MLFB Order Code Breakdown
3RW 44 43 6 B C 4 4
- 3RW: SIRIUS soft starter product series
- 44: High-performance built-in bypass 3-phase fully controlled Softstarter (independent thyristor regulation per phase, integrated bypass contactor as standard)
- 43: Größencode, Nennstrom 203 A bei 40 °C for standard loads
- 6: Control circuit terminal type = screw terminals; main circuit connected via copper busbars
- B: Integrated bypass contactor (2/3-phase bypass for zero loss during steady-state operation)
- C: Independent 3-phase thyristor control (full 3-phase control to balance 3-phase currents)
- 4: Control supply voltage Us = AC 230 V
- 4: Main circuit operating voltage Ue = AC 200~460 V
- Elektrische Kernparameter (40 °C, Klasse 10 Standard Load)
| Artikel | Parameterwert |
| Rated current for standard wiring (motor directly connected to soft starter) | 203 A |
| Matched motor power at 400 V | 110 kW |
| Rated current for inside-delta connection (motor windings split into two branches) | 352 A |
| Matched motor power at 400 V for inside-delta wiring | 200 kW |
| Spannungsbereich des Hauptstromkreises | AC 200~460 V (50/60 Hz) |
| Control supply | Wechselstrom 230 V ±10% |
| Phase control mode | Anti-parallel thyristors per phase with independent regulation |
| Standardfunktionen | Integrated bypass contactor to bypass thyristors during running |
| Standard overload trip class | Klasse 10; Klasse 10/20/30 configurable manually |
| Schutzfunktionen | Phasenverlust, phase unbalance, Motorüberlastung, Überhitzung, thyristor short-circuit, start timeout, earth fault detection |
| Communication expansion | Profibus DP compatible (requires 3RW4900-0KC00 communication module) |
| Gewicht | Ca. 11.2 kg |
| Country of origin | Deutschland |
III. Lastabgleich & Selection Limits
- Anwendbare Lasten
Wasserpumpen, Fans, Förderbänder, Luftkompressoren, Kältemaschinen, centrifugal equipment (feste Geschwindigkeit, only smooth start/stop required)
- Derating Reference for Heavy-Duty Operation (40 °C)
Klasse 20 Schwerlastbetrieb (häufige Starts, high starting torque): permissible current 170 A, matched motor 90 kW
Klasse 30 extra heavy duty (Kugelmühlen, Brecher): permissible current 145 A, matched motor 75 kW
- Prohibited Operating Conditions
Continuous speed regulation, frequent forward/reverse switching, high-frequency jogging (≥30 times per hour)
- Hardware Structure & Beschreibung der Verkabelung
- Hauptstromkreis: Copper busbar terminals; L1/L2/L3 line side input, T1/T2/T3 motor side output; supports standard wiring and inside-delta wiring
- Steuerkreis: Screw terminals for start/stop signals, fault outputs, reset, external thermistor input
- Bedienfeld: Built-in LCD display for setting start ramp, initial voltage, sanfter Stopp, current limit and protection thresholds
- Installation: Vertikale Wandmontage; minimum 150 mm top/bottom clearance for heat dissipation; ambient temperature 0~40 °C (derate for temperatures above 40 °C)
- Produktlebenszyklus & Ersatzmodelle
- Status: 3RW44 series discontinued (PLM: PM490 end-of-support phase); original manufacturer stops mass production, only stock spare parts available
- Direct OEM Replacement Model (Recommended for New Projects)
3RW5543-6HA14 (new-generation 3RW55 series, same 203 Ein Nennstrom, 230 V control supply, 200-460 V main voltage, Schraubklemmen, integrierter Bypass)
- Differences Between Old & Neue Modelle
Smaller footprint, geringerer Stromverbrauch, native Modbus RTU and optimized protection logic for 3RW55
Different mounting cutout dimensions; copper busbars and mounting brackets need modification during cabinet retrofit
- Recommended Matching Protection Devices
- Main Circuit Short-Circuit Protection: Moulded case circuit breaker matched to 110 kW motor circuit
- Specialized Thyristor Protection: aM/gR ultra-fast fuse 500 V 315 A (mandatory upstream of soft starter, no thyristor short-circuit protection without it)
- Additional Motor Protection: External PTC thermistor connectable to control terminals for winding overtrip protection
VII. Typical Troubleshooting Matrix
| Fehlersymptom | Grundursache | Lösung |
| Overheating alarm during startup | Blocked cooling air duct / ambient temp above 40 °C / long-duration heavy-load startup | Clean dust, Verbesserung der Schrankbelüftung, upgrade to higher-rated soft starter |
| Phase loss alarm | Single-phase power loss, loose busbar connection, broken motor winding | Verkabelung festziehen, measure 3-phase input voltage and motor winding resistance |
| Unrestricted starting current, direct full voltage output | Broken-down thyristors, welded bypass contactor contacts | Disconnect power supply to test thyristors; replace bypass contact module |
| Startup timeout trip | Too low initial voltage, seized mechanical load, insufficient ramp time | Increase initial voltage, inspect mechanical load, extend start ramp time |
VIII. Hauptvorteile
- Independent 3-phase voltage regulation; eliminates 3-phase current unbalance common in 2-phase soft starters, extending motor bearing service life
