(رقم المادة: 175G5221)
VLT® Compact Starter MCD202 Compact بداية لينة
Short model code: MCD202015T4CV1
✅شرح الكود النموذجي
MCD202: MCD202 series, current limit start + built-in motor protection (different from MCD201; MCD201 only has voltage ramp, no built-in motor overload protection)
015: تصنيف 15 كيلوواط
ت: ثلاث مراحل
4: Main circuit voltage 200–440 VAC
CV1: التحكم في العرض 24 الخامس التيار المتناوب/تيار مستمر
Frame A, DIN rail mountable (specifications ≤30 kW support DIN rail mounting)
✅ المواصفات الكهربائية الأساسية
قوة المحرك المناسبة: 15 كيلوواط
التصنيف الحالي: 34 أ
Main supply: 3×200~440 VAC (-15% / +10%), 45–66 Hz
التحكم في العرض: 24 الخامس التيار المتناوب/تيار مستمر
Start mode: بداية محدودة الحالية + TVR timed voltage ramp soft stop
تجاوز مدمج: نعم; bypasses SCR after start completion to reduce heat loss
وظائف الحماية: الزائد للمحرك (default Class 10), over-temperature, phase sequence loss, خسارة المرحلة, SCR fault, motor PTC thermistor input
Starting capability: Standard 4×Ie for 6 ق; heavy-duty mode 4×Ie for 20 ق
طريقة التحكم: 2-سلك / 3-wire start-stop, إخراج التتابع
الوزن الصافي: 2.4 كجم; gross weight: 2.9 كجم
درجة حرارة التشغيل المحيطة: حتى 50 °C without derating
✅ التطبيقات النموذجية
مضخات المياه, المشجعين, الناقلات, الضواغط. Ideal for scenarios requiring current-limited starting to reduce grid inrush, without needing an external thermal relay.
✅ مقارنة السلاسل المتقاطعة & ملاحظات الاستبدال
- MCD202-015-T4-CV3: Control supply 110–440 VAC (CV3 version, الأكثر شيوعا). Not CV1; control circuits cannot be directly interchanged.
- MCD201-015-T4-CV1: Same power and voltage rating, but MCD201 has no built-in motor protection and fewer functions.
- Successor replacement: The MCD200 series is end-of-life. New projects are recommended to use the MCD600 series equivalent.
✅ Fault Quick Reference (Common for MCD202)
خطأ 1: الإفراط في درجة الحرارة
خطأ 2: الزائد للمحرك
خطأ 4: خسارة المرحلة / عدم التوازن الحالي
خطأ 5: Start timeout
خطأ 6: SCR fault
خطأ 10: PTC motor overheat
✅ Start and stop times are adjustable. The MCD202 uses rotary dip-knob adjustment (no menu display panel).
ملحوظة: The MCD201 does not support soft stop. Only the MCD202 features TVR voltage-type soft stop.
Parameter Ranges (Manual MG17C241)
- Start ramp-up time (Ramp Up): 2~20 s, الافتراضي للمصنع 10 ق
Operating logic: Current limiting is primary, voltage ramp is secondary; current ramp can also be enabled (2/5/15 s preset gears)
- Soft stop time (Soft Stop / Ramp Down): 2~20 s by gear selection; can also be set to soft stop disabled for direct power-off shutdown (الافتراضي للمصنع: soft stop disabled)
طريقة التعديل
Four adjustment knobs on the front face:
مقبض الباب 1: المحرك المقدر الحالي
مقبض الباب 2: بدء الحد الحالي
مقبض الباب 3: Start ramp-up time (Ramp Up)
مقبض الباب 4: Soft stop ramp-down time (Soft Stop)
Brief Application Guidance (Most common for pump applications)
المشجعين: 5–10 s start time; soft stop is usually not required
Centrifugal pumps for water hammer suppression: Enable soft stop, set 8–15 s soft stop time
Soft stop principle: TVR timed voltage ramp-down. It is not variable-frequency deceleration and cannot provide precise constant-speed slowdown; it is only used to suppress water hammer and light-load buffering.
