AH 16 أكون 1 0 N 5A
AH: AH500 high-end modular PLC مسلسل
16: Total I/O points = 16 نقاط
أكون: Digital Input module
1: مدخل تيار مستمر 24 فولت
0: No output channels
ن: No output type
5أ: Removable terminal block (JIS terminal)
📋 Core Technical Specifications
Points: 16-point DC24V Digital Input (من)
جهد الإدخال: تيار مستمر 24 فولت, المدخلات الحالية: 5أماه
نوع الإدخال: NPN/PNP compatible (Sink/Source universal). No hardware rewiring required to switch between sink/source أجهزة الاستشعار.
ميزة: Hot-swap capable, modules can be replaced without system power-off for convenient maintenance.
Status Indicator: Independent LED status indicator per channel
استهلاك الطاقة: 0.1دبليو, الأعلى. 1.9W for the module
أبعاد (الارتفاع × العرض × العمق): 110 × 35 × 103 مم
تصاعد: AH500 local backplane / expansion backplane; رقمي, analog and motion modules can be mixed on the same backplane.
برامج البرمجة: ISPSoft
📌 Product Features
- Hot Swap: Modules can be installed/removed while the system remains powered on to minimize production downtime.
- Universal Input: Compatible with 2-wire / 3-wire proximity sensors, أجهزة الاستشعار الكهروضوئية, مفاتيح الحد, pushbuttons and other 24V sensors.
- كتلة المحطة القابلة للإزالة: The terminal strip can be detached as a whole, simplifying wiring construction and on-site troubleshooting.
- High-integration AH500 Platform: Can be paired with AH-series CPUs, AH16ANxx output modules, AD/DA analog modules and EtherCAT motion modules for mixed expansion.
🏭 Typical Application Scenarios
ماكينات التعبئة والتغليف, textile equipment, آلات الطباعة, معالجة المياه, automated production lines and machine tool I/O signal acquisition. Used to collect signals from limit switches, أجهزة الاستشعار الكهروضوئية, مفاتيح القرب, valve feedback and pushbutton DI signals.
🔁 Cross-series Comparison & الاختيار البديل
AH16AM10N-5A: 16-point DC24V DI with removable terminal block
AH32AM10N-5B: 32-point DC24V DI with DB37 connector
AH16AN01P-5A: 16-point PNP transistor DO output module (for matching use)
⚠️ Troubleshooting Guide
- Input LED not lit: Check DC24V power supply, S/S common terminal wiring of sensors and verify NPN/PNP matching.
- Flickering signals: Caused by unshielded sensor cables, voltage drop or loose terminals.
- Module not recognized: Poor backplane contact or mismatched module firmware version. Hot-swap function requires AH500 CPU firmware that supports hot swapping.
دلتا AH16AM10N-5A Application Cases (AH500 16-point DI Module)
The AH16AM10N-5A is a DC24V digital input expansion module for the AH500 PLC system. Its core function is to acquire switching signals from field sensors, مفاتيح الحد, pushbuttons and valve feedback. Hot swap and NPN/PNP universal compatibility are key advantages for site selection. Below are 5 practical engineering cases.
قضية 1: 3D Printing Equipment (Classic Application of AH16AM10N-5A)
System Hardware List
AHCPU530-EN (AH500 CPU)
AHPS05-5A Power Supply + AHBP08M1 Backplane
AH16AM10N-5A ×1 (DI signal acquisition)
AH16AN01T-5A Transistor DO Output Module
AHMC20A DMCNET motion module, temperature control module
Signal Assignment for AH16AM10N-5A (16 Points)
- X0~X3: Home position, positive/negative hard limit for 3 محاور
- X4~X7: Print head abnormal temperature, filament break detection, low material sensor
- X8~X11: باب الأمان, توقف الطوارئ, reset and start pushbuttons
- X12~X15: Platform in-position, material bin presence, fan feedback, alarm reset
Solution Highlights
NPN/PNP compatibility supports mixed use of photoelectric and proximity sensors from different brands.
Hot-swap capability allows equipment maintenance without full machine power-off.
Collected DI signals are sent to AH500 to realize axis linkage control together with the motion module.
غاية: Collect safety signals, position sensors and material detection switches as interlock conditions for motion control.
