Complete Technical Parameters of Siemens 3WL1116/3WL1216 1600A ETU45B-G-LCD-3P

The parameters cover dimensions including basic electrical characteristics, capacidad de ruptura, trip unit, mechanical & environmental performance, communication and installation, facilitating engineering selection and system matching.

  1. Parámetros eléctricos básicos
Elemento de parámetroSpecification ValueObservaciones
Serie de productosSiemens SENTRON 3WLDisyuntor de aire (ACB)
Frame Size3WL1116 (Frame I) / 3WL1216 (Frame II)3WL1116: Standard breaking capacity; 3WL1216: High breaking capacity
Corriente nominal (En)1600AFrame size current 1600A, setting range 0.4–1In
Número de polo3PAGThree-pole, 3-phase main circuit
Rated Operational Voltage (Ue)690V y50/60Hz, Cumple con IEC 60947-2
Tensión nominal de aislamiento (interfaz de usuario)1000V yBenchmark value for insulation withstand capability
Rated Impulse Withstand Voltage (Uimp)12kVCompliant with IEC 60947-1
Rated Short-time Withstand Current (Icw)Frame I: 66kA/1s; Frame II: 80kA/1sEnsures short-time thermal stability at 500V
Capacidad de ruptura (uci)Frame I: 55/66el; Frame II: 80/100elUltimate breaking capacity at 500V; Frame II offers higher breaking capacity
  1. Parameters of ETU45B-G-LCD Electronic Trip Unit
Function ModuleSpecification ValueDescripción
Tipo de protecciónLSIG (l: Overload/Long-time Delay; S: Short-circuit/Short-time Delay; I: Instantaneous Short-circuit; GRAMO: Ground Fault)Complete power distribution protection configuration
Protección contra sobrecarga (l)Characteristic Curve: I²t/I⁴t selectable; Setting Range: 0.4–1InI⁴t characteristic improves selectivity with downstream devices
Short-time Delay Short-circuit Protection (S)Configuración actual: 2–10In; Time Delay: 0.1–0.4sAdjustable inverse/definite time delay to prevent selective tripping
Instantaneous Short-circuit Protection (I)Configuración actual: 2–10InRapid short-circuit current interruption without time delay
Protección de falla a tierra (GRAMO)Configuración actual: 0.2–0.8In; Time Delay: 0.1–2sDetects ground faults to avoid equipment damage
Mostrar & OperationLCD screen, rotary coding switchReal-time display of current, trip cause and fault records
Método de reinicioManual/Auto selectableQuick power supply recovery after fault clearance

III. Mechanical & Environmental Parameters

Elemento de parámetroSpecification ValueObservaciones
Vida mecánica150,000 operacionesNo-load operation, Cumple con IEC 60947-2
Vida eléctrica10,000 operaciones (AC-3, at rated current)On-load breaking life, related to operating frequency
Operating MechanismSpring-loaded energy storage type (manual/electric optional)Electric mechanism suitable for remote control
Contactos auxiliaresStandard: 2NO+2NC, expandable to 4NO+4NCStatus feedback and control circuit interlocking
Temperatura ambiente-25℃~+70℃ (operating); -40℃~+85℃ (storage)Wide temperature range for industrial applications
Clase de protecciónIP30 (body); IP40 (with protective cover)Prevents solid foreign object intrusion
Altitud≤2000m (derating required above 2000m)Rated current derating by 1% for every 100m altitude increase
Método de montajeFixed type/Drawout typeDrawout type enables maintenance without power outage
  1. Communication & Measurement Parameters
FunciónEspecificaciónInterface/Protocol
Communication ModuleCOM15 (PROFIBUS DP) / COM16 (MODBUS RTU)Opcional, supports data upload to monitoring system
Measurement AccuracyCurrent: ±1%; Voltage: ±1.5%; Power: ±2%Compatible with Plus measurement function for energy management
Data Logging100 fault records (trip type, time, current value)Fault tracing and system diagnosis
Mando a distanciaSupports remote opening/closing and parameter settingRealized by electric mechanism + communication module
  1. Instalación & Dimension Parameters
Mounting TypeAncho (W.)Height (h)Depth (D)Peso
3WL1116 Fixed Type320milímetros434milímetros291milímetrosAprox.. 45kilos
3WL1116 Drawout Type320milímetros434milímetrosAprox.. 450milímetrosAprox.. 55kilos
3WL1216 Fixed Type460milímetros434milímetros291milímetrosAprox.. 56kilos
3WL1216 Drawout Type460milímetros434milímetrosAprox.. 450milímetrosAprox.. 65kilos
Mounting Mode35mm DIN rail/screw mountingFrame I width: 320milímetros; Frame II width: 460milímetros; Unified height: 434milímetros
  1. Key Selection & Application Tips
  2. Breaking Capacity Matching: Select frame size based on the system’s maximum short-circuit current. Frame I is suitable for scenarios ≤66kA, while Frame II is for ≤100kA. A 20% margin is recommended.
  3. Trip Unit Setting: Enable LSIG protection for motor loads, with the ground fault setting recommended at 0.3–0.5In. LSI protection is sufficient for power distribution loads.
  4. Communication Compatibility: Select COM15/COM16 module for remote monitoring, ensuring protocol compatibility with PLC/SCADA systems (PROFIBUS/MODBUS).
  5. Espacio de instalación: The drawout type occupies approximately 160mm more depth than the fixed type. Reserve sufficient operation and maintenance space during cabinet design.
  6. Replacement & Upgrade: The 3WL series has been upgraded to the 3WA series (p.ej., 3WA1116-3EG45-4GA4), featuring compatible dimensions and protection functions, plus added Ethernet communication and intelligent diagnosis.

 

 

VII. Cumplimiento & Proceso de dar un título

Compliant Standards: ES 14048.2, CEI 60947-2, EN 60947-2

Certificaciones: CE, UL, CSA (for some models), meeting compliance requirements for global industrial applications