Wechat: +86-13184948252 WhatsApp: 0086-13811255435 E-Mail: kent@bestcontactor.com

Um Kontakt |

Schneider Contactor LC1D09BDC - Schütz,Leistungsschalter,Solarwechselrichter,Stromzähler,Solarbatterien

Schütz/

Schneider Contactor LC1D09BDC

ParameterelementDetails
ProduktmodellLC1D09BDC
SerieSchneider TeSys D (Domestic Version)
Main Contact Configuration3-Pol normalerweise offen (3NEIN), rated current 9A
NennbetriebsspannungBis zu 690 V Wechselstrom
Coil SpecificationDC24V DC coil
Auxiliary Contact1 normalerweise offen + 1 normalerweise geschlossen (1NO+1NC)
Service CategoryAC-1 (ohmsche Last), AC-3 (squirrel-cage induction motor)
MontagemethodeStandard 35mm DIN rail or screw mounting
Mechanisches LebenApprox. 10 Millionen Operationen; Electrical life approx. 1 Millionen Operationen
CertificationsCCC, CE, UKCA, RoHS, REACH
Overall Dimensions45mm (W)*77mm (H)*95mm (D), Weight approx. 0.48kg

  • Produktdetails

Schneider LC1D09BDC

Schneider LC1D09BDC is a 3-pole AC-Schütz of the TeSys D series, with a rated current of 9A, a coil voltage of DC24V, 3NO main contacts and 1NO+1NC auxiliary contacts. It is suitable for AC-1/AC-3 loads, supports DIN rail mounting, and is commonly used in industrial automation and motor control.

Kernparameter

ParameterelementDetails
ProduktmodellLC1D09BDC
SerieSchneider TeSys D (Domestic Version)
Main Contact Configuration3-Pol normalerweise offen (3NEIN), rated current 9A
NennbetriebsspannungBis zu 690 V Wechselstrom
Coil SpecificationDC24V DC coil
Auxiliary Contact1 normalerweise offen + 1 normalerweise geschlossen (1NO+1NC)
Service CategoryAC-1 (ohmsche Last), AC-3 (squirrel-cage induction motor)
MontagemethodeStandard 35mm DIN rail or screw mounting
Mechanisches LebenApprox. 10 Millionen Operationen; Electrical life approx. 1 Millionen Operationen
CertificationsCCC, CE, UKCA, RoHS, REACH
Overall Dimensions45mm (W) * 77mm (H) *95mm (D), Weight approx. 0.48kg

Interpretation des Modellcodes

LC1D: 3-pole contactor of TeSys D series

09: Nennstrom 9A

B: DC coil type

D: Coil voltage DC24V

C: Mark for domestic version

Typical Applications and Replacement Selection

  1. Anwendungsszenarien: Suitable for start-stop control of squirrel-cage motors with current ≤9A, as well as control of AC-3/AC-1 loads such as heating equipment, fans and water pumps. It is compatible with DC control circuits of PLC and DCS systems.
  2. Replacement Selection

Intra-series replacement: LC1D09BD (imported version with identical parameters)

Cross-brand replacement: ABB A16-30-01 (DC24V), Siemens 3RT2015-1BB41 (DC24V), Chint NXC-0910Z (DC24V)

Installation and Safety Points

  1. Installationsspezifikationen

Ambient temperature: -5℃~+40℃, Altitude ≤2000m, Avoid dust/corrosion/condensation

Reserve heat dissipation clearance, spacing between adjacent devices ≥5mm

Wiring torque: Main circuit 1.7N·m, Control circuit 0.5N·m

  1. Safety Tips

Verify voltage after coil power-off to prevent residual voltage

It is recommended to match a thermal overload relay (z.B., LRD06C) for motor circuits

Derating is required for frequent start-stop scenarios (recommended ≤80% of rated current)

