SIMATIC ET200SP RQ 4×120VDC…230VAC/5A NO ST Relay وحدة الإخراج
Distributed IO ET200SP, 4-channel normally-open digital تتابع output module, contact isolated type
✅ Model Code Interpretation
6ES7: SIMATIC S7 الأتمتة نظام
132: ET200SP Digital Output Module
6HD01: 4-channel relay output, 120VDC~230VAC, 5A normally open
0BB1: Single pack (1 unit per box); `2BB1` = 10-piece bulk pack
📋 Key Technical Specifications
| غرض | المعلمة |
| عدد القنوات | 4 normally-open relay outputs (لا), channel-to-channel isolation |
| تقييم الاتصال | 120V DC ~ 230V AC, الأعلى. 5لكل قناة |
| Base Unit Type | Compatible with BU B0 / BU B1 base units; color code CC40 |
| Backplane Bus Supply | 55أماه, typical power consumption 1.5W |
| وظائف التشخيص | Module supply diagnostics, substitute value output |
| درجة حرارة التشغيل | 0 ~ +60 درجه مئوية (standard module) |
| تواصل | بروفينت / بروفيبوس موانئ دبي (with ET200SP interface module) |
| رمز النظام المنسق | 85389091 |
🧩 Features
- Relay dry contact isolation: Galvanic isolation between PLC low-voltage side and load high-voltage side. Suitable for solenoid valves, المقاولين, indicator lamps and other AC loads.
- Substitute value: When communication fails or CPU stops, output state can be preset in TIA Portal: hold / reset to 0 / تعيين ل 1.
- Channel status LEDs + module diagnostic LED for fault alarm.
- Separate base & electronic module design: Hot-swappable electronics while wiring remains on base for easy maintenance.
⚙️ Typical Application Scenarios
Control of 220VAC solenoid valves, small contactors, alarm lamps, fan start/stop in control cabinets
غير مناسب لتطبيقات التبديل عالية التردد (limited relay mechanical service life; cannot handle high-speed pulses)
Distributed remote IO station deployed with IM155-6 interface module
⚠️ Selection & ملاحظات الأسلاك
- Base unit must be BU B0 / BU B1 type, A-type bases are incompatible; recommended BU20-P16+A0+2B.
- Relay contacts are passive dry contacts. Load power is not supplied by module backplane, external power supply required.
- الأحمال الحثية (لفائف المقاولين) are recommended to connect varistor / freewheeling diode in parallel to extend relay service life.
- 5A per channel is rated current; pay attention to heat dissipation when all 4 channels run at full load simultaneously.
📌 Alternative & Derivative Models
6AG1132-6HD01-7BB1: SIPLUS wide-temperature conformal coated version, -40~+70 درجة مئوية, for harsh environments (الصناعة الكيميائية, في الهواء الطلق)
البدائل المحلية: ET200SP compatible 4-channel normally-open 5A relay modules. Verify base compatibility and diagnostic telegram.
Application Scenarios for 6ES7132-6HD01-0BB1 (ET200SP 4-Channel Relay Output Module)
الميزات الأساسية: Passive dry contacts, channel isolation; الأعلى. 5أ للأحمال المقاومة, الأعلى. 2A for inductive loads; supports 24V~230V AC/DC loads; PROFINET distributed remote IO. Ideal for low-frequency switching control requiring galvanic isolation between strong and weak circuits.
- Industry-specific Applications
- تصنيع الآلات (الأكثر شيوعًا)
220VAC pneumatic & hydraulic solenoid valve control (اسطوانة, hydraulic valve on/off)
Drive coils of small AC contactors to indirectly control fans, مضخات, الناقلات
Equipment alarm lights, مسموع & الإنذارات المرئية, panel indicator lamps
Door interlock, guard door signal output, equipment enable signal
ملائم: ماكينات التعبئة والتغليف, أدوات الآلة, خطوط الإنتاج, آلات صب الحقن, textile machinery remote IO stations
- أتمتة العملية / معالجة المياه
Remote field cabinet: 220V solenoid valves, dosing pumps, صمامات الصرف, agitator start/stop control
Field instrument power switching, warning lights, on-site audible & الإنذارات المرئية
Water tank level interlock output; remote stations deployed at different plant locations
ميزة: Relay isolation prevents field high-voltage interference from coupling into PROFINET bus
- التدفئة والتهوية وتكييف الهواء & أتمتة البناء
AC220V air damper actuators, electric butterfly valve on/off control
Contactor coil control for fans, exhaust fans, مضخات المياه
Fire linkage signal output, on-site alarm indication
- طاقة, الكهروضوئية & Power Auxiliary Control
Switchgear auxiliary circuit, relay loop switching, alarm contact output
Small heater, dehumidifier on/off control
Signal isolation transfer: Convert PLC low-voltage signals to dry contacts for 3rd-party systems (DCS, relay protection)
- Supported Load Types
- AC220V solenoid valves, مصابيح المؤشر, buzzers
- AC220V contactor / intermediate relay coils
- الأحمال المقاومة: heating tapes, incandescent lamps (≥5A)
- DC24V~DC120V DC loads (dry contacts work for both AC and DC)
- Passive contact output for hard-wired interlock with other control systems
ثالثا. تطبيقات غير مناسبة
- ❌ High-frequency switching: Mechanical relay has limited service life, not for multiple operations per second. Use transistor DQ modules for high frequency.