- Integrated bypass eliminates thyristor power loss during steady operation, delivering over 98% energy saving vs non-bypass models
- Supports soft stop and pump stop water hammer suppression, ideal for water supply, drainage and HVAC systems
- Comprehensive integrated motor protection, eliminating the need for separate thermal overload relays
Full Dimension Specifications of Siemens 3RW4443-6BC44
- Overall Equipment Dimensions (B × H × T, Einheit: mm)
210 (Breite) × 230 (Höhe) × 298 (Tiefe)
- Mounting Cutout & Fixing Dimensions
- Horizontal center distance between mounting holes: 167 mm
- Vertical center distance between mounting holes: 190 mm
- Fastener specification: M8 bolt, Anzugsdrehmoment 15 N·m
- Cabinet panel cutout minimum reserved width ≥210 mm, height ≥230 mm
III. Mandatory Minimum Cabinet Clearance for Heat Dissipation (Vertical Wall Mount)
Top clearance: ≥100 mm
Bottom clearance: ≥75 mm
Side clearance (multiple units side-by-side): ≥5 mm
Equipment rear surface to cabinet backplate: direct contact permitted
- Outer Carton Dimensions (Lagerung & Logistics Reference)
348 × 433 × 394 mm, net weight 11.22 kg
- Ergänzende Hinweise
- Schutzklasse: IP00; for cabinet installation only
- All 3RW4443 variants (-6BC34/-6BC44/-2BC45) share identical overall dimensions; differences only in control terminals and supply voltage
- Replacement model 3RW5543-6HA14 has a smaller footprint; recalculate cabinet cutout size for retrofits
Complete List & Function Definition of Control Terminals – Siemens 3RW4443-6BC44
This model is equipped with screw-type control terminals, categorized into five groups: Steuerstromversorgung, digitale Eingänge, motor PTC temperature sensing, programmierbare Relaisausgänge, general fault relay.
- Control Power Supply Terminals (Unit Main Supply)
- A1, A2
Funktion: Main control power supply for soft starter
Model rating: Wechselstrom 230 V ±10%, 50/60 Hz
Wiring rule: A1 live line L, A2 neutral line N
- PE
Control circuit protective earth terminal; connect to cabinet earth busbar
- L+, L-
Built-in internal DC24 V auxiliary supply for passive digital input switches; extern 24 V power supply not required
L+ = DC24 V positive pole; L= DC24 V negative pole (Gemeinsamkeit)
- 4 Programmable Digital Input Terminals IN1 / IN2 / IN3 / IN4
Logik: Connect one end of switch to L+, the other end to corresponding INx to trigger assigned function; all functions configurable via panel parameters
Factory Default Allocation
IN1: Motor start (Parameter Group 1 Vorwärtsdrehung)
IN2: Unassigned
IN3: Unassigned
IN4: Fault trip reset
All Customizable Functions
Local manual mode, emergency start, low-speed creep, fast emergency stop, fault reset, 3 groups of forward/reverse motor parameter switching
III. Motor Winding Temperature Sensing Terminals T1, T2
For external motor PTC thermistor connection (motor overheat protection)
Soft starter trips automatically when winding temperature exceeds threshold
Short-circuit T1 and T2 if no PTC fitted to disable thermal protection
- 3 Independent Programmable Relay Outputs (Passive dry contacts, AC250 V / 5 A)
Each pair consists of normally-open contacts with fully assignable functions via parameter menu
- 13, 14 Ausgabe 1
Standard: Motor running signal (closes after startup completion and bypass contactor pull-in)
- 23, 24 Ausgabe 2
Standard: Unassigned; configurable for bypass status, startup-in-progress, Voralarm, DC braking, usw.
- 33, 34 Ausgabe 3
Standard: Unassigned; customizable for all types of equipment status signals
- General Fault Relay Terminals 95, 96, 98 (Global Fault Alarm)
3-pole changeover contact for unified fault signaling, widely used in safety circuits
95: Common terminal COM
95-96: Normalerweise geschlossen (NC): conductive when unit healthy; opens upon fault trip
95-98: Normalerweise geöffnet (NEIN): closes when fault occurs, for fault indicator light / alarm horn wiring
Terminal Summary Table
| Terminal Group | Terminalnummer | Core Purpose |
| Steuerstromversorgung | A1, A2 | AC230 V control voltage input |
| Schutzerde | PE | Control circuit grounding |
| Eingebaut 24 V Supply | L+, L- | DC24 V power for digital inputs (positive / Boden) |
| Digitale Eingänge | IN1, IN2, IN3, IN4 | Start/stop, reset, parameter switchover, manual mode etc. |
| PTC Temperature Sensing | T1, T2 | Motor winding overheat thermistor interface |
| Relaisausgang 1 | 13, 14 | Motor running status (normalerweise offen) |
| Relaisausgang 2 | 23, 24 | Customizable equipment status (normalerweise offen) |
| Relaisausgang 3 | 33, 34 | Customizable equipment status (normalerweise offen) |
| Fault Changeover Contact | 95, 96, 98 | Global fault alarm (COM + NC + NEIN) |
Supplementary Wiring Guidelines
- Tightening torque for control wires: 1.2~1.5 N·m; wire cross-section 0.75~1.5 mm² copper conductors
- Digital inputs are passive contact type; power solely from internal L+/Lwithout external PLC 24 V-Versorgung
- Series the normally closed 95/96 contacts in safety circuit to cut upstream contactor power on fault
- Profibus communication requires separate 3RW4900-0KC00 module with dedicated port (not part of front control terminals)