ABB MS116-4.0 Technical Datasheet (Manual Motor Starter / Motor Protection Circuit Breaker) Key Overview: 3-polo, rated current 4.0A (adjustable 2.5~4.0A), Class 10A tripping, 50kA/400V breaking capacity, suitable for 1.5kW/400V AC-3 motors, 45mm DIN-rail mounting, IP20 protection, global order number 1SAM250000R1008. Model Explanation Model Part Description MS116 ABB MS116 series compact 3-pole manual motor starter, integrated ...

  • Detalles del producto

ABB MS116-4.0 Technical Datasheet (Manual Motor Starter / Motor Protection Circuit Breaker)

Key Overview: 3-polo, rated current 4.0A (adjustable 2.5~4.0A), Class 10A tripping, 50kA/400V breaking capacity, suitable for 1.5kW/400V AC-3 motors, 45mm DIN-rail mounting, IP20 protection, global order number 1SAM250000R1008.

  1. Model Explanation
Model PartDescripción
MS116ABB MS116 series compact 3-pole manual motor starter, integrated thermal-magnetic protection (sobrecarga + cortocircuito + falla de fase), fuse-free design
4Rated operational current Ie = 4.0A, adjustable range 2.5~4.0A
1SAM250000R1008Global order code
Dimensiones / MontajeWidth 45mm, standard 35mm DIN rail mounting, IP20 degree of protection
  1. Core Electrical & Mechanical Data

2.1 Básico & Protection Parameters

ParámetroValorDescripción
Number of poles3-poloFor three-phase motor protection
Rated current Ie4.0AAdjustable range 2.5~4.0A
Tripping classClase 10ATypical motor tripping characteristic; trips in approx. 10 s at 10 overload current
Protección contra cortocircuitos50A (fixed)Instantaneous magnetic trip, no extra fuse required
Breaking capacity Ics50el (400V y)Rated service short-circuit breaking capacity
Tensión nominal690V y, 50/60HzSuitable for various voltage systems
Applicable power (AC-3)1.5kilovatios (400V) / 2 hp (480V)For standard motor duty
Protection functionsTemperature compensation, fuse-free protection, free tripping mechanism, isolation function, phase failure protectionComprehensive motor protection, IEC compliant

2.2 Mecánico & Mounting Data

  1. ParámetroValor
    Ancho45milímetros
    Height90milímetros
    Depth85.6milímetros
    Peso0.225kilos
    MontajeCarril DIN estándar de 35 mm (TH35-15/TH35-7.5)
    ConnectionScrew terminals, main circuit torque 0.8~1.2Nm
    OperationRotary handle (clear ON/OFF indication), free tripping mechanism
    Degree of protectionIP20 (front)
    Consumo de energía5.4W.
    Temperatura ambiente-25C≈+55C

    Guía de selección

3.1 Aplicaciones típicas

Direct starting and protection of small three-phase motors (1.5kW/400V)

Control of pumps, fans, compressors and industrial automation equipment

Replacement of traditional “fuse + contactor” combinations to save space and cost

Applications requiring manual control and reliable motor protection

3.2 Selection Steps

  1. Verify motor rated current: within 2.5~4.0A adjustable range
  2. Check motor power: ≤ 1.5kW (400V y-3)
  3. Confirm system voltage: ≤ 690V AC, 50/60Hz
  4. Evaluate short-circuit current: system short-circuit current ≤ 50kA (400V)
  5. Installation space: reserve 45mm DIN rail width
  6. Ambient conditions: temperature -25°C ~ +55°C, no excessive vibration or corrosive gas

3.3 Setting & Operation Notes

Protección contra sobrecarga: set to 1.0~1.1 × motor rated current (within 2.5~4.0A)

Ensure reliable phase failure protection for all three-phase motor applications

Use isolation function: safe electrical isolation after shutdown for maintenance

Can be used with contactors for remote control and automatic protection

  1. Cross-Brand Replacement Models
MarcaModeloMain ParametersDifferences
SchneiderGV2ME083-polo, 2.5~4.0A, Clase 10, 50kA/400VSame width (45milímetros), functionally compatible, direct replacement
siemens3RV2011-0JA103-polo, 2.5~4.0A, Clase 10, 50kA/400VMatching mounting dimensions, compatible protection characteristics
EatonPKZM0-43-polo, 2.5~4.0A, Clase 10, 50kA/400VFunctionally and dimensionally compatible, cost-effective
ABB UpgradeMS132-4.03-polo, 2.5~4.0A, Clase 10, 100kA/400VHigher breaking capacity, backward compatible mounting
  1. Application Notes
  2. Thermal-magnetic characteristics: Class 10A is intended for standard squirrel-cage motors; not recommended for special loads (p.ej., transformers, condensadores)
  3. Protección contra fallo de fase: Trips within 2~5 seconds if any phase is lost, effectively preventing motor burnout
  4. Fuse-free design: Eliminates external fuses, reduces cost and maintenance; ensure line short-circuit current ≤ 50kA
  5. Free tripping mechanism: Forces tripping under overload/short-circuit even in ON position, ensuring safety
  6. Temperature compensation: Protection characteristics stable over ambient temperature range -25°C ~ +55°C