Marca: pentrónico (Suecia), a Nordic manufacturer of high-precision sensores de temperatura. El 5810080 La serie es un detector de temperatura de resistencia industrial Pt100 ensamblado. (IDT). It is often mistakenly referred to as a thermocouple in the industry; this distinction is critical.
- Explicación del código del modelo
5810080: Serie de productos, assembled industrial platinum RTD with terminal head and protection thermowell
-001: Versión / construction suffix, representing single Pt100 element, Class A accuracy, base version with standard thermowell material, probe length and thread specification
Other variants within the series include 5810080-002 y 5810080-003, commonly dual Pt100 elements, alternative probe lengths or pressure ratings.
- Especificaciones técnicas básicas
| Artículo | Especificación |
| Elemento sensor | Pt100 Platinum RTD (compliant with IEC60751) |
| Clase de precisión | Clase A |
| Rango de temperatura | -200℃ ~ +500℃ (depends on thermowell material) |
| Configuración de cableado | Standard 4-wire (3-wire optional). The 4-wire design eliminates lead resistance error and is preferred for high-precision measurement |
| Thermowell Material | 316L acero inoxidable (estándar); Hastelloy or Titanium optional for highly corrosive media |
| Probe Construction | Solid mineral-insulated / drilled protection tube, vibration-resistant structure (Pentronic thermally conductive filling for faster response) |
| Terminal Head | Aluminium waterproof head, IP65; built-in temperature transmitter optional (4-20salida mA) |
| Montaje | Threaded installation (G1/2, M20×1.5 commonly used), compatible with protection thermowell |
| Tiempo de respuesta | t0.5: aprox. 2~8s (in liquid media, subject to probe diameter) |
| SIL | SIL2 loop assessment available (dual-element version 5810080-002) |
- Características principales
- Excellent stability: Class A platinum wire with annual drift as low as 0.05℃, suitable for long-term continuous process measurement
- Vibration-resistant construction: Internal metal filling reduces air gaps, withstands vibration for temperature measurement on compressor, pump and turbine casings
- Replaceable insert: Sensing element is a removable insert. Sensor core can be replaced without removing the thermowell, cutting downtime maintenance cost
- Corrosion-resistant options: Custom Hastelloy and Monel thermowells available for corrosive chemical service
- Accesorios opcionales: Built-in HART temperature transmitter providing direct 4–20mA signal to DCS/PLC
- Escenarios de aplicación típicos

pentrónico 5810080-001 Sensor de temperatura
Thermal power, aceite & gas, químico, paper and pharmaceutical industries; temperature measurement of pipelines, equipment casings and tank media; high-precision temperature acquisition for TSI and process control loops.
Frequently paired with Bently Nevada TSI systems for unit temperature monitoring.
- Instalación & Directrices de puesta en marcha
- Instalación: Protection thermowell is recommended for online replacement. Probe insertion depth ≥ 8~10 times thermowell inner diameter to ensure accurate temperature reading
- Alambrado: 4-wire Pt100 with two excitation wires and two measurement wires. Must not be used with thermocouple extension wires
- Blindaje: Cable shield single-point grounded inside terminal head to avoid common-mode interference; ruta alejada de los cables de alimentación
- Calibración: Calibre los valores de resistencia según IEC60751 utilizando un calibrador de bloque seco o un baño de aceite a temperatura constante
- Versiones a prueba de explosiones: A partir de ahora / Ex d disponible; Los certificados deben verificarse para la selección de áreas peligrosas.
- Lista de verificación de solución de problemas comunes
- Fluctuación de temperatura: Conexiones de cables flojas, puesta a tierra multipunto del blindaje, Aflojamiento del terminal causado por la vibración del campo.
- Persistentemente alto / lecturas bajas: La sonda no está completamente sumergida en el medio., termopozo sucio, resistencia excesiva del plomo (cambiar a configuración de 4 cables)
- Alarma de circuito abierto: Alambre de platino roto o daño por flexión en la raíz (visto con frecuencia en condiciones de vibración)
- Mayor deriva: Envejecimiento del elemento de platino después de un funcionamiento prolongado a temperatura excesiva
- Serie alternativa & Referencia de selección
| Modelo | Construcción | Solicitud |
| 5810080-001 | Pt100 único, Clase A | Medición de temperatura de un solo punto para procesos generales |
| 5810080-002 | Pt100 doble, Clase A/A | Medición redundante, Bucle SIL2 |
| 5810080-003 | Elemento único, sonda extendida / termopozo de alta presión | inserción profunda, high-pressure pipelines |
contactor,cortacircuitos,sensor,Codificador,SOCIEDAD ANÓNIMA,Convertidor