AVP-63 Single-phase Adjustable Dual-display Auto-reset Over/Under الجهد االكهربى + حامي التيار الزائد
ملحوظة: AVP-63 is a general model, not exclusive to one brand. Many electrical manufacturers in China produce this same design. It is a popular export DIN rail protection module.
يكتب: Single-phase 2P, جبل السكك الحديدية DIN, dual digital display (الجهد االكهربى + حاضِر), adjustable parameters, auto-reset protector
وظائف: حماية الجهد الزائد, حماية الجهد المنخفض, overload overcurrent protection, power restoration delay. It automatically closes after voltage returns to normal, no manual reset required.
Standard Technical Specifications (Mainstream Version)
الجهد المقنن: تيار متردد 230 فولت / 50هرتز (compatible with 220V mains)
التصنيف الحالي: Continuously adjustable from 1~80A, default 63A
Overvoltage Threshold: Adjustable 230~300V (factory default commonly 280V)
Undervoltage Threshold: Adjustable 140~210V (factory default commonly 160/170V)
Restoration Delay: Adjustable 1~400s, الافتراضي 30 ثانية
استهلاك الطاقة: ≤2W
الأبعاد الشاملة: تقريبا. 85×36×66 mm
تصاعد: 35مم السكك الحديدية DIN القياسية
الشهادات: Most versions carry CE; some domestic units can obtain CCC
رمز النظام المنسق: 8536500000 (switching protection electrical apparatus)
مبدأ التشغيل
- When voltage/current exceeds the set threshold → trip and cut off power immediately
- Fault cleared and voltage back within normal range → wait for configured delay then auto-close to restore power
- Dual screens display real-time voltage and output current; panel keys SET + UP/DOWN for parameter configuration
سيناريوهات التطبيق النموذجية
توزيع الطاقة السكنية, photovoltaic grid-tie side, small industrial control, communication power supplies, المعدات التجارية, overseas single-phase power distribution projects (widely used in Southeast Asia and Central Asia)
اختيار النموذج & ملاحظات الاستبدال
Domestic well-known auto-reset over/under voltage protectors (without current display): alternatives from Delixi, شينت, Tengen are available, but they lack current monitoring and adjustable dual-display interface
When replacing AVP-63, confirm three priorities: ① whether overcurrent protection is required ② whether local digital parameter setting is needed ③ whether auto-reset delay is mandatory
Firmware parameter ranges differ between manufacturers (a few versions support undervoltage limit down to 80V). Verify datasheet before purchase.
الأخطاء الشائعة
No display after power-up: live/neutral reversed, missing supply voltage
التعثر الكاذب المتكرر: thresholds set too close to normal voltage, large line surges
No power restoration after fault clears: delay set to maximum value, internal relay damaged
AVP-63 Panel Key Operation Steps (Mainstream Version, تعيين / ▲ / ▼ / Power Key)
Panel: Upper screen = Voltage V, Lower screen = Current A; 4 مفاتيح: تعيين, ▲ Up, ▼ Down, ⏻ Manual on/off key
⚠️ Safety Warning: Risk of electric shock during live commissioning; isolate upstream circuit breaker before maintenance
- Basic Operation Procedure
- Standby State: After power on, dual screens show real-time voltage and current
- Enter Parameter Menu: Long press SET for 3 ثواني, screen shows R1 (parameter code) to enter setting mode
- Switch Parameter Items: Short press SET to cycle through R1~R12
- Modify Value: When the target parameter flashes, press ▲ to increase, ▼ to decrease
- Confirm and Next Item: Short press SET to save and jump to next parameter
- Exit Setting: After all adjustments, long press SET for 3 seconds to exit, or wait 8~10 seconds for auto-save and exit
- Manual Close / رحلة: Short press ⏻ power key to directly control output on/off, without modifying protection thresholds
- Parameter Sequence (R1~R12, General Domestic Firmware)
| كود المعلمة | اسم المعلمة | نطاق قابل للتعديل | القيمة الافتراضية |
| ر1 | Power-on Delay (waiting time before closing after energization) | 1~500s | 10ق |
| R2 | Overvoltage Trip Value | 230~300V | 270V |
| R3 | Overvoltage Recovery Value (voltage must drop below this to enable reset) | 225~295V | 265V |
| R4 | Overvoltage Restoration Delay | 1~500s | 30ق |
| R5 | Overvoltage Action Delay (delay before tripping once overvoltage threshold is exceeded) | 0.1~ 30 ثانية | 1ق |
| R6 | Undervoltage Trip Value | 140~210V | 170V |
| R7 | Undervoltage Recovery Value | 145~215V | 175V |
| R8 | Undervoltage Restoration Delay | 1~500s | 30ق |
| R9 | Undervoltage Action Delay | 0.1~ 30 ثانية | 1ق |
| R10 | Overcurrent Protection Value | 1~63A | 63أ |
| R11 | Overcurrent Restoration Delay | 1~500s | 30ق |
| R12 | Overcurrent Action Delay | 0.1~ 30 ثانية | 1ق |
- Additional Functions (Password Lock on Some Versions)
Password item P19 appears at the end of menu; كلمة المرور الافتراضية 112. If password mismatch, only view access, modification locked
When locked, long pressing SET only allows browsing parameters; يدخل 112 to unlock editing
Some units support auto-reset toggle: P16, Con = Auto Reset, OFF = Manual Close (must press power key to restore after fault)
- Fault Code Indication
رأ: Overcurrent Trip
أوه: Overvoltage Trip
أول: رحلة انخفاض الجهد
After fault, power restores automatically when voltage/current returns to normal and delay expires. If manual mode is enabled, press ⏻ key to restore power.
