Siemens 7NG3211 Head-Mounted Pt100 Temperature Transmitter
- Grundlegende Produktpositionierung
7NG3211 corresponds to SITRANS TH100. It is a 2-wire 4–20 mA head-mounted transmitter dedicated exclusively to Pt100 without HART communication. It only supports resistance temperature detectors (RTDs) and is incompatible with thermocouples. Designed to fit DIN Type B connection heads (44 mm round), it serves as a general-purpose basic temperature transmission module for chemical, power and HVAC industries.
Full Order Code Breakdown (7NG3211-XNNXX)
Take common models `7NG3211-0AN00` and `7NG3211-1NN00` as examples:
- 7NG3211: Fixed series prefix, representing standard round plastic housing of TH100
- 1st suffix digit: Explosion-proof certification
0 = Intrinsically safe ATEX Ex ia/ib and NEPSI certification (for Zone 0/1 Gefahrenbereiche)
1 = Standard non-explosion-proof type (for ordinary safe areas)
- 2nd character A/N: No electrical isolation (all TH100 variants feature no isolation)
- Last three digits 00: Standard terminals, no optional extra functions
- Kernelektrik & Measurement Specifications
2.1 Eingang (Pt100 IEC60751 only)
Wiring compatibility: 2-wire / 3-wire / 4-wire Pt100, configurable via software
Messbereich: -200 ~ +850°C
Minimum span: 25°C; Maximum span: 1050°C
Maximum total wire resistance: ≤20 Ω (suitable for long cables)
Measuring current: 0.4 mA, with immunity to 50/60 Hz power frequency interference
Genauigkeit (at 23°C ambient temperature): ≤0.1%FS; Temperature drift ≤0.1%FS per 10°C; Repeatability <0.1°C
Sensor fault signal (offener Stromkreis / Kurzschluss): Compliant with NAMUR NE43, configurable as either low fault level (3.6 mA) or high fault level (22.8 mA)
Filter damping: Einstellbar von 0 Zu 30 s via software, factory preset to 0 S
Verpolungsschutz, 12-bit resolution
2.3 Umweltfreundlich & Mechanische Parameter
Betriebstemperatur: -40°C ~ +85°C (transmitter body)
Abmessungen: Φ44 mm, Dicke 20.8 mm; Gewicht: 50 G
Max cross-section of cable for terminals: 2.5 mm²
Schutzstruktur: Potting plastic housing, compatible with standard temperature sensor connection heads
- Terminaldefinition & Verdrahtung
Six terminals in total, divided into power circuit (Terminals 1, 2) and Pt100 sensor circuit (Terminals 3, 4, 5, 6)
- Terminal 1 (+): Positive pole of 24 V DC-Stromversorgung
- Terminal 2 (-): Negative pole of 4–20 mA signal (shared ground for 2-wire loop)
3/4/5/6: Terminals for Pt100 RTD wiring
3-wire Pt100: Terminals 3 Und 4 connect to two ends of RTD, Terminal 5 for compensation wire, Terminal 6 vacant
4-wire Pt100: Terminals 3&4 as one pair, Terminals 5&6 as another pair to eliminate lead resistance error
Critical note: Nach der Verkabelung, 2/3/4-wire Pt100 mode must be matched via SIPROM T software; otherwise severe temperature deviation will occur.
- Konfiguration & Calibration Method
- Mandatory tools: SIPROM T configuration software + dedicated USB modem
- Configurable parameters:
Upper/lower measuring range limits, temperature unit (°C / °F)
Switch between 2-wire / 3-wire / 4-wire Pt100 modes
Filter damping time, sensor offset compensation (±100°C)
Fault output level (low limit: 3.6 mA / high limit: 22.8 mA)
- Einschränkung: No HART protocol support. Calibration via handheld communicator is unavailable; offline configuration via computer USB only.
- Explosion-Proof Certification List (0AN00 Explosion-Proof Model)
ATEX Ex ia IIC T4/T5/T6, FM and NEPSI intrinsic safety certifications. Applicable for flammable and explosive working conditions in Zone 0/1; Compliant with dust explosion protection Zone 21/22 Standards.
