Schneider LC1E1801 Contactor

شرح كود النموذج: LC1E = TeSys E series contactor; 18 = rated 18A at 400V under AC-3 duty; 01 = built-in 1 اتصال مغلق عادة (1نورث كارولاينا) ⚠️ The LC1E series has been discontinued (production stopped in July 2020). The standard replacement model is LC1N1801, fully compatible in mounting, terminal layout and performance. Key Specifications Main ...

  • تفاصيل المنتج

شرح كود النموذج: LC1E = TeSys E series قواطع; 18 = rated 18A at 400V under AC-3 duty; 01 = built-in 1 اتصال مغلق عادة (1نورث كارولاينا)

⚠️ The LC1E series has been discontinued (production stopped in July 2020). The standard replacement model is LC1N1801, fully compatible in mounting, terminal layout and performance.

المواصفات الرئيسية

جهات الاتصال الرئيسية: 3ص, 3لا

ايه سي-3 (motor duty): 18أ @ 400 فولت; ايه سي-1 (حمل مقاوم): 25أ

تصنيف المحرك: 7.5kW @ 380/400V; 4kW @ 220V; 9kW @ 440V

جهد العزل واجهة المستخدم: 690V; دفعة تحمل الجهد Uimp: 6كيلو فولت

الاتصال المساعد: 1نورث كارولاينا (مغلق عادة)

تصاعد: السكك الحديدية الدين / تركيب المسمار لوحة القاعدة

الأبعاد الشاملة: W45mm × H74mm × D80mm, net weight ≈0.3kg

فئة الحماية: IP20; درجة حرارة التشغيل: -5~+55℃; No derating up to 3000m altitude

الحياة الميكانيكية: 10 مليون عملية; الحياة الكهربائية AC-3: 1.2 مليون عملية; أقصى تردد التشغيل: 1800 دورات / ساعة

Coil suffix definitions (complete model number)

LC1E1801B5: تيار متردد 24 فولت, 50هرتز

LC1E1801F5: تيار متردد 110 فولت, 50هرتز

LC1E1801M5: تيار متردد 220 فولت, 50هرتز (most common in China)

LC1E1801Q5: تيار متردد 380 فولت, 50هرتز

لاحقة 7 = 50/60Hz universal; لاحقة 6 = 60Hz only

استهلاك الطاقة لفائف (M5 220V example)

Inrush VA: 95فرجينيا; Sealed holding VA: 8.5فرجينيا; Coil heat dissipation: 2~3W

الجهد البيك اب: 0.85~1.1Uc; الجهد التسرب: 0.3~0.6Uc

تشديد عزم الدوران & wire gauge

Torque for main circuit and control circuit terminals: 1.2 ن · م

سلك صلب: 1.5~6mm²; سلك مجدولة (مع الطويق): 1~4mm²

Matching selection reference

مطابقة التتابع الحراري الزائد: LRD07 / LRN07 (current range suitable for 18A)

مُكَمِّلات: LA1EN auxiliary contact block, LA9D coil surge suppressor, mechanical interlock block

البديل المحلي: CJX2-1801 (similar outline, pay attention to mounting hole and marking differences)

دليل استكشاف الأخطاء وإصلاحها

  1. يتم تنشيط الملف ولكن لا يوجد سحب للداخل: Check if coil voltage is within 0.85~1.1Uc; inspect broken coil wire and loose terminals
  2. Pulled in but main circuit no continuity: Main contact erosion, لحام الاتصال, الأسلاك فضفاضة
  3. Buzzing / chattering: انخفاض الجهد, large harmonic distortion, dust accumulated on core faces
  4. Failed to drop out after power-off: Welded main contacts, core stuck by oil and dirt

Detailed Installation Procedure for شنايدر LC1E1801 Contactor

⚠️ Safety precondition: Operated by qualified electricians; cut off all power supply and verify zero voltage before installation. LC1E1801: 3P main contacts with built-in 1NC auxiliary contact. Terminal marking: Main circuit L1/L2/L3 (line side, incoming), T1/T2/T3 (load side, outgoing); Coil A1, A2; الاتصال المساعد: 95, 96 (1نورث كارولاينا)

  1. التحضير قبل التثبيت
  2. التحقق من جهد الملف: LC1E1801M5=AC220V, Q5=AC380V, F5=AC110V. Coil rated voltage must match control circuit voltage to avoid coil burnout.
  3. التفتيش البصري: No shell cracks, intact terminals, armature moves freely without jamming when pressed manually.
  4. أدوات: 2 مفك فيليبس, متجرد الأسلاك, المتر المتعدد, وجع عزم الدوران; 35mm standard DIN rail or mounting base plate.
  5. Wire specification