Limitation Reminders
This compact soft starter uses stepped gear adjustment instead of continuous stepless fine-tuning.
Soft stop only activates after a stop command. Once full-speed bypass is closed, the SCRs are bypassed and no longer regulate voltage.
The start timeout protection must be set in coordination; its value must be longer than the actual start time, otherwise Err5 start timeout will trigger.
MCD202-015-T4-CV1 Start / Stop Time Adjustment Precautions
Core premise: This unit uses TVR timed voltage ramp start/soft stop + تجاوز مدمج. It is not a VFD. SCRs only work during the start ramp and soft stop ramp. After bypass pull-in at full speed, thyristors are out of circuit.
- Start Ramp-Up Time (Ramp Up)
- Adjust the current limit knob together with ramp time; do not only adjust the time setting.
The MCD202 operates in current-limit priority mode. Even if ramp time is set to 20 ق, a low current limit may prevent the motor from accelerating and trigger Err5 (بدء المهلة). The ramp only defines the voltage change profile; the current ceiling is locked by the current limit knob.
Field tip: Set current limit first to guarantee rotation, then configure ramp time. For heavy-duty conveyors and compressors, raise current limit before extending start time.
- Start timeout protection (Err5) must be longer than the actual acceleration time.
Start timeout range: 2~20 s. Timeout setting actual time to reach full speed, leave a margin of 2–5 s. أ 15 s ramp paired with a 10 s timeout will almost certainly trip.
- Gear-based adjustment, not continuous stepless regulation
Knob settings are discrete preset steps, not smooth fine adjustment. Fixed range: 2~20 s, الافتراضي للمصنع 10 ق.
- Longer start times extend SCR heating; restrict starts per hour.
Long ramp times combined with high current limits increase thyristor heat generation. For frequent start-stop applications, avoid setting maximum 20 s ramp, otherwise Err1 over-temperature occurs easily. The built-in bypass reduces temperature at full speed, but the SCRs bear load and heat during acceleration.
- Differentiate between loaded and light-duty starting
Light-duty fans / مضخات الطرد المركزي: 5–10 s is sufficient. Excessively long ramps may cause low-speed stall and sustained high current.
سيور ناقلة, screw feeders, مضخات للخدمة الشاقة: Ramp can be extended moderately, paired with higher current limit.
- Soft Stop Time (Ramp Down, MCD202 exclusive; unavailable on MCD201)
- Soft stop ≠ VFD deceleration; it only reduces voltage gradually.
Constant-speed deceleration cannot be achieved. Torque drops with voltage reduction, and the motor slows by load inertia. For high-inertia fans, even 20 s soft stop may still result in fast coasting; do not expect precise speed control.
- Factory default = soft stop disabled. When disabled, the bypass opens and the motor coasts freely.
Soft stop is only enabled for pumps requiring water hammer protection. Soft stop is unnecessary for most fan applications.
Critical point: The bypass contact only opens after soft stop completes and voltage falls to a low level. SCRs remain active and generate heat throughout the soft stop sequence.
- Do not use long soft-stop times for low-inertia loads
الناقلات الصغيرة, valve actuators and similar low-inertia loads will draw sustained low-voltage high current under long soft-stop settings, leading to motor overload Err2 or soft starter overheat Err1.
- Emergency stop overrides soft stop logic
External emergency stop cuts the circuit directly and skips the soft stop ramp. Soft stop only responds to normal stop commands.
- المأزق المشترك: Bypass Operation Logic
Start sequence: Start command → SCR voltage ramp → full voltage reached → built-in bypass relay closes, SCRs exit operation. The configured start time only applies before bypass closure.
Stop sequence: Stop command → bypass contact opens first, switching back to SCR control before soft stop ramp begins. If bypass contacts are welded or poorly contacting, soft stop fails immediately and faults occur.
