Marke: Pentronic (Schweden), a Nordic manufacturer of high-precision Temperatursensoren. Der 5810080 series is an assembled industrial Pt100 Resistance Temperature Detector (FTE). It is often mistakenly referred to as a thermocouple in the industry; this distinction is critical.
- Erklärung des Modellcodes
5810080: Produktserie, assembled industrial platinum RTD with terminal head and protection thermowell
-001: Version / construction suffix, representing single Pt100 element, Class A accuracy, base version with standard thermowell material, probe length and thread specification
Other variants within the series include 5810080-002 Und 5810080-003, commonly dual Pt100 elements, alternative probe lengths or pressure ratings.
- Grundlegende technische Spezifikationen
| Artikel | Spezifikation |
| Sensing Element | Pt100 Platinum RTD (compliant with IEC60751) |
| Genauigkeitsklasse | Klasse A |
| Temperaturbereich | -200℃ ~ +500℃ (depends on thermowell material) |
| Verkabelungskonfiguration | Standard 4-wire (3-wire optional). The 4-wire design eliminates lead resistance error and is preferred for high-precision measurement |
| Thermowell Material | 316L Edelstahl (Standard); Hastelloy or Titanium optional for highly corrosive media |
| Probe Construction | Solid mineral-insulated / drilled protection tube, vibration-resistant structure (Pentronic thermally conductive filling for faster response) |
| Terminal Head | Aluminium waterproof head, IP65; built-in temperature transmitter optional (4-20mA-Ausgang) |
| Montage | Threaded installation (G1/2, M20×1.5 commonly used), compatible with protection thermowell |
| Ansprechzeit | t0.5: ca. 2~8s (in liquid media, subject to probe diameter) |
| SIL | SIL2 loop assessment available (dual-element version 5810080-002) |
- Kernfunktionen
- Excellent stability: Class A platinum wire with annual drift as low as 0.05℃, suitable for long-term continuous process measurement
- Vibration-resistant construction: Internal metal filling reduces air gaps, withstands vibration for temperature measurement on compressor, pump and turbine casings
- Replaceable insert: Sensing element is a removable insert. Sensor core can be replaced without removing the thermowell, cutting downtime maintenance cost
- Corrosion-resistant options: Custom Hastelloy and Monel thermowells available for corrosive chemical service
- Optionales Zubehör: Built-in HART temperature transmitter providing direct 4–20mA signal to DCS/PLC
- Typische Anwendungsszenarien

Pentronic 5810080-001 Temperatursensor
Thermal power, Öl & Gas, chemisch, paper and pharmaceutical industries; temperature measurement of pipelines, equipment casings and tank media; high-precision temperature acquisition for TSI and process control loops.
Frequently paired with Bently Nevada TSI systems for unit temperature monitoring.
- Installation & Inbetriebnahmerichtlinien
- Installation: Protection thermowell is recommended for online replacement. Probe insertion depth ≥ 8~10 times thermowell inner diameter to ensure accurate temperature reading
- Verdrahtung: 4-wire Pt100 with two excitation wires and two measurement wires. Must not be used with thermocouple extension wires
- Shielding: Cable shield single-point grounded inside terminal head to avoid common-mode interference; route away from power cables
- Kalibrierung: Calibrate resistance values against IEC60751 using dry block calibrator or constant temperature oil bath
- Explosion-proof versions: Ex ia / Ex d available; certificates must be verified for hazardous area selection
- Common Troubleshooting Checklist
- Temperature fluctuation: Loose lead connections, multi-point grounding of shield, terminal loosening caused by field vibration
- Persistently high / low readings: Probe not fully immersed in media, fouled thermowell, excessive lead resistance (switch to 4-wire configuration)
- Open circuit alarm: Broken platinum wire or bending damage at root (frequently seen under vibrating conditions)
- Increased drift: Platinum element aging after prolonged over-temperature operation
- Series Alternative & Auswahlreferenz
| Modell | Konstruktion | Anwendung |
| 5810080-001 | Single Pt100, Klasse A | Single-point temperature measurement for general process |
| 5810080-002 | Dual Pt100, Class A/A | Redundant measurement, SIL2 loop |
| 5810080-003 | Single element, extended probe / high-pressure thermowell | Deep insertion, high-pressure pipelines |
Schütz,Leistungsschalter,Sensor,Encoder,SPS,Konverter