Main circuit solid wire: 1.5~6mm²; Stranded wire with ferrule: 1~4mm²

دائرة التحكم (A1/A2, اتصالات مساعدة): 0.75~1.5mm²

تشديد عزم الدوران: 1.2 ن · م (avoid over-tightening to prevent thread stripping, or loose connection causing overheating)

  1. Environmental check: Cabinet temperature -5℃~+55℃, الابتعاد عن الغبار, الرطوبة والزيت. Mount vertically upright. Do NOT install upside down or horizontally.
  2. تحديد (2 methods: السكك الحديدية الدين / تركيب المسمار لوحة القاعدة)

طريقة 1: 35تركيب السكك الحديدية مم DIN (المفضل)

  1. The contactor has upper hooks and a spring locking clip at the bottom.
  2. Hook the upper notch onto the top edge of the DIN rail first.
  3. Press the bottom of the contactor down until you hear a click, the bottom clip locks onto the rail.
  4. Shake lightly to confirm firm fixation. إزالة: Use a flat screwdriver to pry down the bottom clip and pull out the contactor.

طريقة 2: Screw mounting on insulated base plate (no rail)

  1. Mark and drill holes on the insulated plate according to the rear mounting holes (for M4 screws).
  2. Insert screws diagonally, pre-tighten, then torque evenly in diagonal sequence; do not force one side to avoid casing deformation.
  3. Accessory Fitting (خياري: LA1EN auxiliary block, mechanical interlock etc.)
  4. Top auxiliary contact block: Align with the slots on top of contactor, push vertically down until latched.
  5. Thermal relay LRD/LRN: Clip directly underneath the contactor, align positioning slots; the linkage will engage automatically.
  6. Surge suppressor LA9D: Clip beside coil terminals A1/A2, absorbs back EMF to protect PLC output points.
  7. Wiring Sequence (Main circuit → Auxiliary contacts → Coil control circuit)

Standard routing: Line side on top, load side on bottom. L1/L2/L3 on top for three-phase supply; T1/T2/T3 at bottom for load (محرك).

  1. توصيلات الدائرة الرئيسية

Strip insulation 5~6mm, avoid loose copper strands; ferrules are mandatory for stranded wire.

Keep phase sequence L1→T1, L2→T2, L3→T3 as per drawing.

Torque screws to 1.2N·m; only one conductor per terminal.

  1. Built-in auxiliary contact (95-96, نورث كارولاينا)

المحطات 95-96: Conductive when coil de-energized, open when contactor pulls in. Usually used in stop circuit or fault feedback for motor control.

If NO contact is required, add LA1EN auxiliary block.

  1. Coil A1, A2 (دائرة التحكم)

A1 and A2 have no polarity for AC. For AC220V: one to live, one to neutral; for AC380V: connect to two different phases.

Wire in series with start/stop pushbuttons, thermal relay NC contact or PLC outputs.

Route control wires separately from power cables to reduce interference.

Terminal summary:

L1/L2/L3 (Supply In), T1/T2/T3 (Load Out), A1 A2 (لفائف), 95-96 (Built-in 1NC)

  1. التفتيش قبل التشغيل
  2. فحص بصري: All terminals tightened, no exposed copper, no short circuit risk, no loose strands touching adjacent terminals.
  3. Continuity test with multimeter:

De-energized state: No continuity between L-T; 95-96 auxiliary contact is conductive.

Manually press armature to simulate pull-in: L-T becomes conductive, 95-96 يفتح.

  1. Double-check coil voltage; separate power supply for main circuit and control circuit.
  2. تشغيل الطاقة
  3. Energize control circuit only, keep main power off: Press start button, contactor should pull-in smoothly without chattering or buzzing; release stop button for reliable drop-out.

الثرثرة: Low supply voltage, loose wiring or dirty core surfaces.

  1. After control circuit test passes, energize main circuit and run on load.
  2. Temperature check after 10min running: No obvious overheating at terminals (temperature rise indicates poor connection).
  3. ملاحظات التثبيت & المحظورات
  4. Keep minimum clearance ≥10mm between contactor and fuse / MCB for heat dissipation.
  5. Minimum spacing ≥5mm between multiple contactors; increase spacing for high ambient temperature.
  6. Do not plug or remove auxiliary blocks when energized.
  7. Do not trap wire insulation inside terminal clamps; copper must be fully clamped.
  8. LC1E discontinued, spare replacement: LC1N1801, same mounting size and terminal definition.
  9. Common Installation Faults

No pull-in after energized: Wrong A1/A2 voltage, broken control wire or open button circuit

Buzzing when pulled in: انخفاض الجهد, dust or rust on magnetic core faces

Cannot drop out after power cut: Welded main contacts or core jammed by oil

Schneider Easy TeSys E (LC1E / EasyPact TVS) Series Full List

ملاحظة هامة: LC1E series fully discontinued in July 2020. الاستبدال المباشر: LC1N series, أبعاد التركيب متطابقة والتخطيط النهائي.