أعراض: Soft stop configured but motor cuts off instantly when stopping. Prioritize inspecting the bypass contactor.
- Timing & Start-Stop Interval
A fixed 2 s interlock delay is built between successive starts to dissipate motor back EMF. Do not program extremely short start-stop pulses in PLC, repeated rapid cycling will trigger main-circuit faults.
Do not send a new start command while the motor is still coasting down. The MCD202 does not support flying start and will see severe inrush current.
- Coordination with Motor Protection (CV1 variant has built-in motor protection)
حماية المحرك الزائد (فصل 10) accumulates thermal capacity based on operating current:
Long start ramps with sustained low-speed high current build thermal load and may trip Err2 overload during acceleration.
The motor rated current knob must match the motor nameplate rating, otherwise all protection thresholds are invalid.
- Control Supply Variant Note (Your unit CV1: 24 الخامس التيار المتناوب/تيار مستمر)
Start-stop logic is unaffected by the CV1 supply. لكن: Loss of the 24 V control supply disables soft stop, and the motor shuts down directly without ramp.
- Recommended Field Commissioning Sequence
- Set motor rated current to match the motor nameplate
- Set current limit to guarantee successful loaded start
- Configure start ramp-up time
- Set start timeout = ramp time + هامش الأمان
- Enable soft stop only for water hammer control; set to soft-stop off for other loads
- Test start-stop under no load, observe indicator timing and monitor for Err1/Err2/Err4/Err5
- Fault Mapping
Err5 Start timeout: Current limit too low OR ramp too long OR timeout threshold set too small
Err1 Over-temperature: ركوب الدراجات بشكل متكرر, excessively long start/stop ramps, continuous SCR heating
Err2 Motor overload: Long duration of low-speed high current causing thermal accumulation
دانفوس Soft Starter Full Model List & Material Order Codes (Mainstream 400V for China market, T4 = 200–440 VAC)
Model coding rules for MCD201 / MCD202
CV1: 24 V AC/DC control supply (Your MCD202-015-T4-CV1 is CV1)
CV3: 110–240 VAC / 380–440 VAC control supply (most widely ordered)
T4 = 200–440 V; T6 = 200–575 V
MCD201: Voltage ramp start only, no built-in motor overload protection, no soft stop
MCD202: بداية محدودة الحالية + TVR soft stop + complete motor protection (series you are using)
حالة: MCD200 (MCD201/MCD202) is phased out. New projects select MCD600.
- MCD202 (With protection + توقف ناعم, including your model)
| Power @400V | التصنيف الحالي | النموذج الكامل | Material Order No. |
| 7.5 كيلوواط | 18 أ | MCD202-007-T4-CV1 | 175G5210 |
| 7.5 كيلوواط | 18 أ | MCD202-007-T4-CV3 | 175G5211 |
| 11 كيلوواط | 24 أ | MCD202-011-T4-CV1 | 175G5212 |
| 11 كيلوواط | 24 أ | MCD202-011-T4-CV3 | 175G5213 |
| 15 كيلوواط | 34 أ | MCD202-015-T4-CV1 | 175G5221 (your part) |
| 15 كيلوواط | 34 أ | MCD202-015-T4-CV3 | 175G5222 |
