(تسلسل المرحلة / خسارة المرحلة / 3-Phase Voltage Unbalance)
مسلسل: Zelio Control / Harmony RM17T Series, DIN rail mounted 3-phase monitoring relay, commonly known as phase sequence protector.
✅ Monitoring Functions
Phase sequence detection (L1-L2-L3): Instant trip upon reverse phase sequence
Phase loss detection: Instant trip if any phase is lost (including phase loss with regenerated voltage from motors)
3-phase voltage asymmetry (unbalance): Adjustable threshold from 5% ل 15% of Un, with time-delayed tripping
Logic rule: Phase reversal / phase loss → instantaneous trip; voltage unbalance → delayed trip.
📌 Key Electrical Specifications
Monitoring voltage range: AC 208~480V (operating limit: 183~528V AC)
تكرار: 50/60 هرتز (±10%)
Output contact: 1 ج/س (SPDT), 5أ / 250بطالة
Time delay adjustment: 0.1~10ث (only for unbalance faults)
Reset delay: تقريبا. 1.5ق
استهلاك الطاقة: ≤22VA @ 400V 50Hz
تصاعد: DIN 35mm rail; width 17.5mm (1 عرض الوحدة)
Indication: Status LED; sealed transparent cover prevents accidental parameter changes
🧮 RM17T Series Selection Comparison (Key for Model Selection)
RM17TT00: تسلسل المرحلة + خسارة المرحلة (NO unbalance monitoring)
RM17TA00 (Current Model): تسلسل المرحلة + خسارة المرحلة + 3-phase voltage asymmetry
RM17TU00: تسلسل المرحلة + خسارة المرحلة + انخفاض الجهد
RM17TE00: تسلسل المرحلة + خسارة المرحلة + asymmetry + الجهد الزائد + انخفاض الجهد (full-function model)
🛠️ سيناريوهات التطبيق النموذجية
مصاعد, hoisting & معدات النقل, ضواغط الهواء, مضخات المياه, وحدات التبريد, آلات التعبئة والتغليف; prevents motor reverse rotation, burnout from phase loss, and overheating caused by three-phase unbalance.
🔌 Wiring Guidelines
- Connect L1/L2/L3 directly to the monitored three-phase supply (ذاتية التشغيل, no separate auxiliary supply required).
- المحطات 15/16/18 form one changeover contact: 15-16 = normally closed; 15-18 = normally open.
- Panel setting: First select rated voltage (208/220/380/400/415/480V), then set unbalance threshold and fault delay time.
- استرداد الخطأ: Automatic reset once power returns to normal; no manual reset button.
⚠️ Troubleshooting
Relay does not energize after power-up: Check phase sequence, خسارة المرحلة, and voltage range dip switch setting.
Frequent tripping during normal operation: Increase unbalance percentage threshold, extend time delay, and investigate single-phase load current imbalance.
No LED illumination: Three-phase input voltage exceeds the 183~528V operating range.
📎 Replacement Options
Direct upgraded replacement within the same product line: RM22TA33 (RM22 series, same functions with 2 C/O contacts).
البدائل المحلية: شينت / Delixi three-phase phase-sequence & unbalance monitoring relays.