- Kernunterschiede: TH100 (7NG3211) vs TH200 vs TH320
| Modell | Order Prefix | Kommunikation | Eingabetyp | Isolierung | Anwendungsszenario |
| TH100 7NG3211 | 7NG3211 | Pure 4–20 mA, no HART | Pt100 only | No isolation | Low-cost temperature measurement with ordinary Pt100 |
| TH200 7NG3212 | 7NG3212 | With HART | Pt100 only | No isolation | Remote calibration via handheld communicator required |
| TH320 7NG3213 | 7NG3213 | HART | Universal (Pt100 + Thermoelement) | Elektrische Isolierung | Sites with multiple sensors and heavy electromagnetic interference |
- Typical Troubleshooting Matrix
| Fehlerphänomen | Grundursache | Lösungsschritte |
| Consistently low / high temperature reading | 1. Mismatch between wiring mode and software configuration | 1. Verify 2/3/4-wire configuration |
| 2. Incorrect range setting | 2. Rewrite correct measuring range | |
| 3. Pt100 lead resistance exceeds 20 Oh | 3. Use thicker compensation wires | |
| Fixed output at 3.6 mA / 22.8 mA | Pt100 open circuit or short circuit | Measure sensor resistance with multimeter, replace RTD |
| No 4–20 mA current output | 1. Supply voltage below 8.5 V | 1. Ensure loop voltage ≥ 10 V |
| 2. Reverse positive and negative poles | 2. Swap power terminals 1 Und 2 | |
| 3. Broken circuit loop | 3. Inspect rear PLC / instrument circuit | |
| Frequent fluctuating readings | No damping setting, power frequency interference | Set damping time 3~10 s in SIPROM T; Single-end grounding for shielded signal cables |
- Alternative Selection Solutions
- Upgraded models with identical head-mounted installation form factor
Remote calibration with HART required: 7NG3212 TH200
Thermocouple compatible with electrical isolation: 7NG3213 TH320
- Domestic substitutes for discontinued / out-of-stock units: 44 mm round head-mounted 2-wire 4–20 mA Pt100 transmitters with fully compatible mounting dimensions
- DIN rail mounted alternative: Siemens SITRANS TR100 DIN rail temperature transmitter module
- Industrial Application Scenarios
Energiewirtschaft: Temperature measurement for boilers, steam turbines and auxiliary equipment bearings
Chemisch & petrochemical industry: Explosion-proof temperature acquisition for pipelines and reactors
Pharmazeutisch & food industry: Temperature monitoring for sanitary tanks and heat exchangers
HVAC: Pt100 temperature detection for air ducts and chillers
Output Signal of Siemens 7NG3211 (SITRANS TH100)
- Standard output type: 2-wire 4~20 mA analog current signal
- No HART protocol support: Pure analog current output only, digital communication not available
- Signal correspondence:
Minimum measuring temperature → 4 mA
Maximum measuring temperature → 20 mA
- Two optional fault outputs (compliant with NAMUR NE43, software configurable):
Low fault level: 3.6 mA (sensor open circuit)
High fault level: 22.8 mA (sensor short circuit)
- Over-range output: 3.84 mA when measured value below lower range limit; 20.5 mA when measured value above upper range limit
- Power supply and signal share two wires; loop load driven by 24 V DC-Stromversorgung.
Full Accuracy Specifications of Siemens 7NG3211 (SITRANS TH100)
(Standard test condition at 23°C specified in original manufacturer manual)
- Overall Basic Measuring Accuracy (Key Indicator)
- Span < 250°C: Maximum error <0.25°C
- Span > 250°C: Maximum error <0.1%FS (Voller Maßstab)
- Nominal overall basic error for the unit: <0.1% of measuring span (at 23°C ambient temperature)
Calculation Examples for Intuitive Understanding
Range 0~100°C (span 100°C < 250°C): Max error ±0.25°C
Range 0~500°C (span 500°C > 250°C): 500 × 0.1% = ±0.5°C
- Repeatability Accuracy
<0.1°C, minimal fluctuation in repeated temperature measurements
- Temperature Drift (Additional error induced by ambient temperature variation)
Max drift value: 0.1%FS per 10°C
Beispiel: 20°C ambient temperature fluctuation brings an extra 0.2% full-scale error
- Other Additional Error Terms
- Supply voltage influence: <0.01%FS per V
- Load resistance influence: <0.025%FS per 100 Oh
- Long-term drift: <0.025%FS per month
- Measuring resolution: 14-bisschen
- Ergänzende Bemerkungen
- Stated accuracy only applies to the transmitter body, excluding inherent error of Pt100 sensor itself.
- No built-in electrical isolation; extra measuring deviation will be introduced at sites with severe electromagnetic interference.
- 2/3/4-wire Pt100 mode must be correctly configured via SIPROM T software; otherwise systematic deviation of several degrees Celsius will occur.
Translation Notes for Industrial Standard Terms
Schütz,Leistungsschalter,Solarwechselrichter,Stromzähler,Solarbatterien