- ❌ Direct drive of high-power motors (only drives contactor coils, not main motor circuit)
- ❌ Inductive load current exceeding 2A (solenoid & contactor are inductive loads; varistor / freewheeling diode required to absorb back EMF)
- ❌ Safety circuits (this module is non-failsafe. F-RQ failsafe modules are required for emergency stop and safety gate circuits)
- ❌ High inrush current loads (contact erosion risk; each channel needs external 6A max. fast fuse protection)
- Architecture Characteristics
ET200SP distributed IO: This module is mounted in remote field enclosures away from the main PLC and connected via IM155-6 PROFINET interface module.
Load wiring for 220VAC is routed locally, reducing long-distance high-voltage cables
Relay isolation protects PLC low-voltage system and improves EMC immunity
Substitute value configurable in TIA Portal: Output state can be defined for bus interruption or CPU stop to ensure safe equipment status
ET200SP Digital Output Module Selection Comparison Sheet
Compare 6ES7132-6HD01-0BB1 (RQ 4-channel relay output) vs common transistor DQ modules
- جدول مقارنة المعلمات الأساسية
| غرض | 6ES7132-6HD01-0BB1 | 6ES7132-6BH01-0BA0 | 6ES7132-6BD20-0BA0 |
| Relay Output RQ | Transistor DQ 16×24VDC | Transistor DQ 4×24VDC/2A | |
| نوع الإخراج | Passive dry contact, normally-open relay NO | الترانزستور PNP, active 24VDC | الترانزستور PNP, active 24VDC |
| عدد القنوات | 4 القنوات | 16 القنوات | 4 القنوات |
| Load Voltage Range | 120VDC ~ 230VAC, تكييف & DC compatible | DC24V only | DC24V only |
| التصنيف الحالي لكل قناة | 5A resistive; 2A inductive | 0.5لكل قناة | 2لكل قناة |
| عزل كلفاني | ✅ Channel isolation, strong/weak voltage isolation | ❌ No channel isolation, common 24V ground | ❌ No channel isolation |
| سرعة الاستجابة | بطيء: millisecond level (mechanical contact) | سريع: microsecond level | سريع: microsecond level |
| خدمة الحياة | Mechanical life ~10⁷ operations (low frequency) | Nearly unlimited electronic life, high frequency capable | Nearly unlimited electronic life |
| الحمل النموذجي | AC220V solenoid valves, لفائف المقاولين, audible/visual alarms, dry-contact interlock | DC24V solenoid valves, مصابيح المؤشر, sensor power supply | High-current DC24V loads, DC solenoid valves |
| Base Color Code | CC40 | CC01 | CC01 |
- When to select 【6ES7132-6HD01-0BB1 Relay Module】
✅ موصى به
- Load voltage is AC220V, no extra intermediate relay required on site
- Galvanic isolation required, heavy field interference, prevent high voltage from damaging PLC IO bus
- Need passive dry contact output for hard-wired interlock to 3rd-party DCS / protection relays
- Low switching frequency (triggered every few minutes/hours, not frequent on/off)
- الأحمال المختلطة: both AC220V and DC loads up to 120V
❌ Not Recommended
- التبديل المتكرر: multiple start-stop per second (rapid contact wear and shortened lifetime)
- Pure DC24V loads with large point count requirement (transistor modules cheaper, higher channel density)
- High-speed pulse & motion control output (relay cannot generate pulses)
- SIL safety circuits (Failsafe F-series modules required)
ثالثا. When to select 【Transistor DQ Module】
✅ موصى به
- All loads are DC24V, frequent switching (continuous actuation of cylinder solenoids)
- Requirement for high-speed switching signals or pulse outputs
- Large I/O point count, high channel density to save cabinet space
- Field loads are low-current DC components without isolation requirement
❌ Not Recommended
- AC220V loads: must add external intermediate relays
- Severe field high-voltage interference without isolation; risk of IO module burnout
- Quick Selection Rule
حمولة: تيار متردد 220 فولت, low frequency, isolation required → 6ES7132-6HD01-0BB1
حمولة: تيار مستمر 24 فولت, frequent operation → Transistor DQ (6BH01 for many points / 6BD20 for high per-channel current)
- Additional Selection Notes
- الأحمال الحثية (صمامات الملف اللولبي, المقاولين) need absorption components: varistor in parallel for AC loads, freewheeling diode for DC loads to suppress back EMF and extend contact life.
- Relay module base color code CC40, not interchangeable with transistor DQ base CC01.
- Cost reference: Relay modules usually cost more for same channel quantity. لكن, overall system cost may be lower when eliminating external intermediate relays.
- Failure characteristics: Relay contacts risk sticking; transistor modules mostly fail by breakdown with no mechanical sticking risk.
- Special Alternatives
Failsafe output: 6ES7136-6DB00-0CA0 (F-DQ for safety circuits)
Solid-state relay output (no moving contacts, suitable for high-frequency AC switching): ET200SP RQ solid-state relay models
المقاولين,قاطع الدائرة,الاستشعار,التشفير,بلك,محول