(BMXCP53500 is an incorrect model number)
- Aufschlüsselung des Modellcodes
| Teil | Bedeutung |
| BMX | Product identifier for Schneider Modicon X80 series |
| CPS | Type code for power supply module |
| 3500 | Specific model: 3 = 36W power rating, 5 = AC input, 00 = standard version |
- Produktübersicht
Das Schneider BMXCPS3500 ist ein Hochleistungs-AC-Netzteilmodul für die Modicon X80-Plattform, Speziell für die programmierbaren Automatisierungssteuerungen Modicon M340 und M580 entwickelt (PAC) Gestelle. Es bietet einen stabilen Gleichstromausgang zur Stromversorgung der Rückwandplatine, I/O-Module, CPU, und Feldsensoren.
- Wichtige technische Spezifikationen
| Parameter | Wert |
| Eingangsspannung | 100–240 V Wechselstrom (operating range: 85–264V AC) |
| Input Frequency | 50/60 Hz (Reichweite: 47–63 Hz) |
| Total Output Power | 36W |
| Ausgangsspannung & Power Allocation | • 3.3V DC: 15W (logic power for I/O modules) |
| • 24V DC (sensor power): 21.6W | |
| • 24V DC (I/O module power): 31.2W | |
| Ausgangsstrom | • 3.3V DC: 4.5A |
| • 24V DC (Sensor): 0.9A | |
| • 24V DC (E/A): 1.3A | |
| Effizienz | Typical 85% |
| Isolierung | Input‑output: 3000V und |
| Output‑output: 500V und | |
| Schutzfunktionen | Internal fuse, Überlastschutz, Überspannungsschutz, short‑circuit protection |
| Montage | Rack‑mount (compatible with BMXXBP series backplanes) |
| Schutz vor Eindringen | IP20 |
| Betriebstemperatur | 0°C bis +60°C |
| Lagertemperatur | -40°C to +85°C |
| Abmessungen | Standard X80 module size, width approx. 17.5 mm |
- Betriebsumgebung & Anwendungen
- Industrielle Automatisierungssysteme: PLC control systems in manufacturing, process industries, Infrastruktur, usw.
- Harsh Industrial Environments: Resistant to wide temperature ranges, Spannungsschwankungen, and electromagnetic interference.
- Medium-to-Large PLC Systems: Supplies stable power for multi-module configurations, supporting expanded I/O and complex control tasks.
- Global Deployment: Wide input voltage design compatible with power grid standards worldwide.
- Ersatzmodelle & Serienvergleich
Complete Model List of X80 Series Power Supply Modules
| Modell | Eingabetyp | Eingangsspannung | Total Power | Merkmale |
| BMXCPS2000 | Gleichstrom | 24In DC | 16.8W | Basic DC power supply |
| BMXCPS2010 | Gleichstrom | 24In DC | 16.8W | Enhanced DC power supply |
| BMXCPS3020 | Gleichstrom | 24–48V DC | 31.2W | Wide‑range DC power supply |
| BMXCPS3500 | Wechselstrom | 100–240 V Wechselstrom | 36W | Standard AC power supply (this product) |
| BMXCPS4002H | Wechselstrom | 100–240 V Wechselstrom | 40W | High‑power AC supply for harsh environments |
Ersatz & Kompatibilitätsinformationen
Direkter Ersatz: BMXCPS3500 can replace legacy M340 series power supply modules.
Compatible Racks: BMXXBP0600, BMXXBP0800, BMXXBP1200, and other X80 series backplanes.
Incompatible: BMEXBP series backplanes (dedicated for EcoStruxure Control Expert platform).
- Official Ordering Code & Dokumentation
Official Ordering Code: BMXCPS3500 (standard version with no suffix)
Offizielles Handbuch: Schneider Electric SQD-BMXCPS3500.PDF
Zertifizierungen: CE, RCM, Merchant Navy, CSA, EAC, UL; konform mit EN 61131-2, IN 61000-6-4, usw.
