تعريف رمز النموذج
Breakdown of NSYCVF165M230PF
| مقطع الكود | معنى | وصف |
| NSY | بادئة سلسلة المنتج | General mark for Schneider ClimaSys cabinet cooling products |
| CV | Sub-series | ClimaSys CV series standard cabinet filter fan |
| ف | Product type | معجب |
| 165 | Air flow rate | Rated airflow 165m鲁/h at 50Hz, 193m鲁/h at 60Hz |
| م | نوع التركيب | Side mounting on cabinet |
| 230 | الجهد المقنن | 230الخامس و |
| ص | تكوين الحماية | Equipped with pre-filter |
| ف | Air outlet configuration | Fitted with front grille |
- معلمات المواصفات الأساسية
| فئة | Technical Index | ملاحظات |
| المعلمات الأساسية | ||
| نوع المنتج | Cabinet Filter Fan | ClimaSys CV series, حماية IP54 |
| Air Flow | 165م³/ساعة (50هرتز) / 193م³/ساعة (60هرتز) | Measured with standard G2 filter |
| نطاق الجهد | 175~253V AC | Compatible with most 230V power grids worldwide |
| الجهد المقنن | 230V 50/60Hz | Dual frequency compatibility |
| المعلمات الكهربائية | ||
| قوة | 16.3دبليو (50هرتز) / 14.3دبليو (60هرتز) | High energy efficiency |
| حاضِر | 0.12أ (50هرتز) / 0.94أ (60هرتز) | تصميم منخفض استهلاك الطاقة |
| اتصال | Faston terminal + power cable | تركيب سهل |
| المعلمات المادية | ||
| External Dimension | 268×248×104mm | Height×Width×Depth |
| Cutout Size | 223×223mm | Standard cabinet mounting hole |
| مادة | Air outlet grille: ASA+PC thermoplastic | Anti-aging, grey RAL 7035 |
| وزن | 1.14كجم | Stable installation, low resonance |
| معلمات الأداء | ||
| فئة الحماية | IP54 | Dustproof and splashproof, suitable for outdoor cabinets |
| Bearing Type | Ball bearing | عمر خدمة طويل, ضوضاء منخفضة |
| Noise Level | 50~51dB | Quiet operation, applicable near office areas |
| Max Static Pressure | 50Pa (0م³/ساعة) | Resists certain air resistance |
| المعلمات البيئية | ||
| درجة حرارة التشغيل | -20℃~60℃ | نطاق درجة حرارة واسع للبيئات القاسية |
| درجة حرارة التخزين | -40درجه مئوية ~ 70 درجه مئوية | Reliable transportation and storage |
| شهادة | REACH, بنفايات | Compliant with environmental standards |
- قائمة نماذج السلسلة الكاملة
| نموذج | Air Flow(م³/ساعة) | الجهد االكهربى | إعدادات | Cutout Size(مم) | External Size(مم) |
| NSYCVF38M230PF | 39 | 230الخامس و | Grille + Filter | 117×117 | 137×137×85 |
| NSYCVF54M230PF | 54 | 230الخامس و | Grille + Filter | 148×148 | 170×170×92 |
| NSYCVF85M230PF | 85 | 230الخامس و | Grille + Filter | 170×170 | 190×190×95 |
| NSYCVF165M115PF | 165/193 | 115الخامس و | Grille + Filter | 223×223 | 268×248×104 |
| NSYCVF165M230PF | 165/193 | 230الخامس و | Grille + Filter | 223×223 | 268×248×104 |
| NSYCVF165M24DPF | 165/193 | 24في العاصمة | Grille + Filter | 223×223 | 268×248×104 |
| NSYCVF300M230PF | 300/350 | 230الخامس و | Grille + Filter | 262×262 | 300×300×110 |
| NSYCVF550M230PF | 550/650 | 230الخامس و | Grille + Filter | 336×336 | 380×380×120 |
| NSYCVF850M230PF | 838/980 | 230الخامس و | Grille + Filter | 400×400 | 450×450×130 |
| NSYCVF850M400PF | 838/980 | 400الخامس و | Grille + Filter | 400×400 | 450×450×130 |
- Cross-brand Replacement Comparison
| ماركة | نموذج | Air Flow(م³/ساعة) | الجهد االكهربى | فئة الحماية | Cutout Size(مم) | Replacement Advantages |
| Rittal | 3239200 | 74/87 | 230الخامس و | IP54 | 148×148 | Tool-free quick installation |
| Rittal | 3241700 | 160/190 | 230الخامس و | IP54 | 223×223 | High-efficiency energy saving series |
| Stego | FK 66230 | 165/193 | 230الخامس و | IP54 | 223×223 | Integrated temperature control, intelligent start-stop |
| Pfannenberg | 1041230 | 160/190 | 230الخامس و | IP54 | 223×223 | Long filter service life, low maintenance frequency |
| RS PRO | 130-853 | 165/193 | 115الخامس و | IP54 | 223×223 | فعالة من حيث التكلفة, sufficient stock |
- استكشاف أخطاء الأخطاء الشائعة وإصلاحها & صيانة