| 18.5 كيلوواط | 39 أ | MCD202-018-T4-CV1 | 175G5224 |
| 18.5 كيلوواط | 39 أ | MCD202-018-T4-CV3 | 175G5225 |
| 22 كيلوواط | 48 أ | MCD202-022-T4-CV1 | 175G5227 |
| 22 كيلوواط | 48 أ | MCD202-022-T4-CV3 | 175G5228 |
| 30 كيلوواط | 60 أ | MCD202-030-T4-CV1 | 175G5230 |
| 30 كيلوواط | 60 أ | MCD202-030-T4-CV3 | 175G5231 |
| 37 كيلوواط | 75 أ | MCD202-037-T4-CV1 | 175G5233 |
| 37 كيلوواط | 75 أ | MCD202-037-T4-CV3 | 175G5234 |
| 45 كيلوواط | 88 أ | MCD202-045-T4-CV1 | 175G5236 |
| 45 كيلوواط | 88 أ | MCD202-045-T4-CV3 | 175G5237 |
| 55 كيلوواط | 105 أ | MCD202-055-T4-CV1 | 175G5239 |
| 55 كيلوواط | 105 أ | MCD202-055-T4-CV3 | 175G5240 |
| 75 كيلوواط | 140 أ | MCD202-075-T4-CV1 | 175G5214 |
| 75 كيلوواط | 140 أ | MCD202-075-T4-CV3 | 175G5215 |
| 90 كيلوواط | 170 أ | MCD202-090-T4-CV1 | 175G5217 |
| 90 كيلوواط | 170 أ | MCD202-090-T4-CV3 | 175G5218 |
| 110 كيلوواط | 200 أ | MCD202-110-T4-CV1 | 175G5220 |
| 110 كيلوواط | 200 أ | MCD202-110-T4-CV3 | 175G5242 |
7.5~30 kW: DIN rail mountable; 37 kW and above: base mount only
- MCD201 (Economy version, no built-in motor protection, no soft stop)
| قوة | حاضِر | النموذج الكامل | رقم المادة. |
| 7.5 كيلوواط | 18 أ | MCD201-007-T4-CV3 | 175G5165 |
| 15 كيلوواط | 34 أ | MCD201-015-T4-CV3 | 175G5166 |
| 18.5 كيلوواط | 39 أ | MCD201-018-T4-CV3 | 175G5167 |
| 22 كيلوواط | 48 أ | MCD201-022-T4-CV3 | 175G5168 |
| 30 كيلوواط | 60 أ | MCD201-030-T4-CV3 | 175G5170 |
| 37 كيلوواط | 75 أ | MCD201-037-T4-CV3 | 175G5171 |
| 45 كيلوواط | 88 أ | MCD201-045-T4-CV3 | 175G5172 |
| 55 كيلوواط | 105 أ | MCD201-055-T4-CV3 | 175G5173 |
| 75 كيلوواط | 140 أ | MCD201-075-T4-CV3 | 175G5174 |
| 90 كيلوواط | 170 أ | MCD201-090-T4-CV3 | 175G5175 |
| 110 كيلوواط | 200 أ | MCD201-110-T4-CV3 | 175G5176 |
- MCD100 (Micro economy range, 1.5~11 kW, لا يوجد تجاوز مدمج)
For small fans and pumps, حجم صغير, no internal bypass
MCD100-001 (1.5 كيلوواط / 3 أ) 175G4001
MCD100-007 (7.5 كيلوواط / 15 أ) 175G4005
MCD100-011 (11 كيلوواط / 25 أ) 175G4009
- MCD600 (New generation flagship, direct replacement for MCD202, graphical menu, وظائف محسنة)
Sample code: MCD600-xxxB-T4-S1X00CV2; material codes start with 132H. Supports flying start, pump cleaning logic, extended protection and communication options. Power range 7.5~1400 kW
Equivalent replacement for your MCD202-015-T4-CV1 (15 كيلوواط /34 أ): MCD600-0034B-T4-S1X00CV1 (CV1 = 24 V control supply)
- Common MCD200 Series Spare Part Order Codes
MCD200 remote operator panel: 175G9004
وحدة الاتصالات Profibus: 175G9040
وحدة مودبوس RTU: 175G9041
EtherNet/IP module: 175G9043
ملاحظات تكميلية
- T6 versions (200–575 V) follow the same naming rule; replace T4 with T6, with separate material numbers.
- CV1 and CV3 control supplies are not interchangeable, a frequent site mistake.
- MCD202 includes built-in bypass; MCD600 can be ordered with or without bypass.
- End-of-life notice: MCD201/MCD202 are stock-only. New projects specify MCD600.