Allgemeine Fehlerbehebung

FehlerphänomenMögliche UrsachenMethoden zur Fehlerbehebung
No power to coilPower circuit break, loose wiringMeasure coil terminal voltage, inspect wires and terminals
High noise after pull-inContaminated iron core contact surface, broken shading ringClean the iron core, replace the shading ring
Contact ablationOverload, incorrect load matchingCheck load type, replace contact set
Durchbrennen der SpuleOvervoltage/undervoltage, frequent on-offInstall a surge suppressor, optimize control logic

Procurement and Maintenance

Order Number: LC1D09BDC, Packaging: 1 pc/box, 21 pcs/carton

Garantiezeitraum: 18 Monate, It is recommended to inspect contact wear and wiring tightness quarterly

The following are the mainstream cross-brand direct replacement models for Schneider LC1D09BDC (3-pole, 9A, DC24V, 3NO main contacts, 1NO+1NC auxiliary contacts), classified by brand with core parameter matching marked for quick selection and replacement.

  1. Key Points for Core Parameter Matching

Ensure the following key parameters are consistent during replacement:

Pole number: 3-pole

Nennstrom: 9A (at AC-3 400V)

Coil voltage: DC24V (Gleichstrom)

Main contacts: 3NEIN (3 normalerweise offen)

Auxiliary contacts: 1NO+1NC (1 normalerweise offen + 1 normalerweise geschlossen)

Service category: AC-1/AC-3 (suitable for resistive loads and squirrel-cage motors)

  1. Cross-brand Replacement Model Comparison Table
BrandModellCore Parameter MatchingRemarks
Schneider (Intra-series)LC1D09BDFully consistent parametersImported version, replacement for domestic LC1D09BDC
ABBAX09-30-11-80*24VDC3P,9A,DC24V,3NO+1NO+1NCAX series for motor-specific use, BC series for general use
BC6-30-11-P01
Siemens3RT2023-1BB413P,9A,DC24V,3NO+1NO+1NC3RT2 as standard type, 3RT6 as economic type
3RT6015-1BB41
ChintNXC-09M/22/Z DC24V3P,9A,DC24V,3NO+1NO+1NCNXC as new model, CJX2 as classic model
CJX2-0911Z DC24V
DelixiCJX2s-0911Z DC24V3P,9A,DC24V,3NO+1NO+1NCZ indicates DC coil version
Eaton MoellerDILM9-10(24VDC)3P,9A,DC24V,3NO+1NO+1NCConfirm auxiliary contact configuration
DILM9-10(24VDC)+Hilfskontakt
Changshu SwitchgearCK3-0910Z DC24V3P,9A,DC24V,3NO+1NO+1NCHigh-quality domestic replacement brand
People’s Electric ApplianceRMK-0910Z DC24V3P,9A,DC24V,3NO+1NO+1NCKostengünstig, suitable for industrial scenarios

III. Notes on Replacement Selection

  1. Installationskompatibilität: All recommended models are suitable for 35mm DIN rail mounting, with dimensions close to LC1D09BDC (ca. 45mm in width), enabling direct replacement of installation positions.
  2. Wiring Matching: Main circuit wiring torque 1.7N·m, control circuit 0.5N·m, consistent with the original contactor.
  3. Thermal Relay Matching: It is recommended to match a thermal overload relay below 9A of the same brand (z.B., ABB TA25DU06, Siemens 3RB2016, Chint NR2-063) to ensure consistent motor protection.
  4. Surge Protection: It is recommended to install a freewheeling diode or surge suppressor for DC coils to extend service life.
  5. Derating Use: For frequent start-stop scenarios (>1200 times/hour), derate to below 7.2A for use.
  6. Quick Selection Suggestions
  7. Pursue original quality: Select Schneider LC1D09BD
  8. Prioritize cost performance: Select Chint NXC-09M/22/Z or Delixi CJX2s-0911Z
  9. System compatibility: Select AX09-30-11-80 for ABB systems, 3RT2023-1BB41 for Siemens systems
  10. Spare part universality: Prioritize mainstream domestic models such as NXC/CJX2s for easier procurement and maintenance

Vorher:

Hinterlassen Sie eine Antwort

Eine Nachricht hinterlassen