(Often mislabeled as Hoerbiger) نوع المنتج: Seismic velocity vibration transmitter (2-wire 4-20mA, loop-powered). Used for vibration monitoring of bearing housings, مضخات, fans and motor casings. ماركة: Metrix. NOT Hoerbiger. This transmitter is frequently supplied together with Hoerbiger components in compressor packages, hence the common confusion. ✅ Model Code Breakdown ST5484E-121-010-00 ST5484E: Series base model 121: ...

  • تفاصيل المنتج

(Often mislabeled as Hoerbiger)

نوع المنتج: Seismic velocity vibration transmitter (2-wire 4-20mA, loop-powered). Used for vibration monitoring of bearing housings, مضخات, fans and motor casings.

ماركة: Metrix. NOT Hoerbiger. This transmitter is frequently supplied together with Hoerbiger components in compressor packages, hence the common confusion.

✅ Model Code Breakdown ST5484E-121-010-00

ST5484E: Series base model

121: Code for measuring range, frequency response and housing material

010: Full scale 10 مم/ثانية (RMS, vibration velocity)

00: موصل / mounting option: 2-core flying lead, no auxiliary dynamic acceleration output (pure 2-wire 4-20mA)

Signal definition: 4أماه = 0 مم/ثانية; 20أماه = 10 mm/s RMS

📌 Key Technical Specifications

غرضالمعلمة
MeasurandVibration velocity (RMS)
يتراوح0~10 mm/s
الإخراج2-wire 4~20mA, loop powered
مزود الطاقة18~28 VDC
استجابة التردد2 Hz ~ 1 كيلو هرتز (standard filter for -121 شفرة)
السكن303 الفولاذ المقاوم للصدأ (316SS optional)
Mounting thread1/4-28 UNF
درجة حرارة التشغيل-40℃ ~ +100℃
حمايةFully potted sealed construction
الحماية من الانفجارEx d flameproof / Ex ia intrinsically safe available (certificate to be verified for base model)

🧩 Applications

Vibration monitoring on bearing housings of fans, centrifugal pumps, المحركات, gearboxes and reciprocating compressors. 4-20mA signal connects directly to PLC/DCS AI analog input channels for vibration trending, alarm and interlock. Widely used in petrochemical, air separation and power plants.

📎 Compatible Accessories

8200 conduit elbow (mandatory for hazardous area explosion-proof installation)

7084 flange mounting adapter (thread to flat flange conversion)

Shielded twisted pair instrument cable (2-core shielded)

⚠️ Selection & ملاحظات الاستبدال

  1. امتياز: ST5484E (velocity 4-20mA transmitter) vs SW5484E (version with relay switch)
  2. Three critical parameters to match for replacement: full scale mm/s, frequency response code, wiring configuration (with/without dynamic acceleration output)
  3. البديل المحلي: Integrated piezoelectric vibration velocity transmitters. Explosion-proof certificate, mounting thread and frequency response curve must be matched.

📦 HS Customs Code Reference

90262090 (Transmitters for measuring / testing physical quantities such as pressure, تدفق, level and vibration)

Metrix ST5484E-121-010-00 Vibration Transmitter Troubleshooting Checklist

ملائم: 2-wire 4~20mA, 0~10mm/s RMS, ST5484E series. Three fault categories: لا يوجد إخراج, Current drift, Signal noise/jitter

Precaution for safety: Follow explosion protection rules in hazardous areas. Power off before wiring inspection. Avoid short-circuit loop tests to prevent transmitter / AI module damage.

Pre-check (Perform first for all faults)

  1. Verify loop power supply: 18~28VDC (measure voltage directly at transmitter terminals, not only power cabinet reading)
  2. Polarity check: Reversed polarity normally does not burn the 2-wire unit, but some AI modules cannot read reversed signals. الأسلاك: + to power positive, to AI module input
  3. Loop total resistance check: AI module input resistance + cable resistance. Total load ≤500Ω (typical maximum load for ST5484E)
  4. التفتيش البصري: Damaged housing, condensation ingress, cracked cable jacket, corroded terminals. Loose mounting thread introduces false vibration readings.
  5. قاعدة التركيب: Rigid mounting required. Gaskets / soft pads attenuate vibration and cause inaccurate readings. Clean rust on mating surface.
  6. بيئة: Confirm temperature within -40~100℃. Strong cables for motors / VFDs routed in parallel nearby easily induce interference.

عيب 1: لا يوجد إخراج (Current locked at ~0mA / below 3.8mA)

خطوات استكشاف الأخطاء وإصلاحها

  1. خارج السلطة, check loop continuity

Disconnect wiring at both ends of transmitter. Do NOT judge transmitter health by measuring resistance of piezoelectric sensor with multimeter; static resistance is not fixed.

Cable check: Open circuit in 2 signal cores; shield must not short to signal conductors.

  1. Standalone loop test (disconnect from DCS/PLC AI)

Simple test: 24VDC power supply in series with multimeter mA range directly connected to transmitter, bypass DCS.

Current ≈4mA: Transmitter healthy → fault on downstream DCS AI channel, terminals or scaling configuration.

Current <3.8mA or 0mA: Fault in transmitter / مزود الطاقة / كابل.

  1. Short circuit inspection

Short between signal cores brings loop current to zero; core-to-earth short also pulls down current.

  1. Power voltage drop

Long cable creates voltage drop; terminal voltage below 18VDC will fail to power up transmitter.

  1. Transmitter hardware failure

Damaged piezoelectric element or potting water ingress. Tapping transmitter housing produces no mA change: sensor likely failed.

Quick Conclusion

✅ 4mA present in standalone 24V test: Transmitter OK, fault in AI channel or wiring

❌ Still no current in standalone test: Cable open circuit / Transmitter failure

عيب 2: Current drift (Slow gradual rise/fall, no jitter, zero offset)

أعراض: Static equipment, current slowly deviates from 4mA; vibration unchanged but reading creeps up or down over time

  1. Zero drift classification

Thermal drift: Slow offset during equipment heat-up / cool-down (inherent minor effect for piezoelectric sensors; large drift is abnormal)

Loose mounting: Unstable vibration transfer due to loose bolts; slow variation with thermal expansion. Retighten to specified torque.

  1. Loop load variation

Degraded AI module or oxidized terminal contact resistance changes loop voltage drop and causes mA drift; clean terminals.

  1. Moisture ingress inside transmitter

Seal failure, moisture on PCB. Drift worsens progressively, later accompanied by jitter or total loss of output. Focus inspection on cable entry seal.

  1. Incorrect DCS scaling

This model maps 0~10mm/s to 4~20mA. Wrong DCS range (على سبيل المثال. 0~20mm/s) causes apparent reading drift while raw signal is normal.

  1. Mechanical resonance / base resonance

Thin weak mounting bracket resonates on stationary equipment and generates false vibration. Reinforce bracket rigidity.

  1. Long-term aging

Piezoelectric element aging after years of service leads to persistent zero offset.

Quick Conclusion

خارج السلطة, cool down fully then restart:

Zero returns close to 4mA: Thermal effect / mounting resonance suspected

Zero remains offset: Poor terminal contact / Transmitter moisture & aging

عيب 3: Signal noise & jitter (Fast current fluctuation, stable actual machine vibration)

أعراض: Stable machine vibration, random mA jumps, noisy DCS trend curve

  1. درع & التأريض (Most frequent root cause)

✅ Correct practice: Shield single-point earthed at DCS cabinet end. Shield at transmitter end must be floating. Dual-point earth creates ground loop and power frequency interference.

Shield touching signal conductors or multiple earth points is top cause of jitter.

  1. Cable routing

Instrument cable laid parallel with VFD / motor power cables. Separate by ≥30cm, cross at 90° where crossing required.

Use 2-core shielded instrument cable, ordinary unshielded cable is not acceptable.

  1. Power supply ripple

Degraded 24V DC supply with high ripple. Add filter at power side or replace regulated power supply.

  1. Ground potential difference (Ground loop)

Transmitter mounted on motor casing; motor frame and cabinet earth have potential difference, generating ground loop current and severe signal jitter. Isolate casing earth.

  1. Mechanical causes

Loose bolts, sand/rust on mating surface causing unstable sensor contact. Clean mounting face and tighten to torque.

  1. DCS AI filter setting

Too short AI input filter time passes interference directly to display. Increasing software filter only masks symptom; hardware interference must be resolved first.

  1. Transmitter hardware defect: PCB solder joint intermittency, random jitter under vibration.

Quick Conclusion

Temporarily disconnect shield earth at cabinet:

Jitter significantly reduced: Ground loop / wrong shield earthing

Jitter unchanged: Power cable interference / supply ripple / transmitter internal fault

Field Quick Test Procedure (Recommended sequence)

  1. Measure DC voltage at transmitter terminals (Confirm 18~28V)
  2. Disconnect DCS side, test transmitter with standalone 24V supply + mA meter
  3. Lightly tap transmitter housing and monitor mA reading:

mA rises smoothly when tapped, falls on release: Sensor basically functional

No mA response when tapped: Sensor failed

Erratic jumping on tapping: الأسلاك فضفاضة / internal bad solder joint

  1. Check shield earthing and confirm single-point earth
  2. Check mounting bolt tightness

Fault Reference Table

أعراضLikely Root Cause
Locked at 4mA on power-up, no response to tappingFailed sensor / Cable open circuit
Slow drift, more obvious with temperature changeMoisture ingress, loose mounting, excessive thermal drift
Fast random jitter with stable machine vibrationDual-point shield earthing, power cable interference, ground loop
Current stuck at 20mA and will not resetShorted signal wires, sensor damage, overload from heavy shock

Important Cautions

  1. Do not apply high voltage to transmitter. Do NOT use megger to test signal cable (will damage piezoelectric element)
  2. This transmitter measures housing vibration, NOT shaft vibration (shaft vibration uses eddy current probes)
  3. For hazardous area, power down equipment before opening cover or disassembly; comply with explosion protection requirements.