(BMXCP53500 is an incorrect model number) Model Code Breakdown Part Meaning BMX Product identifier for Schneider Modicon X80 series CPS Type code for power supply module 3500 Specific model: 3 = 36W power rating, 5 = AC input, 00 = standard version Product Overview The Schneider BMXCPS3500 is a high-power AC power supply module for ...

  • تفاصيل المنتج

(BMXCP53500 is an incorrect model number)

  1. انهيار رمز النموذج
جزءمعنى
BMXProduct identifier for Schneider Modicon X80 series
CPSType code for power supply module
3500Specific model: 3 = 36W power rating, 5 = AC input, 00 = standard version
  1. Product Overview

The Schneider BMXCPS3500 is a high-power AC power supply module for the Modicon X80 platform, specifically designed for Modicon M340 and M580 Programmable Automation Controller (PAC) racks. It provides stable DC output to power the backplane, I/O modules, وحدة المعالجة المركزية, and field sensors.

  1. Key Technical Specifications
المعلمةقيمة
Input Voltage100–240V AC (operating range: 85–264V AC)
Input Frequency50/60 هرتز (يتراوح: 47–63 Hz)
Total Output Power36دبليو
الجهد الناتج & Power Allocation• 3.3V DC: 15دبليو (logic power for I/O modules)
• 24V DC (sensor power): 21.6دبليو
• 24V DC (I/O module power): 31.2دبليو
تيار الإخراج• 3.3V DC: 4.5أ
• 24V DC (sensor): 0.9أ
• 24V DC (I/O): 1.3أ
كفاءةTypical 85%
IsolationInput‑output: 3000الخامس و
Output‑output: 500الخامس و
Protection FeaturesInternal fuse, حماية الزائد, overvoltage protection, short‑circuit protection
تصاعدRack‑mount (compatible with BMXXBP series backplanes)
Ingress ProtectionIP20
درجة حرارة التشغيل0درجة مئوية إلى +60 درجة مئوية
درجة حرارة التخزين-40°C to +85°C
أبعادStandard X80 module size, width approx. 17.5 مم
  1. بيئة التشغيل & التطبيقات
  2. Industrial Automation Systems: PLC control systems in manufacturing, process industries, infrastructure, إلخ.
  3. Harsh Industrial Environments: Resistant to wide temperature ranges, voltage fluctuations, and electromagnetic interference.
  4. Medium-to-Large PLC Systems: Supplies stable power for multi-module configurations, supporting expanded I/O and complex control tasks.
  5. Global Deployment: Wide input voltage design compatible with power grid standards worldwide.
  6. نماذج الاستبدال & Series Comparison

Complete Model List of X80 Series Power Supply Modules

نموذجInput TypeInput VoltageTotal Powerسمات
BMXCPS2000العاصمة24في العاصمة16.8دبليوBasic DC power supply
BMXCPS2010العاصمة24في العاصمة16.8دبليوEnhanced DC power supply
BMXCPS3020العاصمة24–48V DC31.2دبليوWide‑range DC power supply
BMXCPS3500تكييف100–240V AC36دبليوStandard AC power supply (this product)
BMXCPS4002Hتكييف100–240V AC40دبليوHigh‑power AC supply for harsh environments

استبدال & Compatibility Information

Direct Replacement: BMXCPS3500 can replace legacy M340 series power supply modules.

Compatible Racks: BMXXBP0600, BMXXBP0800, BMXXBP1200, and other X80 series backplanes.

Incompatible: BMEXBP series backplanes (dedicated for EcoStruxure Control Expert platform).

  1. Official Ordering Code & Documentation

Official Ordering Code: BMXCPS3500 (standard version with no suffix)

Official Manual: Schneider Electric SQD-BMXCPS3500.PDF

الشهادات: م, آلية التنسيق الإقليمية, Merchant Navy, وكالة الفضاء الكندية, مجموعة شرق أفريقيا, أول; compliant with EN 61131-2, في 61000-6-4, إلخ.

