Complete Technical Parameters of Siemens 3WL1116/3WL1216 1600A ETU45B-G-LCD-3P - Contactor,circuit breaker,solar inverter,electric meter,solar batteries

NewsTrade News

Complete Technical Parameters of Siemens 3WL1116/3WL1216 1600A ETU45B-G-LCD-3P

Complete Technical Parameters of Siemens 3WL1116/3WL1216 1600A ETU45B-G-LCD-3P

The parameters cover dimensions including basic electrical characteristics, breaking capacity, trip unit, mechanical & environmental performance, communication and installation, facilitating engineering selection and system matching.

  1. Basic Electrical Parameters
Parameter ItemSpecification ValueRemarks
Product SeriesSiemens SENTRON 3WLAir Circuit Breaker (ACB)
Frame Size3WL1116 (Frame I) / 3WL1216 (Frame II)3WL1116: Standard breaking capacity; 3WL1216: High breaking capacity
Rated Current (In)1600AFrame size current 1600A, setting range 0.4–1In
Pole Number3PThree-pole, 3-phase main circuit
Rated Operational Voltage (Ue)690V AC50/60Hz, compliant with IEC 60947-2
Rated Insulation Voltage (Ui)1000V ACBenchmark value for insulation withstand capability
Rated Impulse Withstand Voltage (Uimp)12kVCompliant with IEC 60947-1
Rated Short-time Withstand Current (Icw)Frame I: 66kA/1s; Frame II: 80kA/1sEnsures short-time thermal stability at 500V
Breaking Capacity (Icu)Frame I: 55/66kA; Frame II: 80/100kAUltimate breaking capacity at 500V; Frame II offers higher breaking capacity
  1. Parameters of ETU45B-G-LCD Electronic Trip Unit
Function ModuleSpecification ValueDescription
Protection TypeLSIG (L: Overload/Long-time Delay; S: Short-circuit/Short-time Delay; I: Instantaneous Short-circuit; G: Ground Fault)Complete power distribution protection configuration
Overload Protection (L)Characteristic Curve: I²t/I⁴t selectable; Setting Range: 0.4–1InI⁴t characteristic improves selectivity with downstream devices
Short-time Delay Short-circuit Protection (S)Setting Current: 2–10In; Time Delay: 0.1–0.4sAdjustable inverse/definite time delay to prevent selective tripping
Instantaneous Short-circuit Protection (I)Setting Current: 2–10InRapid short-circuit current interruption without time delay
Ground Fault Protection (G)Setting Current: 0.2–0.8In; Time Delay: 0.1–2sDetects ground faults to avoid equipment damage
Display & OperationLCD screen, rotary coding switchReal-time display of current, trip cause and fault records
Reset MethodManual/Auto selectableQuick power supply recovery after fault clearance

III. Mechanical & Environmental Parameters

Parameter ItemSpecification ValueRemarks
Mechanical Life150,000 operationsNo-load operation, compliant with IEC 60947-2
Electrical Life10,000 operations (AC-3, at rated current)On-load breaking life, related to operating frequency
Operating MechanismSpring-loaded energy storage type (manual/electric optional)Electric mechanism suitable for remote control
Auxiliary ContactsStandard: 2NO+2NC, expandable to 4NO+4NCStatus feedback and control circuit interlocking
Ambient Temperature-25℃~+70℃ (operating); -40℃~+85℃ (storage)Wide temperature range for industrial applications
Protection ClassIP30 (body); IP40 (with protective cover)Prevents solid foreign object intrusion
Altitude≤2000m (derating required above 2000m)Rated current derating by 1% for every 100m altitude increase
Mounting MethodFixed type/Drawout typeDrawout type enables maintenance without power outage
  1. Communication & Measurement Parameters
FunctionSpecificationInterface/Protocol
Communication ModuleCOM15 (PROFIBUS DP) / COM16 (MODBUS RTU)Optional, supports data upload to monitoring system
Measurement AccuracyCurrent: ±1%; Voltage: ±1.5%; Power: ±2%Compatible with Plus measurement function for energy management
Data Logging100 fault records (trip type, time, current value)Fault tracing and system diagnosis
Remote ControlSupports remote opening/closing and parameter settingRealized by electric mechanism + communication module
  1. Installation & Dimension Parameters
Mounting TypeWidth (W)Height (H)Depth (D)Weight
3WL1116 Fixed Type320mm434mm291mmApprox. 45kg
3WL1116 Drawout Type320mm434mmApprox. 450mmApprox. 55kg
3WL1216 Fixed Type460mm434mm291mmApprox. 56kg
3WL1216 Drawout Type460mm434mmApprox. 450mmApprox. 65kg
Mounting Mode35mm DIN rail/screw mountingFrame I width: 320mm; Frame II width: 460mm; Unified height: 434mm
  1. Key Selection & Application Tips
  2.  Breaking Capacity Matching: Select frame size based on the system’s maximum short-circuit current. Frame I is suitable for scenarios ≤66kA, while Frame II is for ≤100kA. A 20% margin is recommended.
  3.  Trip Unit Setting: Enable LSIG protection for motor loads, with the ground fault setting recommended at 0.3–0.5In. LSI protection is sufficient for power distribution loads.
  4.  Communication Compatibility: Select COM15/COM16 module for remote monitoring, ensuring protocol compatibility with PLC/SCADA systems (PROFIBUS/MODBUS).
  5.  Installation Space: The drawout type occupies approximately 160mm more depth than the fixed type. Reserve sufficient operation and maintenance space during cabinet design.
  6.  Replacement & Upgrade: The 3WL series has been upgraded to the 3WA series (e.g., 3WA1116-3EG45-4GA4), featuring compatible dimensions and protection functions, plus added Ethernet communication and intelligent diagnosis.

 

 

VII. Compliance & Certification

Compliant Standards: GB 14048.2, IEC 60947-2, EN 60947-2

Certifications: CE, UL, CSA (for some models), meeting compliance requirements for global industrial applications