- Engineering Implementation Recommendations
- Installationshinweise
Install the power supply module on the far left of the rack (recommended position).
Allow sufficient space for heat dissipation; avoid adjacent placement with high-power modules.
Use shielded cable for input power to reduce electromagnetic interference.
- Verkabelungsnormen
Correctly connect live (L), neutral (N), and protective earth (PE) Drähte.
Separate sensor power and I/O power terminals to avoid cross-connection.
High-current loads should be powered directly from external sources to reduce module load.
- Auswahlrichtlinien
Select the appropriate power supply based on total system power requirements, with 20–30% power margin.
Consider on-site power quality; install surge protectors and filters if necessary.
The Schneider BMXCPS3500 is a highly reliable, high-efficiency industrial power supply module that provides a complete power solution for the Modicon X80 platform. Its wide input voltage, multi-channel output, and comprehensive protection make it an ideal choice for medium-to-large PLC systems. If you need to verify BMXCP53500, please confirm the correct model number or contact Schneider Electric technical support for more information.
BMXCPS3500 is an isolated AC/DC switching power supply
that provides stable multi-channel 3.3V and 24V DC power for M340/M580 PLC racks. Its core operation consists of 5 stages:
- Input Processing (AC → High-Voltage DC)
Eingang: 100–240 V Wechselstrom (50/60 Hz)
EMI filtering: suppresses grid surges and high-frequency interference
Rectifier bridge: converts AC to pulsating high-voltage DC (ca. 310In DC)
Capacitive filtering: smoothes into stable high-voltage DC
- High-Frequency DC/DC Conversion (Core Stage)
PWM controller drives MOSFET high-frequency switching (tens of kHz)
High-frequency transformer:
Provides input-output electrical isolation (3000V und)
Converts high-voltage DC into multi-channel low-voltage high-frequency pulses
- Output Rectification & Filtering
Secondary high-frequency pulses → Schottky diodes / synchronous rectification → DC
LC filtering: smoothes ripple to produce clean, stable voltage
- Multi-Channel Regulated Output (Unique to BMXCPS3500)
3.3In DC / 4.5A: powers CPU, backplane bus, and I/O logic
24In DC / 1.3A: main power for rack I/O modules
24In DC / 0.9A: dedicated sensor power (isoliert, independent current limiting)
- Closed-Loop Regulation + Schutzmechanismus
- Voltage Regulation
Output voltage sampled via voltage division → compared with internal reference
PWM duty cycle dynamically adjusted to maintain constant output voltage
- Integrated Comprehensive Protection
Überspannung / undervoltage protection (input and output)
Überlast / Kurzschlussschutz (per-channel current limiting, hiccup recovery)
Overtemperature protection (power reduction or shutdown at excess temperature)
Internal fuse
- Status & Alarm
Front-panel READY LED: ON in normal operation, flashing in fault condition
Passive alarm relay:
Normal: contacts closed
Power loss / fault / overtemperature: contacts open (can connect to PLC or audible-visual alarm)
RESET-Taste: manually restarts the rack and resets faults
- Overall Operating Principle (Zusammenfassung)
Mains AC → Rectification & Filtering → High-Frequency Isolated Switching → Multi-Channel Rectification & Filtering → Closed-Loop Regulation → Distribution to CPU / E/A / Sensors via Backplane, with full protection and status monitoring.
- Typical Application Sequence
- Power-on → Input filtering and rectification
- Control circuit startup → PWM begins operation
- Outputs gradually establish → Regulation locks in
- READY LED illuminates → Alarm relay energizes → CPU startup enabled
- Fehler (Überstrom / overtemperature / power loss) → Outputs shut off immediately → Alarm relay de-energizes → Fault indication
Schütz,Leistungsschalter,Solarwechselrichter,Stromzähler,Solarbatterien