- Quick Setting Example (General Household 220V)
- Long press SET for 3s to enter menu
- R2 Overvoltage: 270V; R6 Undervoltage: 170V
- R10 Overcurrent: 63أ
- R1 Power-on delay 10s, R4/R8/R11 restoration delay 30s
- Long press SET to exit, configuration completed
- Setting Troubleshooting
- SET no response: panel locked by password, faulty key, insufficient supply voltage
- Settings not saved: do not cut power before exit; wait for auto-exit or long press SET to confirm
- التعثر المتكرر: action delay R5/R9/R12 set too short, or thresholds set too close to normal voltage
تحذير للسلامة: Risk of electric shock during live testing. Professional function test is recommended using adjustable AC power supply (variac). Do NOT forcibly raise mains voltage for overvoltage test.
Testing sequence: التفتيش البصري & power-on self-test → Display & manual switching test → Parameter read-write verification → Protection function validation → Long-term load stability test
- Initial Power-on Check (On-site, No Special Instrument Required)
- تشغيل الطاقة, screens light up; upper screen shows voltage, lower screen shows current
- Use multimeter to measure input IN voltage, compare with protector reading: deviation normally ≤±5V. Larger deviation indicates faulty sampling circuit
- Measure output OUT with multimeter:
Normal closed state: IN and OUT voltage nearly equal
Tripped by protection: 0V at OUT
- Indicator definition:
POWER green ON: unit power supply normal
V red ON: Overvoltage fault (أوه)
<V red ON: Undervoltage fault (أول)
A red ON: Overcurrent fault (رأ)
- Manual switching test: short press ⏻ key, output turns on/off accordingly, key response normal
Abnormal conditions: black screen after power-up, garbled flashing, keys unresponsive, green power light ON but no output → likely damaged
- Parameter Read-write Verification (Check Mainboard & Memory Integrity)
- Long press SET for 3s to enter menu, can cycle through R1~R12 normally
- Values can be modified; after saving and exiting, re-enter menu to confirm parameters retained
- If password lock activated, modification allowed after correct password input; locked mode only supports viewing, which is normal
غير طبيعي: parameters revert after exit, menu jumps randomly → firmware / فشل الذاكرة
- Protection Function Validation (Precise Test, Variac Required)
1) Overvoltage Protection Test
- Connect adjustable power supply to AVP-63 input
- Set R2 overvoltage trip value to 270V
- Slowly increase input voltage. After exceeding threshold plus action delay, protector trips, shows OH, >V red light ON, output cuts off
- Reduce voltage below R3 overvoltage recovery value, wait for restoration delay, auto-close and restore power
2) Undervoltage Protection Test
- Set R6 undervoltage trip value to 170V
- Slowly reduce input voltage. Below threshold plus action delay, protector trips, shows UL, <V red light ON
- Raise voltage above R7 undervoltage recovery value, power restores automatically after delay
3) Overcurrent Protection Test (Adjustable Load / Current Source Required)
- Set R10 overcurrent value e.g. 20أ
- Gradually increase load current. When current exceeds threshold plus action delay, protector trips, shows OL, >A red light ON
- Current drops below recovery level, power restores automatically after delay
Acceptance criteria: actual action threshold matches configured value; no missing trip or spurious trip. Auto-restore after fault cleared and delay completed.
- Simple Field Test Without Variac (Emergency Site Check)
- Power cycle the unit, observe power-on delay: it closes after R1 configured time, not instantly
- Run under rated load for a period: current reading stable, no overheating, no random tripping
- Apply mild overload for a short time (safety priority) to verify OL trigger
⚠️ Do NOT test by forcing mains voltage high, risk of equipment burnout
- Long-term Stability & التفتيش البصري
No bulging, burn marks on enclosure; terminal blocks no discoloration or overheating
Readings stable under load, no random fault codes
No frequent false tripping: if OH/UL alarms persist with stable mains, either sensitive threshold setting or faulty sampling board
- Quick Diagnosis Summary Table
| ظاهرة | خاتمة |
| Power-on display normal, keys responsive, input/output voltage consistent, parameters saved | Basically functional |
| Trips at set thresholds, auto-restores after delay | Fully functional |
| Display normal, no output even after manual close | Internal relay failed / welded |
| Random OH/UL alarms with normal voltage, frequent tripping | Sampling circuit fault or improper threshold setting |
| شاشة سوداء, garbled display, keys fully unresponsive | Mainboard damaged |
| Modified parameters cannot be saved | Memory chip failure |
- ملاحظة تكميلية
AVP-63 cannot replace circuit breaker for short-circuit protection. It only provides over/under voltage and overload protection. Short-circuit protection must be provided by upstream circuit breaker. Upstream breaker must be retained as backup during testing.