Chint BZMJ0.4-20-3 Capacitor

CodeMeaning
بShunt Capacitor (Basic Category)
زImpregnant Type: Rapeseed Oil (Insulating and Heat-dissipating Medium)
MJDielectric Material: Metallized Polypropylene Film (Core of Self-healing Function)
0.4Rated Line Voltage: 0.4كيلو فولت (400V)
20Total Three-phase Capacity: 20kvar
3Three-phase Connection Mode

  • تفاصيل المنتج

Chint BZMJ0.4-20-3 is a self-healing low-voltage shunt capacitor designed for three-phase 400V systems with a capacity of 20kvar. It is mainly used for reactive power compensation in low-voltage power grids, to improve power factor and reduce power loss. Its core features include rapeseed oil impregnation + metallized polypropylene film dielectric, self-healing capability and built-in discharge resistor, with an operating temperature range of -25℃~+50℃.

  1. Full Model Interpretation
CodeMeaning
بShunt Capacitor (Basic Category)
زImpregnant Type: Rapeseed Oil (Insulating and Heat-dissipating Medium)
MJDielectric Material: Metallized Polypropylene Film (Core of Self-healing Function)
0.4Rated Line Voltage: 0.4كيلو فولت (400V)
20Total Three-phase Capacity: 20kvar
3Three-phase Connection Mode
  1. Core Technical Parameters (Authoritative Specifications)
المعلمةقيمةRemarks
الجهد المقنن400الخامس و (50هرتز)Line voltage, suitable for low-voltage distribution systems
Rated Capacity20kvar (ثلاث مراحل)Benchmark value of reactive power compensation capability
Rated Frequency50هرتز (60Hz Compatible)Standard frequency for industrial power grids
Capacity Tolerance-5%~+10%Complies with GB/T 12747.1 Standard
التصنيف الحالي28.9أCalculated by I=Q/(√3×U)=20/(1.732×0.4)
Capacitance Valueتقريبا. 199μF (ثلاث مراحل)Calculated by C=Q/(2πfU²)×10⁹
Insulation ClassSelf-healing Metallized FilmAutomatically restores insulation after local breakdown
Discharge PerformanceReduces from √2Un to ≤75V within 3 minutesBuilt-in discharge resistor ensures operational safety after power-off
Overcurrent Withstand Capability1.3 times rated current (Continuous Operation)Tolerates grid voltage fluctuations
Overvoltage Withstand Capability1.1 times rated voltage (Continuous Operation)Adapts to temporary grid voltage surges
Ambient Temperature-25℃~+50℃Universal for indoor and outdoor applications
Relative Humidity≤50% at 40℃; ≤90% at 20℃Moisture-proof requirements
Altitude≤2000mApplicable limit for plateau areas
فئة الحمايةIP20 (Metal Enclosure)Touch-proof, requires installation in distribution box
Executive StandardsGB/T 12747.1-2017 / اللجنة الانتخابية المستقلة 60831-1:2014Dual certification of national and international standards

 

  1. Core Product Features
  2. Self-healing Capability: When local breakdown occurs in the metallized film dielectric, the electrode metal layer evaporates instantly to form an insulating area, automatically restoring performance and extending service life.
  3. تصميم السلامة: Equipped with built-in discharge components, the residual voltage drops to a safe level within 3 minutes after power-off to prevent electric shock hazards.
  4. Reliable Insulation: The rapeseed oil impregnation system delivers excellent heat dissipation and insulation performance, suitable for harsh working conditions.
  5. Durable Structure: Metal enclosure combined with sealed structure resists mechanical impact, dust and moisture, ideal for industrial environments.
  6. High-efficiency Compensation: Low dissipation factor (tanδ≤0.0015) ensures high compensation efficiency and minimal self-power consumption.
  7. سيناريوهات التطبيق & Installation Specifications

سيناريوهات التطبيق:

0.4kV low-voltage distribution rooms, factory workshops and commercial building power distribution systems.

Occasions with concentrated inductive loads (motors, transformers, electric welders), to offset reactive power and improve power factor to ≥0.9.

Improve voltage quality, reduce line loss and transformer load.

Installation Points:

  1. Install in a ventilated and dry distribution box/cabinet free of corrosive gas, avoid direct sunlight exposure.
  2. Adopt three-phase star (Y) connection; connect phases A/B/C to corresponding phase lines respectively, and neutral line to N pole (إذا كان متاحا).
  3. Connect in series with specialized fuses/circuit breakers (32A recommended) to prevent expansion of short-circuit faults.
  4. Reserve a heat dissipation space of ≥15cm; maintain appropriate spacing when multiple capacitors are connected in parallel.
  5. Tighten terminal connections according to the torque specified by the manufacturer (usually 6~8N·m) to prevent loosening and overheating.
  6. Live operation is strictly prohibited; wait for at least 3 minutes after power-off before touching the terminals.
  7. Maintenance & استكشاف الأخطاء وإصلاحها

الصيانة الروتينية:

Conduct quarterly visual inspections: check for no bulging, oil leakage or deformation; ensure terminals are free from overheating and oxidation.

Measure operating temperature: enclosure temperature ≤55℃; if abnormal, investigate overcurrent or harmonic issues.

Test capacitance value: recommend replacement if deviation exceeds ±15%.

Record operating current and voltage to ensure they are within rated ranges.

Common Faults & الحلول:

Fault Phenomenonالأسباب المحتملةالحلول
Enclosure Bulging/Oil LeakageOvervoltage/overcurrent/high temperature/agingStop use immediately and replace with new products
Fuse BlowingInternal short circuit/excessive harmonics/wiring errorsInspect the circuit, eliminate faults and replace with fuses of the same specification
Poor Compensation EffectCapacity attenuation/loose wiring/controller malfunctionMeasure capacitance value, tighten terminals and inspect the compensation controller
Abnormal OverheatingPoor contact/high ambient temperature/overloadClean contacts, improve ventilation and reduce load
Discharge FailureDamaged discharge resistorConduct professional testing and replace the capacitor if necessary
  1. Selection & Replacement Recommendations

Selection Matching:

System Voltage: 0.4 series is preferred for 400V systems; BZMJ0.45-20-3 is recommended for 450V systems.

Capacity Calculation: Configure 70%~90% of the reactive power of the load, or estimate 20%~30% of the transformer capacity.

Alternative Models:

Same Series Upgrade: BZMJ0.45-20-3 (450V, suitable for scenarios with large voltage fluctuations)

Same Parameter Replacement: BSMJ0.4-20-3 (mineral oil impregnated, with similar performance)

Phase-separated Compensation: BZMJ0.4-20-3YN (independent three-phase adjustment, suitable for unbalanced loads)

  1. Safety Warnings
  2. The capacitor is an energy storage device; short circuit is strictly prohibited. Ensure complete discharge before installation.
  3. All wiring, maintenance and replacement operations must be performed in the power-off state.
  4. Using the capacitor beyond the specified temperature, voltage or humidity range will significantly shorten its service life and cause potential safety hazards.
  5. Scrap capacitors must be disposed of as hazardous waste and shall not be discarded at will (containing oil and metal components).