- Full Model List of RM17T Series
(3-phase supply monitoring relays, 17.5mm single-module width, تركيب السكك الحديدية DIN)
1) النموذج الأساسي: RM17TG (Only phase sequence + خسارة المرحلة; no unbalance / undervoltage monitoring)
RM17TG00: 1 C/O changeover contact, 208~480V AC
RM17TG20: 2 C/O dual changeover contacts, 208~440V AC
2) Multifunction Models (RM17TT / مواجهة / TU / TE, 208~480V AC, 1 C/O contact uniformly)
| نموذج | وظائف المراقبة الأساسية |
| RM17TT00 | تسلسل المرحلة + خسارة المرحلة (النسخة الأساسية, no unbalance / انخفاض الجهد) |
| RM17TA00 (Current Model) | تسلسل المرحلة + خسارة المرحلة + 3-phase voltage unbalance (asymmetry) |
| RM17TU00 | تسلسل المرحلة + خسارة المرحلة + انخفاض الجهد |
| RM17TE00 | تسلسل المرحلة + خسارة المرحلة + unbalance + الجهد الزائد + انخفاض الجهد (full function) |
Abbreviation explanation:
TU = T + انخفاض الجهد
TE = T + Everything (وظائف كاملة)
ثالثا. Common Specifications for the Whole Series (All Models Identical)
نطاق الجهد: AC 208~480V (operating limit 183~528V)
تصنيف الاتصال: 5أ / 250بطالة; RM17TG00/TT/TA/TU/TE = 1 ج/س; only RM17TG20 = 2 ج/س
عرض: 17.5مم (1P module)
وضع إعادة الضبط: Automatic reset after fault clears; no manual reset button
- Upgraded Replacement Models (RM22 Series with Extra Contacts)
RM17TA00 → RM22TA33 (2 C/O contacts)
RM17TU00 → RM22TU23
RM17TE00 → RM22TE33
RM17TA00 Overall Dimensions (العرض × الارتفاع × العمق)
17.5 مم × 90 مم × 72 مم
عرض: 17.5 مم (1-pole module, same width as 1P MCB)
ارتفاع: 90 مم
عمق (from DIN rail front face): 72 مم
تصاعد: DIN35 standard rail
الوزن الصافي: تقريبا. 0.13 كجم
✅ All models in RM17T series (RM17TT00 / RM17TU00 / RM17TE00 / RM17TG00) مشاركة أبعاد متطابقة.
Core Positioning of RM17TA00
It provides phase sequence + خسارة المرحلة + three-phase voltage unbalance protection, mainly for three-phase asynchronous motors. It prevents reverse rotation, motor burnout from phase loss, and overheating caused by long-term voltage imbalance. تعمل بالطاقة الذاتية, compact 1-module DIN rail design, ideal for compact control cabinets and retrofitting projects where no PLC signal collection is needed.
- صناعة & Equipment Applications
- الرفع & نقل (التطبيق الأساسي)
Overhead cranes, electric hoists, الناقلات الحزامية, المعبئين, مصاعد; prevents motor reverse rotation after phase reconnection and overheating damage to gearboxes and motors due to long-term unbalance.
- مصاعد & منصات الرفع
Freight elevators, simple lifting platforms, parking lift power circuits; wrong phase sequence causes reverse car movement; voltage unbalance leads to excessive temperature rise of traction motors.
- مضخات المياه & Pumping Stations
High-power centrifugal pumps, submersible sewage pumps, pre-power monitoring before variable-frequency drives; unbalance is frequently caused by mixed single-phase loads in water supply, sewage treatment and chiller pump systems.
- ضواغط الهواء & HVAC Refrigeration Units
Screw air compressors, مبردات المياه, air-source heat pumps, ضواغط التبريد; compressors are highly sensitive to three-phase unbalance, which easily burns out motor windings.
- التعبئة والتغليف, النسيج & Woodworking Automation
Packaging lines, آلات النسيج, بثق, injection molding auxiliary equipment; frequent power maintenance and phase swapping require phase sequence verification before power-on.
- Fan Loads
مراوح العادم, induced draft fans, drying fans; large inertia fans produce regenerated voltage after phase loss; this model supports phase loss detection under regenerated voltage conditions.
- Control Panels & OEM Equipment Matching
380V three-phase control cabinets, non-standard automation OEM factory-fitted protection; old equipment retrofits, hard-contact interlock without adding PLC analog modules.
- Selection Boundary: مناسب / سيناريوهات غير مناسبة
✅ موصى به:
Three-phase motor loads with risks of voltage asymmetry overheating (core advantage over RM17TT00)
Supply voltage AC 208~480V, 50/60هرتز
مساحة خزانة محدودة, only 1 module width available
Hard-contact interlock directly wired into main contactor coil circuit
❌ Not recommended:
الجهد الزائد + undervoltage monitoring required → choose RM17TE00
Only undervoltage protection without unbalance → choose RM17TU00
Dual independent alarm contacts required → upgrade to RM22TA33 (2ج/س)
Motors behind variable-frequency drives: VFDs already have built-in phase loss & حماية عدم التوازن; extra relay is generally unnecessary.
ثالثا. Typical Control Logic
Contact wired in series with the main contactor coil circuit:
Normal power supply → relay energizes and closes, contactor power permitted;
Phase reversal / خسارة المرحلة / voltage unbalance detected → relay de-energizes and opens, cutting off main power, with dry contacts available for PLC or audible-visual alarm signals.
المقاولين,قاطع الدائرة,الاستشعار,التشفير,بلك,محول