Danfoss SV4 series direct-acting low-side liquid level regulating valve, model 027B2024, designed for precise liquid level control in refrigeration and air-conditioning systems. Kv = 0.23 m³/h, maximum working pressure 28 Bar, maximum differential pressure Δp = 23 Bar. Compatible with ammonia (R717) and fluorocarbon refrigerants, with multiple installation and injection options.
1 Model Code Explanation
| Codesegment | Bedeutung |
| SV4 | Produktserie: direct‑acting low‑side liquid level regulating valve, Typ 4 (orifice diameter 3.0 mm) |
| 027B2024 | Danfoss official order number: complete float valve (with float chamber) |
| Notiz | Version without float chamber: 027B2014; matching flange: 027B2027 |
2 Technische Spezifikationen
| Parameter | Wert | Bemerkungen |
| Kv value | 0.23 m³/h | Orifice diameter 3.0 mm |
| Cv value | 0.27 gal/min | – |
| Maximum working pressure (MWP) | 28 Bar (406 psig) | – |
| Maximum allowable differential pressure (Δp) | 23 Bar (334 psi) | Specific to SV4 series |
| Test pressure (MTP) | 42 Bar | – |
| Temperature range | –50°C ~ 120°C | Media temperature |
| Inlet connection size | 21.8 mm | Solder connection |
| Equalizer connection | 1 inch | Solder connection |
| Suitable refrigerants | R134a, R22, R404A/R507A, R717 (ammonia), usw. | Compatible with most non‑flammable refrigerants |
| Materials | Valve body: low‑temperature cast steel | Complies with EN‑GJS‑400‑18‑LT |
| Float chamber: ST 35.8 steel | ||
| Seals: non‑asbestos materials | ||
| Gewicht | Gross 25.91 kg | – |
| Net 24.5 kg | ||
| Approvals | CE, EAC, UL, UKCA | PED Category II |
3 Nennkapazität
| Refrigerant | Kapazität (TR) | Kapazität (kW) | Test conditions |
| R717 (ammonia) | 29 TR | 102 kW | Evaporation temp. +5°C, condensing temp. +32°C, subcooling 4 K |
| R22 | 5.97 TR | 21 kW | – |
| R134a | 4.66 TR | 16.4 kW | – |
| R404A/R507A | 4.38 TR | 15.4 kW | – |
4 Hauptmerkmale
- Zuverlässiger Betrieb: Stable mechanical structure, adapts to varying operating conditions
- Precise regulation: Maintains stable liquid level under changing loads
- Einfache Wartung: Orifice insert and filter can be replaced without emptying the float chamber
- Flexible installation: Available with or without float chamber
- Multiple injection methods: Direct injection into float chamber, evaporator or equalizer vessel
- High-quality materials: Low-temperature cast steel body, ST 35.8 float chamber, non-asbestos gaskets
5 Application Methods
| Injection method | Anwendung | Installation requirement |
| Direct injection into float chamber | Small and medium‑sized systems | Remove 4 M6 screws (pos. 23), plug pos. 24 |
| Direct injection into evaporator | Large evaporators / long pipelines | Remove pos. 24, install solder connection, keep pos. 23 |
| Direct injection into equalizer vessel | Special system designs | Remove 4 M6 screws (pos. 23), plug pos. 24 |
| Capacity adjustment | When capacity is excessive | Remove only 2–3 M6 screws to limit injection flow |
6 Operating Conditions & Limitations
Applicable systems: Low-side liquid level regulation in refrigeration, freezing and air-conditioning systems
Suitable refrigerants: Ammonia (R717) and common fluorocarbons (R22, R134a, R404A, usw.)
Not recommended: Use with flammable hydrocarbons (contact Danfoss if required)
PED classification: Category II, compliant with European Pressure Equipment Directive
7 Installation & Wartung
- Float setting
Rotate main spindle counterclockwise until valve closes (audible click)
Rotate clockwise until valve opens (audible and tactile feedback)
Rotate an additional ½ turn to complete setting and mark position
- Filter cleaning: Inspect and clean filter regularly to ensure stable flow
- Seal kit: Spare part number 027B2070, includes all required seals
- Special orifices: For reduced capacity, replace orifice (1.0–2.8 mm available), spare part numbers 027B2080–027B2083
8 Bestellinformationen
| Beschreibung | Bestell-Nr. | EAN |
| SV4 Float Valve (with float chamber) | 027B2024 | 5702422148319 |
| SV4 Float Valve (without float chamber) | 027B2014 | – |
| Mounting flange (for version without float chamber) | 027B2027 | – |
| Seal kit | 027B2070 | – |
9 Alternative Modelle & Series Comparison
| Modell | Orifice diameter | Kv value | Max | Nennkapazität (R717) | Bestell-Nr. |
| SV4 | 3.0 mm | 0.23 | 23 Bar | 102 kW | 027B2024 |
| SV5 | 3.5 mm | 0.31 | 21 Bar | 138 kW | 027B2025 |
| SV6 | 4.0 mm | 0.43 | 19 Bar | 186 kW | 027B2026 |
10 Key Documents
- Technical manual: Modulating liquid level regulators, direct operated, for low pressure side, types SV 4, 5 Und 6 (Doc. NEIN. 103040)
- Installation guide: Danfoss SV 4 Float Valve Installation Guide
- Spare parts catalogue: RK0XG
Schütz,Leistungsschalter,Solarwechselrichter,Stromzähler,Solarbatterien