| ظاهرة الخلل | الأسباب المحتملة | Inspection Steps | Maintenance Solution |
| Fan not running | 1. Power disconnected | 1. Test power voltage | 1. Reconnect power supply |
| 2. Motor burnout | 2. Check motor winding resistance | 2. Replace identical motor | |
| 3. Stuck bearing | 3. Manually rotate fan blade | 3. Clean and lubricate bearing | |
| 4. Control circuit failure | 4. Inspect loose Faston connector | 4. Reconnect or replace connector | |
| Reduced airflow | 1. Clogged filter | 1. Check filter blockage | 1. Clean or replace G2 filter |
| 2. Dust accumulated on blades | 2. Inspect blade cleanliness | 2. Clean blades with soft brush | |
| 3. انخفاض الجهد | 3. Measure operating voltage | 3. Adjust voltage to rated value | |
| 4. Reverse rotation | 4. Verify mounting direction | 4. Reinstall fan outward air discharge | |
| Abnormal noise | 1. Worn bearing | 1. Locate noise source | 1. Replace bearing or whole fan |
| 2. Unbalanced fan blade | 2. Check blade deformation and attachments | 2. Correct balance and clear debris | |
| 3. Loose mounting | 3. Tighten mounting screws | 3. Fasten all screws | |
| 4. Vibration resonance | 4. Observe cabinet vibration | 4. Add shock pad or adjust position | |
| حماية التيار الزائد | 1. Motor short circuit | 1. Test insulation resistance | 1. Replace motor |
| 2. Excessive bearing friction | 2. Check bearing flexibility | 2. Lubricate or replace bearing | |
| 3. الجهد الزائد | 3. Measure operating voltage | 3. Restore normal voltage |
- بيئة التطبيق & حالات الصناعة
السيناريوهات القابلة للتطبيق
- الأتمتة الصناعية: Cooling for PLC, inverter and servo drive cabinets
- Power System: Heat dissipation for outdoor ring main units, box substations and charging pile control boxes
- Telecommunication: Ventilation for base station cabinets, optical distribution boxes and data center server cabinets
- النقل بالسكك الحديدية: Temperature control for signal boxes and converter cabinets
- الطاقة الجديدة: Cooling for photovoltaic inverters and energy storage control cabinets
Non-recommended Scenarios
- Corrosive atmosphere such as chemical and marine environment (anti-corrosion model required)
- Heavy dust sites like mines and cement plants (extra pre-filter needed)
- Submerged or long-term rain exposure (IP54 only splash-proof)
- Fully sealed space without air inlet circulation
الحالات النموذجية
Automobile Factory: Installed on welding robot cabinets, failure rate reduced by 70% against high temperature
Power Grid Company: Eliminated switch misoperation, equipment service life extended 3 مرات
مركز البيانات: Hierarchical cooling with air conditioner, energy consumption cut by 20%
- نصائح الاختيار & Avoidance Guide
Quick Calculation Rule
- Airflow demand = Cabinet volume × (8~10) م³/ساعة, suitable for 16~20m³ cabinet
- Voltage selection: 230V for general industry, 115V for North America, 24V for DC system
- Mounting mark: M=side, MF=top, FB=bottom
Operation Warnings
- Inspect and replace G2 filter every 3 months to avoid airflow drop and motor overload
- Keep air outlet outward and match air inlet for effective ventilation
- Adopt cabinet air conditioner when external temperature is 5℃ higher than internal temperature
- Restrict voltage fluctuation within ±10% to guarantee service life
- Confirm UL, CE and other certifications for export use
- Order Information
نموذج: NSYCVF165M230PF
رقم الطلب: NSYCVF165M230PF (Global unified)
Package Contents: 1 axial fan motor, 1 cutting template, 1 pre-filter, 1 air outlet grille, 1 power cable, 2 protective grilles
Delivery Lead Time: 3-5 working days for standard stock items
المقاولين,قاطع الدائرة,العاكس للطاقة الشمسية,عداد كهرباء,البطاريات الشمسية