قضية 2: Food Packaging Machine / Vertical Form-Fill-Seal Machine
هندسة النظام
AH500 CPU + AH16AM10N-5A + AH16AN01P Output Module + دلتا سيرفو + DOP HMI
16-Point DI Assignment
أجهزة الاستشعار الكهروضوئية: Bag presence detection, material falling detection
Proximity sensors: Film feeding in-position, cutter home position, gripper home position
Switches: باب الأمان, توقف الطوارئ, manual/auto selector, start/stop pushbuttons
Feedback signals: Solenoid valve action feedback, air pressure switch
قيمة التطبيق
Packaging machines are equipped with large quantities of sensors. The removable terminal block enables batch wiring for high efficiency. Faulty modules can be hot-swapped during production to reduce downtime. DI signals implement interlock logic: cutter movement is disabled if the safety door is open.
قضية 3: Water Plant / معالجة مياه الصرف الصحي (أتمتة العملية)
AH500 projects in Fujian and Jiangxi water plants deploy multiple AH16AM10N-5A modules to collect signals for pump rooms, chemical dosing rooms and filter tanks.
الإشارات المجمعة
Pump running feedback and fault dry-contact signals
Valve open / closed position feedback (electric butterfly valves)
High/low level float switches, differential pressure switches
Local control cabinet pushbuttons, manual/auto selector switches
Solution Features
Field signals are widely dispersed; extension cables for backplane can reach up to 100m.
Multiple AH16AM10N-5A modules expand DI points to acquire massive pump and valve status data.
Signals are transmitted via Ethernet from AH500 to DIAView SCADA for remote pump room monitoring.
قضية 4: Automotive Interior Assembly Line (Multi-station Automation)
نظرة عامة على المشروع: Dashboard assembly line with 26 workstations. AH500 acts as the main controller. Each workstation uses one AH16AM10N-5A to collect workstation sensor signals.
DI Acquisition Content
Pallet in-position, workpiece presence photoelectric sensors
Cylinder limit switches, fixture clamp/release feedback
Safety light curtain signals, توقف الطوارئ, workstation request signals
المزايا
NPN/PNP universal design allows mixed sensors from multiple suppliers without hardware modification. Module LED indicators speed up fault point location. Multiple AH16AM10N-5A modules expand I/O capacity, and one AH500 can control multiple assembly stations.
قضية 5: Warehouse Stacker / Palletizing Robot
تكوين الأجهزة
AH500 motion CPU + AH16AM10N-5A DI Module + AH-series motion modules
Signal Acquisition
Origin and overtravel limit for stacker travelling, lifting and fork axes
Cargo detection photoelectric sensor, fork occupancy detection
دائرة السلامة: توقف الطوارئ, باب السلامة, anti-collision sensor
Manual operation box pushbutton signals
منطق التحكم
AH16AM10N-5A collects limit and safety signals as hardware interlock for motion commands. Servo motion output is immediately cut off once limits are triggered to prevent stacker rail collision.
✅ Common Advantages of AH16AM10N-5A in Projects
- NPN/PNP Universal: Mixed sensors from different brands in projects without rewiring.
- Hot Swap: Maintain production equipment without shutdown, the core selling point of AH500 modules.
- Removable Terminals: Pre-wiring in control cabinets improves on-site installation and commissioning efficiency.
- 16 DI points per module with moderate capacity, ideal for I/O expansion of small & medium workstations and standalone machines. Additional modules can be mounted on AH backplanes for more points.
📌 Typical Configuration Reference (Standalone Machine Scheme)
AHCPU510-EN + AHPS05-5A + AHBP04M Backplane + AH16AM10N-5A + AH16AN01P-5A
طلب: Standalone automation, أدوات الآلة, آلات التعبئة والتغليف, special-purpose machinery
🔎 On-site Commissioning Tips for Project Deployment
- S/S common terminal of sensors: Connect 24V for NPN sensors, connect 0V for PNP sensors. No DIP switch adjustment required on AH16AM10N-5A.
- Use shielded cable with grounding for long sensor wiring to prevent DI signal flickering.
- Hot-swap function requires compatible firmware version of AH500 CPU. Old firmware needs upgrading to support live module replacement.
Delta AH500 Series Digital I/O Module Full List (Same Series as AH16AM10N-5A, All Hot-Swap Supported)
شرح اللاحقة
5أ: Removable detachable terminal block (الأكثر شيوعا, same terminal type as AH16AM10N-5A)
5ب: DB37 pin connector
5ج: IDC header
- Digital Input Modules AM (من)
| نموذج | Points | مواصفة | واجهة |
| AH16AM10N-5A | 16 نقاط | DC24V DI, NPN/PNP compatible | Removable terminal |
| AH16AM30N-5A | 16 نقاط | AC120~240V AC input | Removable terminal |
| AH32AM10N-5A | 32 نقاط | DC24V DI, NPN/PNP compatible | Removable terminal |
| AH32AM10N-5B | 32 نقاط | DC24V DI, NPN/PNP compatible | DB37 connector |
| AH32AM10N-5C | 32 نقاط | DC24V DI, NPN/PNP compatible | IDC header |
| AH64AM10N-5C | 64 نقاط | DC24V DI, NPN/PNP compatible | IDC header |
| AH16AR10N-5A | 16 نقاط | DC24V High-speed interrupt DI | Removable terminal |
- Digital Output Modules AN (يفعل)
| نموذج | Points | مواصفة | واجهة |
| AH16AN01R-5A | 16 نقاط | Relay output 2A | Removable terminal |
| AH16AN01T-5A | 16 نقاط | NPN transistor 0.5A | Removable terminal |
| AH16AN01P-5A | 16 نقاط | PNP transistor 0.5A | Removable terminal |
| AH16AN01S-5A | 16 نقاط | TRIAC AC output | Removable terminal |
| AH32AN02T-5A | 32 نقاط | NPN transistor 0.1A | Removable terminal |
| AH32AN02T-5B | 32 نقاط | NPN transistor 0.1A | DB37 connector |
| AH32AN02T-5C | 32 نقاط | NPN transistor 0.1A | IDC header |
| AH32AN02P-5A | 32 نقاط | PNP transistor 0.1A | Removable terminal |
| AH32AN02P-5B | 32 نقاط | PNP transistor 0.1A | DB37 connector |
| AH32AN02P-5C | 32 نقاط | PNP transistor 0.1A | IDC header |
ثالثا. Mixed I/O Modules AP (Integrated DI+DO)
| نموذج | Points | مواصفة | واجهة |
| AH16AP11R-5A | 8د + 8 ج | من:تيار مستمر 24 فولت / يفعل:Relay 2A | Removable terminal |
| AH16AP11T-5A | 8د + 8 ج | من:تيار مستمر 24 فولت / يفعل:NPN transistor 0.5A | Removable terminal |
| AH16AP11P-5A | 8د + 8 ج | من:تيار مستمر 24 فولت / يفعل:PNP transistor 0.5A | Removable terminal |
Supporting AH500 Basic System Modules (Full PLC Assembly, Non-DIO)
CPU Units
AHCPU510-EN, AHCPU520-EN, AHCPU530-EN, AHCPU540-EN, AHCPU550-EN, AHCPU560-EN2 (High-end Redundant CPU)
Power Supply Modules
AHPS05-5A (Standard Power Supply), AHPS15-5A (High-power Power Supply)
Backplanes (محلي / Expansion Backplane)
AHBP04M1, AHBP06M1, AHBP08M1 (Standard Backplane)
AHBP04MR1-5A / AHBP06ER1-5A / AHBP08ER1-5A (Redundant Backplane)
Other A500 Special Modules (التناظرية, Motion, تواصل)
- Analog AIO: AH04AD, AH08AD, AH04DA, AH08DA, AH04PT, AH04TC RTD / Thermocouple Modules
- High-speed Counter: AH02HC-5A 2-channel high-speed counter
- Motion Module: AHMC20A (DMCNET motion)
- وحدة الاتصالات: AH10SCM (Serial port), AH10EN (إيثرنت), AH10DNET DeviceNet
✅ Quick Selection Guide
- Standalone machines commonly use AH16AM10N-5A (من) + AH16AN01P/T-5A (يفعل)
- Large I/O quantity with DB37 wiring in control cabinets: select suffix 5B
- Centralized I/O cabinet with ribbon cable wiring: select suffix 5C IDC header
- AC sensor input: AH16AM30N-5A
- Mixed small amount DI+DO to save backplane slots: AH16AP series
المقاولين,قاطع الدائرة,الاستشعار,التشفير,بلك,محول























NH42-63-318x560.png)