| Unstable speed | AI noise, poor parameters | Use shielded cable, adjust filtering |
| Communication failure | Wrong settings, bad wiring | Check Group 98, RS485, termination |
8 Maintenance
8.1 الصيانة الروتينية
Clean cooling channels every 6 شهور
Check terminal torque annually
Log operating current and temperature
8.2 Long-Term Storage
درجة حرارة: -25درجة مئوية إلى +60 درجة مئوية
Dry, ventilated environment
Power on for 1 hour every 6 شهور
9 Appendix: Options and Replacements
9.1 Recommended Options
Braking resistor: 100 أوه / 50 دبليو
EMC filter
RS485 Modbus RTU module
Shielded cable for control wiring
9.2 Cross-Brand Alternatives (0.37 كيلوواط, 1-مرحلة 220 V, IP20)
| ماركة | نموذج | Matching Features |
| شنايدر | ATV12HU04M2 | 0.37 كيلوواط, 1-مرحلة 220 V, IP20 |
| سيمنز | V20 6SL3210-5BB12-5UV1 | 0.37 كيلوواط, 1-مرحلة 220 V, IP20 |
| شينت | NVF2-0.37/2 | 0.37 كيلوواط, 1-مرحلة 220 V, IP20 |
| ايه بي بي | ACS150-01E-02A4-2 | Direct same-power replacement |
Manual Version: V1.0 (based on ABB official ACS355 manual, adapted for ACS355-01E-02A4-2)
Effective Date: February 2026
Copyright: ABB Group, جميع الحقوق محفوظة