Wechat: +86-13184948252 WhatsApp: 0086-13811255435 E-Mail: kent@bestcontactor.com

Um Kontakt |

Schneider LC1DT60AM7 Schütz - Schütz,Leistungsschalter,Solarwechselrichter,Stromzähler,Solarbatterien

Schütz/

Schneider LC1DT60AM7 Schütz

Basic Parameters TeSys Deca Series 4-pole Contactor (4P 4NO) is specially designed for non-inductive loads, suitable for AC-1 applications such as resistance furnaces and lighting systems. Parameter Value Rated Operating Current 60A (at ambient temperature ≤60°C) Rated Operating Voltage Power circuit ≤690V AC/≤300V DC; Control circuit 220V AC 50/60Hz Number of Poles 4P (4 normalerweise offen ...

  • Produktdetails

Grundparameter

TeSys Deca Series 4-pole Schütz (4P 4NO) is specially designed for non-inductive loads, suitable for AC-1 applications such as resistance furnaces and lighting systems.

ParameterWert
Nennbetriebsstrom60A (at ambient temperature ≤60°C)
Rated Operating VoltagePower circuit ≤690V AC/≤300V DC; Control circuit 220V AC 50/60Hz
Number of Poles4P (4 normalerweise offene Kontakte)
Auxiliary Contacts1NEIN + 1NC (with NC mirror certification)
Electrical Service Life1.4 Millionen Operationen (60A, AC-1, Ue≤440V)
Mechanical Service Life6 Millionen Operationen
Control Coil CharacteristicsInrush power: 160VA at 50Hz / 140VA at 60Hz
Holding power: 15VA at 50Hz / 13VA at 60Hz
SchutzklasseIP20 (front panel)
CertificationsIEC, UL, CSA, CCC, EAC, Classification Society Certification, compliant with RoHS/REACh

Installation Dimensions

L×W×H: 122mm×70mm×120mm, Weight: 1.09kg

Mounting Methods:

DIN rail mounting (standard 35mm)

Screw mounting (M4 screws, maximum torque 3.1Nm)

Wiring Diagram

Main Circuit Wiring

4-pole main contacts: L1/L2/L3/L4 (power input) → T1/T2/T3/T4 (load output)

Terminal MarkingFunctionWiring Capacity
L1~L4Main contacts1~35mm flexible/solid wires (without terminals)
T1~T4(power/load connection)1~25mm flexible wires (with terminals)
Tightening Torque8Nm for 25~35mmcables
5Nm for 1~25mm cables

Control Circuit Wiring

Coil terminals: A1 (input), A2 (output), connected to 220V AC 50/60Hz control power supply

Auxiliary Contacts:

13-14: NEIN (normalerweise offen) Kontakte

21-22: NC (normalerweise geschlossen) Kontakte (with mirror certification)

Terminal MarkingFunctionWiring Capacity
A1, A2Coil connection1~4mm flexible/solid wires
1~2.5mm flexible wires with terminals
13-14Auxiliary contactsSame as coil terminals
21-22
Tightening Torque1.7Nm

Vorsichtsmaßnahmen bei der Verkabelung

  1. Power-off Operation: Cut off all power supplies and lock the circuit before wiring to prevent electric shock.
  2. Cable Selection:

Main circuit: Copper conductors ≥6mm² are recommended for 60A loads.

Control circuit: Copper conductors ≥1mm² are recommended.

  1. Terminal Fastening:

Main contacts: Use a torque wrench to ensure the specified torque is achieved.

Control terminals: Tighten moderately (1.7Nm) to avoid terminal damage.

  1. Application of Auxiliary Contacts:

NO contacts are commonly used for self-locking control.

NC contacts are used for interlocking or fault indication.

Anwendungsszenarien

Control of industrial heating equipment (resistance furnaces)

Main switch for lighting systems

On/off control of non-inductive loads

Power switching for star-delta motor starting (used with other contactors)

Mounting Methods of Schneider LC1DT60AM7 Contactor

Schneider LC1DT60AM7 contactor offers two standard mounting methods:

  1. DIN-Schienenmontage (Recommended)

Suitable for quick installation and replacement in control cabinets, compatible with standard 35mm DIN rail (EN 60715 Standard)

Mounting Steps:

  1. Align the rail clips on the back of the contactor with the upper edge of the 35mm DIN rail.
  2. Press the contactor downward while pushing it toward the rail until aclicksound is heard, indicating the clips are locked in place.

Removal Method:

Gently pry the spring clips at the bottom of the contactor with a screwdriver and push it downward slightly to disengage from the rail.

  1. Direct Screw Mounting

Suitable for fixed installation scenarios without DIN rails

Mounting Steps:

  1. Use 3 M4 screws (spring washers and flat washers are recommended).
  2. Fix the contactor through the 3 mounting holes on its back: 2 at the top and 1 at the bottom.
  3. Tighten the screws with torque controlled within 3.1Nm to prevent housing damage.

Vorsichtsmaßnahmen bei der Installation

  1. Position and Orientation

Must be installed vertically (tilt angle ≤5°) to ensure the normal operation of internal mechanisms and heat dissipation.

The coil terminal A1 should face upward, complying with operational habits and visual indication requirements.

  1. Environment and Space

Select a dry and well-ventilated location, away from heat sources and humid areas.

Reserve sufficient space (≥100mm) for arc flash and heat dissipation to avoid damage to adjacent components.

  1. Erdungsanforderungen

The metal mounting base must be properly grounded (PE) to ensure safety.

When using DIN rail mounting, the rail should be connected to an earthed conductive backplane.

  1. Wiring and Fixing

All terminals (including unused ones) must be tightened to ensure good contact.

Tightening torque for main circuit terminals: 8Nm for 25~35mm² cables; 5Nm for 1~25mm² cables.

Tightening torque for control circuit and auxiliary contact terminals: 1.7Nm.

The LC1DT60AM7 contactor provides flexible mounting options: 35mm DIN rail mounting is convenient and fast, suitable for standardized layout of control cabinets; M4 screw mounting is stable and reliable, applicable to special installation environments. Regardless of the method, vertical installation and good grounding must be ensured to guarantee the contactor’s performance and service life.

Vorher:

Nächste:

Hinterlasse eine Antwort