Model rule: LC1E + current code + auxiliary contact code (10=1لا; 01= 1 نك) + coil suffix

Coil suffix description:

B5=AC24V 50Hz; F5=AC110V 50Hz; M5=AC220V 50Hz; Q5=AC380V 50Hz

B7/F7/M7/Q7=50/60Hz universal; BD=DC24V; 6=60Hz only

  1. 3P LC1E Contactors (تيار متردد-3 @400 فولت)
النموذج الأساسيتيار AC-3Motor Rating @400VBuilt-in Auxiliary Contact
LC1E06106أ2.2كيلوواط1لا
LC1E06016أ2.2كيلوواط1نورث كارولاينا
LC1E09109أ4كيلوواط1لا
LC1E09019أ4كيلوواط1نورث كارولاينا
LC1E121012أ5.5كيلوواط1لا
LC1E120112أ5.5كيلوواط1نورث كارولاينا
LC1E181018أ7.5كيلوواط1لا
LC1E180118أ7.5كيلوواط1نورث كارولاينا (your referenced model)
LC1E251025أ11كيلوواط1لا
LC1E250125أ11كيلوواط1نورث كارولاينا
LC1E321032أ15كيلوواط1لا
LC1E320132أ15كيلوواط1نورث كارولاينا
LC1E381038أ18.5كيلوواط1لا
LC1E380138أ18.5كيلوواط1نورث كارولاينا
LC1E401140أ18.5كيلوواط1لا + 1NC
LC1E501150أ22كيلوواط1لا + 1NC
LC1E651165أ30كيلوواط1لا + 1NC
LC1E801180أ37كيلوواط1لا + 1NC
LC1E951195أ45كيلوواط1لا + 1NC
LC1E120120أ55كيلوواطلا المدمج في, add auxiliary block separately
LC1E160160أ75كيلوواطلا المدمج في, add auxiliary block separately
LC1E200200أ90كيلوواطلا المدمج في, add auxiliary block separately
LC1E300300أ160كيلوواطلا المدمج في, add auxiliary block separately

Example complete model: LC1E1801M7 = 18A, 1نورث كارولاينا, AC220V 50/60Hz universal

  1. Matching LRE Thermal Overload Relays (plug-on fit for LC1E)

LRE01N~LRE35N (for 06~38A); LRE322N~LRE365N (for 40~300A)

LRE01N: 0.1~0.16A

LRE02N: 0.16~0.25A

LRE03N: 0.25~0.4A

LRE04N: 0.4~0.63A

LRE05N: 0.63~1A

LRE06N: 1~1.6A

LRE07N: 1.6~2.5A

LRE08N: 2.5~4A

LRE09N: 4~6 أ

LRE10N: 6~10 أ

LRE12N: 10~16 أ

LRE14N: 16~24A

LRE16N: 24~36A

LRE21N: 28~36A

LRE22N: 36~48A

LRE322N: 55~70A

LRE323N: 63~80A

LRE353N: 80~104A

LRE355N: 104~135A

LRE365N: 130~165A

  1. E-series Accessories
  2. LA1EN: Top-mounted auxiliary contact block (1لا / 1نورث كارولاينا, stackable)
  3. LAEM1: وحدة التعشيق الميكانيكية (for two contactor interlocking)
  4. LA9D: مانع زيادة التيار (شبكة RC / مكثف, PLC output protection)
  5. LAEB1N / LAEB3N: Thermal relay independent base (when not mounted under contactor)
  6. LA1EBN: Timed auxiliary contact block (على التأخير / خارج التأخير)
  7. 2ص / 4P LC1E (single phase, إضاءة & حمل مقاوم, AC-1 duty)

LC1E0920: 2س9أ

LC1E2520: 2ص 25 أ

LC1E0940: 4س9أ

LC1E2540: 4ص 25 أ

LC1E4040: 4P 40A

4P versions commonly used for HVAC, lighting and heating resistive loads

  1. Cross Reference Table
Old LC1E ModelDirect Replacement LC1N
LC1E0601/0610LC1N0601 / LC1N0610
LC1E0901/0910LC1N0901 / LC1N0910
LC1E1201/1210LC1N1201 / LC1N1210
LC1E1801/1810LC1N1801 / LC1N1810
LC1E2501/2510LC1N2501 / LC1N2510
LC1E3201/3210LC1N3201 / LC1N3210
LC1E3801/3810LC1N3801 / LC1N3810
LC1E40~95LC1N40~95