MITA-Teknik 9780351 Wind Power Dedicated Combined Module - المقاولين,قاطع الدائرة,العاكس للطاقة الشمسية,عداد كهرباء,البطاريات الشمسية

ويشات: +86-13184948252 واتس اب: 0086-13811255435 بريد إلكتروني: كينت@bestcontactor.com

عن اتصال |

MITA-Teknik 9780351 Wind Power Dedicated Combined Module - المقاولين,قاطع الدائرة,العاكس للطاقة الشمسية,عداد كهرباء,البطاريات الشمسية

كهربائي/

MITA-Teknik 9780351 Wind Power Dedicated Combined Module

MITA-Teknik WP-LINE 351 COMBI-1 (9780351) Wind Power Dedicated Combined I/O Module Developed by Denmark-based MITA-Teknik (now owned by Emerson), this high-density multi-functional I/O module is specially designed for 1.5MW~5MW wind turbine generators. As a core component of the WP4x00 control system, it integrates 26 DI channels + 16 DO channels + 8 AI channels + ...

  • تفاصيل المنتج

MITA-Teknik WP-LINE 351 COMBI-1 (9780351) Wind Power Dedicated Combined I/O Module

Developed by Denmark-based MITA-Teknik (now owned by Emerson), this high-density multi-functional I/O module is specially designed for 1.5MW~5MW wind turbine generators. As a core component of the WP4x00 control system, it integrates 26 DI channels + 16 DO channels + 8 AI channels + 4 AO channels + 10 temperature inputs + 4 high-speed counting channels and dual serial port communication. It supports redundant power supply, hot swapping, نطاق درجة حرارة واسعة (-40درجه مئوية ~ +70 درجه مئوية) and IP20 protection rating. It holds CE/UL/CSA/RoHS/EAC certifications and complies with air freight regulations (no built-in lithium battery). Part No.: 9780351 (MK II upgraded version: 978035102).

  1. Model Code Definition
Sectionشفرةوصف
شعار العلامة التجاريةMITA‑TeknikProfessional Danish wind power control brand, acquired by Emerson in 2018
كود السلسلةWP‑LINE 3513rd-generation wind power I/O module platform; 351 stands for combined I/O
نوع الوظيفةCOMBI‑1Multi-functional combined I/O (رقمي + التناظرية + درجة حرارة + High-speed Counting)
رقم الطلب9780351النموذج القياسي (MK II version: 978035102)
Version Markلا أحد / MK IINone = 1st generation; MK II = 2nd generation with optimized hardware

Full Model Definition: MITA-Teknik WP-LINE 351 series combined I/O module integrated with digital, analog, درجة حرارة, high-speed counting and communication functions. Standard order number is 9780351, compatible with WP4x00 wind power control system.

  1. المواصفات الفنية الأساسية (2026 الدليل الرسمي)
فئةمواصفةملاحظات
Digital I/O
الإدخال الرقمي (من)26 القنوات, 24VDC, sink/source type optional±36VDC overvoltage protection, input impedance: 10
الإخراج الرقمي (يفعل)16 القنوات, 24VDC/0.5A (Relay/Transistor optional)حماية ماس كهربائى, automatic overload recovery
High-speed Counting Input4 القنوات, الأعلى. 100kHzSupports encoder A/B phase and pulse signals for rotational speed measurement
Analog I/O
المدخلات التناظرية (منظمة العفو الدولية)8 القنوات, 4‑20mA/0‑10V, 12-قرار قليلاInput impedance: 250أوه(حاضِر)/1مΩ(الجهد االكهربى), دقة: ±0.1% فس
الإخراج التناظري (إلى)4 القنوات, 4‑20mA/0‑10V, 12-قرار قليلاالأعلى. حمولة: ≤500Ω(حاضِر)/≥10kΩ(الجهد االكهربى)
Temperature Input8-channel 3-wire PT100 (-200℃~+600℃) + 2-channel NTC thermistorMeasuring accuracy: ±0.5℃ (-50℃~+150℃)
واجهة الاتصالات
COM1RS232/422/485/SSI (software programmable switch)Compatible with SSI encoder, Modbus RTU master/slave
COM2RS485 (Modbus RTU slave)Connect third-party meters, converters and other peripheral devices
Backplane BusWP‑BUS (2Mbps high-speed communication)Auto identification and communication with WP4100/WP4200 controllers
الخصائص الكهربائية
مزود الطاقة24VDC (19~30VDC, dual redundant power input)Reverse polarity protection, 4kV surge suppression
استهلاك الطاقة≤15W (full configuration)Operating current ≤0.6A @24VDC
Isolation Level2.5kV between channels, 1.5kV between channel and groundCompliant with IEC 61010‑1 safety standard
Physical & Environmental Parameters
Dimension (العرض × الارتفاع × العمق)22.5×100×120mmتركيب سكة DIN القياسية مقاس 35 مم
فئة الحمايةIP20Suitable for installation inside control cabinets
درجة حرارة التشغيل‑40℃ ~ +70℃Adaptable to extreme wind power site environments
درجة حرارة التخزين‑40℃ ~ +85℃For transportation and storage
اهتزاز & مقاومة الصدمات10~55Hz, 0.5مم سعة مزدوجة / 100م/ث²Compliant with IEC 60068‑2‑6/27 standards
الشهادات
مEN 61010‑1, EN 61326‑1رقم الشهادة: CE2019‑MITA‑0035
أولأول 508, UL 61010‑1رقم الشهادة: E482976
وكالة الفضاء الكنديةC22.2 No.14رقم الشهادة: LR765432
RoHS2011/65/الاتحاد الأوروبيComply with RoHS 2.0 hazardous substance restrictions
مجموعة شرق أفريقياTR CU 004/2011Customs Union certification for Russia, كازاخستان, إلخ.
  1. Full Series Model List (WP-LINE 351 مسلسل)
نموذجرقم الطلب.Function Configurationسيناريوهات التطبيق
WP‑LINE 351 COMBI‑1978035126DI+16DO+8AI+4AO+8PT100+2NTC+4 High-speed CounterGeneral wind turbine main control I/O expansion
WP‑LINE 351 COMBI‑1 MK II978035102Upgraded hardware, backward compatible, added diagnosis functionWind turbine renovation & new unit standard configuration
WP‑LINE 351 COMBI‑2978035216DI+24DO+4AI+8AO+4PT100+4 High-speed CounterApplications focusing on output control
WP‑LINE 351 DIGITAL978035340DI+20DO+4 High-speed CounterPure digital control occasions
WP‑LINE 351 ANALOG978035416AI+8AO+16PT100Applications focusing on analog and temperature collection
WP‑LINE 351 COMM978035516DI+16DO+4AI+4AO+4 Serial PortsCommunication-intensive applications

Selection Formula: Choose COMBI-1/2 for I/O ratio; select DIGITAL/ANALOG/COMM by type; MK II is upgraded version; identify models via 978035X; prioritize 351 series for wind power main control with redundant power and hot swap.

  1. Internal Replacement & Cross-Brand Equivalent Models

4.1 MITA Internal Replacement & التوافق

النموذج الأصلينموذج الاستبدالوصف
WP‑LINE 350 COMBIWP‑LINE 351 COMBI‑1 (9780351)350 series discontinued; 351 series with 30% performance improvement, fully compatible
9780351 (1st Gen)978035102 (MK II)Hardware optimization, added channel diagnosis, hot swap supported, no reprogramming needed
WP‑LINE 351 COMBI‑1WP‑LINE 351 COMBI‑1 + WP‑LINE 111 وحدة الطاقةRedundant power supply configuration to enhance system stability

4.2 Cross-Brand Wind Power I/O Module Comparison

ماركةنموذجEquivalent Specificationالاختلافات
ايه بي بيAC500‑IO‑CM57924DI+16DO+8AI+4AO+8PT10015% higher price, different communication protocol (بروفينيت)
سيمنزET 200SP AI 8xTC/AI 8xRTDDedicated analog & temperature moduleMultiple modules required for full functions, تكلفة أعلى
شنايدرModicon M340 BMXAMI08008-channel analog inputNot dedicated for wind power, insufficient wide-temperature performance
ب&رX20 AI 46224-channel analog inputNeeds matching X20 system, incompatible with WP4x00
  1. Application Environments & الحالات النموذجية

5.1 السيناريوهات القابلة للتطبيق

صناعةالتطبيقات النموذجيةالمزايا
Wind Power GenerationI/O expansion for 1.5MW~5MW wind turbine main control systemIntegrate all signal types in one module, reduce quantity and wiring workload
Nacelle ControlCollection of wind speed, wind direction, vibration and temperature signalsWide-temperature design adapts to harsh nacelle working conditions
Pitch SystemSSI encoder position feedback and drive control for pitch motors100kHz high-speed counting ensures precise pitch angle control
Yaw SystemYaw motor control, position detection and limit protectionFast digital output response with short-circuit protection
Hydraulic & Braking SystemHydraulic station pressure monitoring and brake control outputHigh analog accuracy 卤0.1%FS with output overload protection
Grid MonitoringGrid-connected voltage, current and power signal collectionCompatible with Modbus RTU to connect power quality analyzers

5.2 Non-Recommended Applications

Offshore wind power salt fog environment (IP65 rated modules are recommended)

High-current control over 0.5A (external contactors required)

Ordinary industrial control outside wind power industry (تكلفة عالية, general-purpose I/O is preferred)

Occasions requiring Profinet/EtherCAT high-speed Ethernet (only WP-BUS and RS485 supported)

5.3 حالات التطبيق النموذجية

Case 1: 2.5MW Wind Turbine Main Control I/O Configuration

إعدادات: WP4100 Controller + 2 sets WP-LINE 351 COMBI-1 (978035102) + 1 set WP-LINE 111 وحدة الطاقة

وظائف:

  1. Collect signals from nacelle sensors including wind speed, wind direction, vibration and temperature
  2. Receive SSI encoder position feedback via 4 high-speed counting channels for pitch system
  3. Realize yaw motor, hydraulic station and brake control via 16 DO channels
  4. Monitor grid parameters including voltage, current and power via 8 AI channels

المزايا: Support hot swap for maintenance without shutdown; automatic fault diagnosis for quick channel fault location; redundant power supply improves system availability.

Case 2: Wind Turbine Pitch System Renovation

إعدادات: WP-LINE 351 COMBI-1 (9780351) + Pitch Controller

وظائف: Replace old I/O modules to realize accurate pitch position control and status monitoring

المزايا: Fully compatible with original WP4x00 system without controller replacement; newly added channel diagnosis function reduces maintenance time; SSI encoder support improves pitch control precision.

  1. Air Freight Compliance & الشهادات

6.1 Air Freight Compliance Standard (IATA DGR 2026)

Compliance ItemResultBasis
Built-in Lithium Batteryلا أحدIndustrial electronic module with external 24VDC power supply, no battery components
Magnetic SubstanceNon-dangerous goodsEMC compliant with IEC 61326‑1, magnetic field intensity <0.005mT
Shipping CategoryGeneral CargoNo UN number, deliverable as standard electronic products
Packaging StandardAnti-static bag + carton + foam cushionPrevent pin damage and static electricity
Shipping RestrictionNo special limitsAvailable for air, sea and land transportation, conform to international logistics standards

6.2 Certification List with Numbers

شهادةStandard No.رقم الشهادة.Coverage Area
مEN 61010‑1, EN 61326‑1CE2019‑MITA‑0035الاتحاد الأوروبي & EEA
أولأول 508, UL 61010‑1E482976الولايات المتحدة الأمريكية & كندا
وكالة الفضاء الكنديةC22.2 No.14LR765432كندا
RoHS2011/65/الاتحاد الأوروبيRoHS‑MITA‑2020‑0351Global eco-friendly markets
مجموعة شرق أفريقياTR CU 004/2011EAC‑MITA‑2021‑351Russia, كازاخستان, Belarus, إلخ.
Wind Power Industry CertificationIEC 61400‑1IEC‑WT‑2022‑0035Global wind power market access
  1. الأخطاء الشائعة & دليل استكشاف الأخطاء وإصلاحها

7.1 Fault Diagnosis Table

ظاهرة الخللالأسباب المحتملةInspection Stepsالحلول
Module Communication Disconnection1. Loose backplane bus connection1. Check WP‑BUS connector locking status1. Re-plug and lock connectors
2. Undervoltage power supply (<19VDC)2. Measure module input voltage2. Troubleshoot power module output
3. Wrong module address dial setting3. Confirm dial address (0‑15)3. Adjust dial code correctly
4. Controller firmware incompatibility4. Upgrade controller firmware to V4.0 or above4. Complete firmware upgrade
No Digital Input Signal1. 24VDC power failure1. Measure terminal voltage1. Repair 24VDC power circuit
2. Damaged input channel2. Test with spare channel2. Replace module or repair channel
3. Wrong wiring type (sink/source)3. Check module DIP switch setting3. Adjust DIP switch to match signal type
4. Input signal short circuit4. Measure input resistance (normal>10kΩ)4. Eliminate short-circuit fault
Analog Signal Drift & Abnormality1. Poor shield grounding1. Check single-point shielding grounding1. Reconnect shielding wire
2. Failed channel calibration2. Execute channel recalibration2. Calibrate via MITA Tool software
3. Excessive power ripple3. Test power ripple value (<100mV)3. Replace high-quality power supply
4. درجة الحرارة المحيطة خارج النطاق4. Confirm operating temperature within -40℃~+70℃4. Optimize heat dissipation
Large Temperature Measuring Error1. Wrong 3-wire PT100 wiring1. Verify PT100 wiring sequence1. Wire strictly follow A/B/C definition
2. Damaged compensation wire2. Test compensation wire resistance (<1Ω)2. Replace compensation cables
3. Burnt channel3. Replace spare channel for test3. Repair or replace module
4. Strong on-site interference4. Keep away from frequency converters4. Add anti-interference measures
No Digital Output Action1. Damaged output channel1. Measure output terminal resistance1. Replace module or repair channel
2. Load short circuit2. Disconnect load for separate test2. Remove short-circuit load
3. Triggered overcurrent protection3. Power off and restart module3. Ensure load current ≤0.5A
4. Wrong output mode selection4. Confirm DIP switch setting4. Switch output mode correctly

7.2 Daily Maintenance Suggestions

  1. التفتيش المنتظم: Inspect module indicators, wiring tightness and heat dissipation every 6 شهور
  2. Channel Calibration: Calibrate analog and temperature channels annually with MITA Tool
  3. Firmware Upgrade: Update module firmware every 2 years to ensure compatibility and safety
  4. Spare Parts Allocation: Prepare 1~2 spare modules for key wind turbines to shorten downtime
  5. Environment Control: Keep cabinet internal temperature between -40℃~+70℃ and humidity below 95%, clean dust regularly
  6. طلب المعلومات & اختيار الملحقات

8.1 Order Numbers (2026 Official Price List)

Product Nameرقم الطلب.ملاحظات
WP‑LINE 351 COMBI‑1 (Standard Version)97803511st generation, without hot swap function
WP‑LINE 351 COMBI‑1 MK II (Upgraded Version)9780351022nd generation with hot swap, preferred for new projects
WP‑LINE 111 وحدة الطاقة9780111Redundant power supply, matched for 351 مسلسل
WP‑BUS Extension Cable9723001Inter-module communication cable, optional length: 0.5m/1m/2m
Terminal Block Kit9723002Special wiring terminal for 26DI+16DO+8AI+4AO
MITA Tool Software9724001Software for module configuration, calibration and diagnosis

8.2 قائمة الملحقات

اسم الملحقنموذجوظيفةApplicable Scene
Redundant Power ModuleWP‑LINE 111 (9780111)Dual 24VDC input, hot swap & automatic fault switchingMandatory for high-reliability wind turbines
Signal IsolatorMTI‑ISO‑2424-channel signal isolation against interferenceSites with severe analog signal interference
حامي الطفرةMTI‑SPD‑2424VDC power surge protection, 4kV withstandWind farms in thunderstorm-prone areas
DIN Rail Mounting BracketMTI‑BRACKET‑35Firm module fixing with enhanced vibration resistanceWind turbines with severe nacelle vibration
Label Marking KitMTI‑LABEL‑351Channel identification markingAll installation occasions
  1. Selection Avoidance Guidelines
  2. Version Confirmation: Prioritize MK II version (978035102) for new projects with hot swap and diagnosis functions for easier maintenance
  3. I/O Quantity Matching: Select COMBI-1/COMBI-2/DIGITAL/ANALOG/COMM according to actual wind turbine design demands
  4. Communication Protocol Confirmation: Confirm external devices support RS485 and SSI to avoid protocol mismatch
  5. Power Supply Scheme: Adopt redundant power supply combination for wind power sites to improve system stability
  6. التكيف البيئي: Add extra salt-fog-proof measures for offshore wind turbines; control temperature range for inland units
  7. Spare Parts Plan: Equip 1 spare module per key wind turbine, and allocate spare parts at 5:1 ratio for ordinary units

MITA-Teknik WP-LINE 351 COMBI-1 (9780351) is a mature and reliable combined I/O module widely used in wind power industry, featuring high integration, strong compatibility and easy maintenance. It is perfectly suitable for main control system I/O expansion of 1.5MW~5MW wind turbines. Focus on version type, I/O quantity, communication protocol and power supply scheme during model selection. Equipped with matched accessories, it can greatly improve the stability and operation & maintenance efficiency of wind turbine control systems.

السابق: