Schneider GVAE11 Auxiliary Contact Block

GVAE11 is a 1NO + 1NC instantaneous auxiliary contact block of Schneider TeSys GV series. It is front-mounted and compatible with GV2/GV3 series motor circuit breakers. With a rated current of 2.5A and IP20 protection degree, it is used for status monitoring and signal feedback of motor control circuits, serving as a standard accessory for ...

  • تفاصيل المنتج

GVAE11 is a 1NO + 1NC instantaneous auxiliary contact block of Schneider TeSys GV series. It is front-mounted and compatible with GV2/GV3 series motor circuit breakers. With a rated current of 2.5A and IP20 protection degree, it is used for status monitoring and signal feedback of motor control circuits, serving as a standard accessory for motor control in industrial automation systems.

مقطع الكودمعنىوصف
GVAفئة المنتجAuxiliary contact block for GV series
هموقف التركيبFront mounting, different from side-mounted models
11تكوين الاتصال1 مفتوح عادة (لا) + 1 مغلق عادة (نورث كارولاينا) instantaneous contacts with mechanical linkage

تعريف النموذج الكامل: GVAE11 = Schneider GV series, front-mounted, 1NO+1NC instantaneous auxiliary contact block

  1. المواصفات الفنية الأساسية
فئةتحديدملاحظات
General Characteristics
نوع المنتجInstantaneous auxiliary contact blockMechanically linked, operates synchronously with main contacts of circuit breaker
تكوين الاتصال1لا + 1نورث كارولاينا (لحظية)NO/NC status switches in sync with the main circuit of the circuit breaker
Compatible DevicesSchneider TeSys GV2/GV3 series motor circuit breakersCompatible with GV2L, GV2LE, GV2ME, GV2P, GV2RT, GV3L, GV3P and other models
طريقة التركيبFront snap-on installationTool-free assembly & quick removal with precise positioning
المعلمات الكهربائية
تصنيف الجهد التشغيلي24-240 فولت تيار متردد, 24–60V DCSuitable for standard voltages of control circuits
تصنيف التشغيل الحالي2.5أ (إيث)Continuous current carrying capacity
تصنيف الجهد العزل690الخامس وComplies with insulation requirements for industrial control circuits
التحمل الميكانيكي100,000 دورات التشغيلHigh reliability for frequent operations
التحمل الكهربائي100,000 دورات التشغيل (AC-15 2.5A/240V)Meets long-term service requirements of control circuits
نوع المحطةمحطات المسمارCopper wire cross-section: 0.5–1.5mm²; Tightening torque: 0.8–1.2Nm
بدني & المعلمات البيئية
درجة الحمايةIP20Prevents finger access to live parts
أبعاد (W × H × D)45 × 20 × 15mmهيكل مدمج, no extra installation space required for circuit breakers
درجة حرارة التشغيل-25درجه مئوية ~ +60 درجه مئويةنطاق درجة حرارة واسعة للبيئات الصناعية
لونGreyMatches the appearance of GV series circuit breakers
الشهاداتسي سي سي, أول, وكالة الفضاء الكندية, مجموعة شرق أفريقياMulti-standard certifications for global application
طلب المعلومات
Manufacturer Part No.GVAE11Official Schneider model
رمز الطلب القياسيGVAE11Original imported version
رمز EAN3.38911ه+12International universal commodity code
  1. قائمة النماذج الكاملة (GVAE Series Auxiliary Contacts)
نموذجتكوين الاتصالموقف التركيبCompatible Devicesالتطبيق الرئيسي
GVAE11NO or 1NC (خياري)أمامGV2/GV3 SeriesSimple status indication, single signal output
GVAE111لا + 1نورث كارولايناأمامGV2/GV3 SeriesStandard status monitoring, output open/close signals simultaneously
GVAE202لاأمامGV2/GV3 SeriesControl circuits requiring multiple NO signals
GVAE022نورث كارولايناأمامGV2/GV3 SeriesControl circuits requiring multiple NC signals
GVAE141لا + 1نورث كارولايناجانبGV2/GV3 SeriesSide mounting for space-limited installations
GVAE242لاجانبGV2/GV3 SeriesSide mounting for multiple NO signal demands
GVAE042نورث كارولايناجانبGV2/GV3 SeriesSide mounting for multiple NC signal demands
  1. نماذج الاستبدال & Competitor Comparison

4.1 Internal Schneider Replacements

النموذج الأصلينموذج الاستبدالالاختلافاتسيناريوهات التطبيق
GVAE11GVAE14Different mounting position (side mounting)Insufficient front space, side mounting required
GVAE11GV2ME + Built-in Contactsتصميم متكامل, no extra assembly neededNew equipment selection for integrated layout
GVAE11GV3P + Built-in ContactsUpgraded series with enhanced functionsHigh-standard applications requiring advanced protection

4.2 Cross-brand Competitor Comparison

ماركةنموذجتكوين الاتصالCompatible Devicesالاختلافات الرئيسية
شنايدرGVAE111لا + 1نورث كارولايناGV2/GV3 SeriesPrecise mechanical linkage, حماية IP20, high compatibility
ايه بي بيMS132-011لا + 1نورث كارولايناMS132 SeriesSide mounting, rated current 3A, similar price
سيمنز3RV2091-1A1لا + 1نورث كارولاينا3RV20 SeriesPlug-in mounting, rated current 2A, complete certifications
إيتونPKZM0-AUX111لا + 1نورث كارولايناPKZM0 SeriesFront mounting, rated current 2.5A, spring terminals
شينتNXC-A111لا + 1نورث كارولايناNXC Seriesفعالة من حيث التكلفة, reliable domestic alternative
  1. Application Environments & الحالات النموذجية

5.1 التطبيقات الموصى بها

Motor Control Circuit: Feedback circuit breaker ON/OFF status for PLC/DCS system monitoring

Alarm System: Trigger audible and visual alarms via NC contacts when the circuit breaker trips

Interlock Control: Prevent simultaneous startup of multiple motors and realize sequence control

المراقبة عن بعد: Transmit status signals to SCADA system for remote diagnosis

Safety Circuit: Form safety protection circuits together with emergency stop buttons

5.2 التطبيقات غير الموصى بها

Main Circuit Usage: Rated current is only 2.5A, not applicable for motor main circuits

High-frequency Switching: زيادة 1000 switching cycles per hour will shorten service life

Severe Electromagnetic Interference Environment: Additional shielding is required to avoid malfunction

Humid/Corrosive Environment: IP20 protection is insufficient; install extra enclosure or select higher protection grade products

5.3 حالات التطبيق النموذجية

قضية 1: Pump Unit Control in Wastewater Treatment Plant

معدات: 15kW submersible pump, GV2P32 circuit breaker + GVAE11 auxiliary contact

إعدادات: NO contact of GVAE11 connected to PLC digital input module; NC contact connected to alarm circuit

حصيلة: Real-time monitoring of pump operating status, automatic alarm and event recording upon faults

قضية 2: Conveyor System in Automotive Production Line

معدات: 12 conveyor lines, each equipped with GV2P32 + GVAE11

إعدادات: GVAE11 contacts linked with PLC to realize sequential startup and interlock protection for conveyors

سمات: Mechanical linkage ensures accurate status feedback and reduces misjudgment of control systems

  1. استكشاف الأخطاء وإصلاحها & Maintenance Manual

6.1 الأخطاء الشائعة & الحلول

ظاهرة الخللالأسباب المحتملةالحلول
No change of contact signals1. Improper installation of contact block1. Reinstall the block and ensure the clip is fully engaged
2. Damaged mechanical linkage2. Inspect linkage mechanism and replace damaged unit
3. Burned or oxidized contacts3. Clean or replace the contact block
4. الأسلاك الخاطئة4. Check wiring and confirm correct connection of NO/NC contacts
الاتصال باللحام1. Excessive current in control circuit1. Ensure control circuit current ≤ 2.5A
2. Overheating caused by frequent switching2. Reduce switching frequency or select higher-rated contacts
3. Arc erosion3. Replace with a new contact block
تدخل الإشارة1. Control wires not separated from main wires1. Separate control wires from main wires (spacing ≥ 100mm)
2. No shielded cable used2. Use shielded cable with single-end grounding
3. التأريض السيئ3. Inspect and ensure reliable grounding
Loose installation1. Clip not fully locked1. Reinstall until a click sound is heard
2. Loosening caused by vibration2. Fit shock-absorbing pads or reinforce installation

6.2 Maintenance Procedures

  1. التفتيش اليومي (أسبوعي)

Check installation condition and ensure no looseness

Inspect terminals for overheating and looseness

Test contact switching to confirm synchronization with circuit breaker

  1. الصيانة الروتينية (كل 6 شهور)

Power off and remove dust on the contact block

قياس مقاومة الاتصال (shall be ≤ 50mΩ)

Check flexibility of mechanical linkage

  1. Annual Maintenance

Replace frequently used contact blocks

Test insulation performance of control circuits

Retighten all electrical connections

6.3 Quick Diagnosis Tips

No signal? Check installation and linkage first.

Contact welded? Limit current and cut switching times.

تدخل الإشارة? Separate wires, apply shielding and good grounding.

Loose fitting? Re-clip firmly and add shockproof measures for vibrating sites.

  1. اختيار & إرشادات التثبيت

7.1 قواعد الاختيار

التوافق: Confirm matching with GV2/GV3 series circuit breakers; not applicable for other series

تكوين الاتصال: Select 1NO+1NC (GVAE11), 2لا (GVAE20) or 2NC (GVAE02) according to control demands

موقف التركيب: Choose GVAE11 for front mounting, GVAE14 for side mounting

المطابقة الحالية: Control circuit current shall not exceed 2.5A; select higher-specification products if overloaded

7.2 ملاحظات التثبيت

Installation Sequence: Install circuit breaker first, then attach the contact block and fully lock the clip

Wiring Standard: Use 0.5–1.5mm² copper wires with tightening torque of 0.8–1.2Nm; avoid over-tightening

Clear Marking: Label NO/NC contacts to prevent wiring errors

Linkage Test: Manually operate the circuit breaker after installation to verify synchronous contact action

تدابير الحماية: Install extra enclosures for dusty or humid environments

  1. Production Status & حلول الاستبدال

Current Status of GVAE11: In production, no discontinuation plan (as of June 2026)

يرقي & خيارات الاستبدال:

  1. Functional Upgrade: GV3 series models with built-in contacts (no extra assembly, fewer fault points)
  2. ترقية ذكية: TeSys T series (with communication function for network-based status transmission)
  3. البديل المحلي: Compatible domestic GVAE11 models (lower cost with equivalent performance)