  1. Engineering Implementation Recommendations
  2. ملاحظات التثبيت

Install the power supply module on the far left of the rack (recommended position).

Allow sufficient space for heat dissipation; avoid adjacent placement with high-power modules.

Use shielded cable for input power to reduce electromagnetic interference.

  1. Wiring Standards

Correctly connect live (ل), neutral (ن), and protective earth (بي) الأسلاك.

Separate sensor power and I/O power terminals to avoid cross-connection.

High-current loads should be powered directly from external sources to reduce module load.

  1. إرشادات الاختيار

Select the appropriate power supply based on total system power requirements, with 20–30% power margin.

Consider on-site power quality; install surge protectors and filters if necessary.

The Schneider BMXCPS3500 is a highly reliable, high-efficiency industrial power supply module that provides a complete power solution for the Modicon X80 platform. Its wide input voltage, multi-channel output, and comprehensive protection make it an ideal choice for medium-to-large PLC systems. If you need to verify BMXCP53500, please confirm the correct model number or contact Schneider Electric technical support for more information.

BMXCPS3500 is an isolated AC/DC switching power supply

that provides stable multi-channel 3.3V and 24V DC power for M340/M580 PLC racks. Its core operation consists of 5 stages:

  1. Input Processing (AC → High-Voltage DC)

Input: 100–240V AC (50/60 هرتز)

EMI filtering: suppresses grid surges and high-frequency interference

Rectifier bridge: converts AC to pulsating high-voltage DC (تقريبا. 310في العاصمة)

Capacitive filtering: smoothes into stable high-voltage DC

  1. High-Frequency DC/DC Conversion (Core Stage)

PWM controller drives MOSFET high-frequency switching (tens of kHz)

High-frequency transformer:

Provides input-output electrical isolation (3000الخامس و)

Converts high-voltage DC into multi-channel low-voltage high-frequency pulses

  1. Output Rectification & Filtering

Secondary high-frequency pulses → Schottky diodes / synchronous rectification → DC

LC filtering: smoothes ripple to produce clean, stable voltage

  1. Multi-Channel Regulated Output (Unique to BMXCPS3500)

3.3في العاصمة / 4.5أ: powers CPU, backplane bus, and I/O logic

24في العاصمة / 1.3أ: main power for rack I/O modules

24في العاصمة / 0.9أ: dedicated sensor power (isolated, independent current limiting)

  1. Closed-Loop Regulation + Protection Mechanism
  2. Voltage Regulation

Output voltage sampled via voltage division → compared with internal reference

PWM duty cycle dynamically adjusted to maintain constant output voltage

  1. Integrated Comprehensive Protection

الجهد الزائد / undervoltage protection (input and output)

الزائد / حماية ماس كهربائى (per-channel current limiting, hiccup recovery)

Overtemperature protection (power reduction or shutdown at excess temperature)

Internal fuse

  1. Status & Alarm

Front-panel READY LED: ON in normal operation, flashing in fault condition

Passive alarm relay:

طبيعي: contacts closed

Power loss / fault / overtemperature: contacts open (can connect to PLC or audible-visual alarm)

RESET button: manually restarts the rack and resets faults

  1. Overall Operating Principle (ملخص)

Mains AC → Rectification & Filtering → High-Frequency Isolated Switching → Multi-Channel Rectification & Filtering → Closed-Loop Regulation → Distribution to CPU / I/O / Sensors via Backplane, with full protection and status monitoring.

  1. Typical Application Sequence
  2. Power-on → Input filtering and rectification
  3. Control circuit startup → PWM begins operation
  4. Outputs gradually establish → Regulation locks in
  5. READY LED illuminates → Alarm relay energizes → CPU startup enabled
  6. Fault (التيار الزائد / overtemperature / power loss) → Outputs shut off immediately → Alarm relay de-energizes → Fault indication

السابق: