Contactor CHINT NC1-2508/220V - contactor,cortacircuitos,inversor solar,medidor electrico,baterias solares

contactor/

Contactor CHINT NC1-2508/220V

Segmento de modeloDescripción
NC1Código de serie del producto; CHINT Electric NC1 series AC contactor, suitable for remote on/off control of AC circuits and frequent control of AC motors
25Rated operating current class; rated operating current is 25A under AC-3 utilization category (at 400V)
8Auxiliary contact configuration, 0 normalmente abierto + 8 normalmente cerrado (actually a 4-pole contactor with 2NO+2NC main contacts; auxiliary contacts need to be configured separately)
220VRated control voltage of the coil; CA 220 V, compatible with 50/60Hz frequency

  • Detalles del producto
  1. Interpretación del modelo
Segmento de modeloDescripción
NC1Código de serie del producto; CHINT Electric NC1 series AC contactor, suitable for remote on/off control of AC circuits and frequent control of AC motors
25Rated operating current class; rated operating current is 25A under AC-3 utilization category (at 400V)
8Auxiliary contact configuration, 0 normalmente abierto + 8 normalmente cerrado (actually a 4-pole contactor with 2NO+2NC main contacts; auxiliary contacts need to be configured separately)
220VRated control voltage of the coil; CA 220 V, compatible with 50/60Hz frequency
  1. Parámetros técnicos básicos
Categoría de parámetroSpecific Index
Tensión de funcionamiento nominal (Ue)Three-phase AC 690V (50/60Hz); Rated Insulation Voltage Ui = 800V
Corriente de funcionamiento nominal (En)25A at 400V under AC-3; 40A at 400V under AC-1; 16A at 690V under AC-3
Utilization CategoryAC-1 (non-inductive or slightly inductive loads), AC-3 (starting/running/breaking of squirrel-cage induction motors), AC-4 (frequent starting/reversing/braking of squirrel-cage induction motors)
Main Contact Configuration4-polo, 2NO+2NC (2 Normalmente abierto + 2 Normalmente cerrado)
Contactos auxiliaresNeed separate configuration (p.ej., AX series auxiliary contact sets); can be expanded to combinations like 2NO+2NC
Parámetros de la bobinaRated voltage AC 220V, 50/60Hz; Pick-up power approx. 370Virginia; Holding power approx. 45Virginia
Vida mecánica≥10 million cycles (no-load operation)
Vida eléctrica≥100,000 cycles under AC-3 (breaking at rated current)
Clase de protecciónIP20 (prevents finger access)
Método de montajeStandard 35mm DIN rail mounting or screw fixing
Compliance StandardsIEC/EN 60947-4-1, GB14048.4

III. Functional Features

  1. Flexible Multi-Pole Configuration: 4-diseño de poste (2NO+2NC main contacts) adapts to various circuit control requirements, especially suitable for scenarios requiring bidirectional control or switching of the main circuit.
  2. Wide Voltage Compatibility: The coil supports universal 50/60Hz frequency, adapts to power grid frequencies in different regions, and ensures stable and reliable control voltage.
  3. Long Mechanical and Electrical Life: Mechanical life up to 10 million cycles and electrical life of 100,000 cycles under AC-3, meeting the requirements of industrial scenarios with frequent start-stop operations.
  4. Modular Expansion: Accessories such as auxiliary contact sets and mechanical interlock modules can be added to realize function expansion including signal feedback and reversible control.
  5. Safe and Reliable Design: Adopts silver alloy contacts with strong anti-welding capability; the high-efficiency arc extinguishing system ensures short arcing distance during breaking, guaranteeing electrical safety.
  6. High Versatility: Designed with reference to the Schneider LC1 series; can be matched with CHINT NR2 series thermal overload relays to form electromagnetic starters for overload protection.
  7. Ámbito de aplicación
  8. Control de motores: Can control motors up to 11kW (400V three-phase induction motor) under AC-3 category, suitable for frequent start-stop of equipment such as fans, water pumps and conveyors.
  9. Power Distribution System: Used for remote on/off control of circuits below AC 690V, such as control of non-inductive or slightly inductive loads (AC-1 category) like lighting systems and heating equipment.
  10. Automatización Industrial: Serves as the core component of control circuits such as star-delta starters and reversible contactors, adapting to various motor control schemes including DOL (Direct-On-Line) starting and star-delta starting.
  11. Building Electrical Engineering: Control circuits of equipment such as fans, air conditioners and water pumps in shopping malls, edificios de oficinas, factory workshops and other places.
  12. Not Suitable For: DC circuits, occasions with frequent reversing and large load inertia (AC-4 dedicated contactors are required), and heavy-duty circuits exceeding rated current.
  13. Selection Suggestions
  14. Coincidencia de carga:

Motor Load: Select according to motor power; 25A contactor is suitable for ≤11kW three-phase motors at 400V.

Power Distribution Load: Can carry 40A current under AC-1 category, suitable for lighting or heating loads with total power ≤17kW.

  1. Control Voltage Confirmation: Ensure that the coil voltage (220V) matches the power supply of the control circuit to avoid coil burnout.
  2. Auxiliary Contact Expansion:

For signal feedback: Install AX-02 auxiliary contact set (2NO).

For interlock control: Install mechanical interlock module (suitable for reversible control).

For alarm function: Install alarm contact module.

  1. Protection Configuration: Use with NR2-25 series thermal overload relays with setting current 16-25A to achieve motor overload protection.
  2. Brand Replacement Reference:
MarcaReplacement ModelDiferencias fundamentales
SchneiderLC1D25008M7 220VPrecio más alto, same auxiliary contact configuration, slightly higher breaking capacity
siemens3RT6026-1AN20 220VDiseño modular, compatible with Siemens automation systems, higher price
DeliciosoCJX2-2508 220VDomestic product of the same grade, consistent parameters, high cost performance
  1. Solución de problemas
Fallos comunesPosibles causasSoluciones
Coil not pulling in after power-on1. Mismatched coil voltage or open circuit in control loop1. Verify coil voltage and check control loop wiring
2. Burned coil2. Measure coil resistance (aprox. several hundred ohms under normal condition); replace if burned
3. Jammed mechanical mechanism3. Clean the interior of the contactor and check for jamming of springs and armature
Loud noise after pull-in1. Oil stain or rust on armature end face1. Clean armature end face to remove oil stain and rust
2. Broken shading ring2. Replace shading ring or contactor body
3. Low coil voltage3. Check control power supply voltage to ensure it is within 卤10% of the rated value
Overheating or welding of contacts1. Load current exceeding rated value1. Replace with contactor of larger capacity or reduce load
2. Poor contact of contacts2. Clean contacts and polish oxide layer; replace contacts if severely damaged
3. Failure of arc extinguishing system3. Check for damage to arc extinguishing cover and replace in time
Abnormal signal of auxiliary contacts1. Poor contact of auxiliary contacts1. Clean auxiliary contacts and check wiring
2. Loose installation of auxiliary contact set2. Reinstall auxiliary contact set and tighten screws
3. Severe wear of contacts3. Replace auxiliary contact set
Frequent coil burnout1. Excessive fluctuation of control voltage1. Install voltage stabilizer or surge protector
2. Long-term coil energization (exceeding design life)2. Optimize control loop to avoid long-term coil energization
3. Temperatura ambiente alta3. Improve ventilation and heat dissipation conditions to reduce ambient temperature

VII. Installation and Maintenance Notes

  1. Antes de la instalación, check that the contactor has no damage to appearance, no oxidation of coil and contacts, and the mechanical mechanism is flexible without jamming.
  2. When installing on DIN rail, reserve ≥50mm heat dissipation space and avoid close installation with other heating elements.
  3. During wiring, use wires suitable for 25A current for main circuit terminals (4mm² copper core cable is recommended) and tighten terminal screws (tightening torque 2.5N·m).
  4. Use 1.5mm² copper core cable for control loop wiring to avoid excessive voltage drop due to insufficient wire diameter.
  5. Conduct regular inspection every 3 meses:

Check contact wear; replace when contact thickness is less than 1mm.

Monitor coil temperature; normal operating temperature should be ≤80℃.

Check flexibility of mechanical mechanism and remove dust and oil stains.

  1. After a fault occurs, cut off power supply first, troubleshoot and repair before putting into use; operation with fault is strictly prohibited.

Parameter Comparison Table of CHINT NC1 Series Contactors (9A/12A/25A/40A/65A/95A)

Dimensión de comparaciónNC1-09NC1-12NC1-25NC1-40NC1-65NC1-95
Corriente de funcionamiento nominal (AC-3, 400V)9A12A25A40A65A95A
Suitable Three-Phase Motor Power (400V)4KW5.5KW11KW18.5KW30KW45KW
Corriente de funcionamiento nominal (AC-1, 400V)12A18A40A63A100A150A
Tensión nominal de aislamiento (interfaz de usuario)800V800V800V800V800V800V
Tensión de funcionamiento nominal (Ue)AC 690VAC 690VAC 690VAC 690VAC 690VAC 690V
Main Contact Configuration3NO (3 Normalmente abierto)3NO2NO+2NC (4-polo)3NO3NO3NO
Coil Voltage OptionsAC 24/36/110/220/380VSame as leftSame as leftSame as leftSame as leftSame as left
DC 24/110V
Coil Pick-up PowerAprox.. 70VirginiaAprox.. 85VirginiaAprox.. 370VirginiaAprox.. 500VirginiaAprox.. 650VirginiaAprox.. 800Virginia
Coil Holding PowerAprox.. 8VirginiaAprox.. 10VirginiaAprox.. 45VirginiaAprox.. 60VirginiaAprox.. 80VirginiaAprox.. 100Virginia
Vida mecánica≥10 million cycles≥10 million cycles≥10 million cycles≥10 million cycles≥10 million cycles≥8 million cycles
Vida eléctrica (AC-3)≥100,000 cycles≥100,000 cycles≥100,000 cycles≥100,000 cycles≥100,000 cycles≥80,000 cycles
Clase de protecciónIP20IP20IP20IP20IP20IP20
Método de montaje35mm DIN rail/screw fixingSame as leftSame as leftSame as leftSame as leftSame as left
Matching Thermal Overload RelayNR2-11.5NR2-11.5NR2-25NR2-40NR2-65NR2-95
Escenarios de aplicación típicosSmall fans, zapatillas, lighting controlConveyors, small compressorsCentral air conditioning fans, bombas de aguaLarge fans, air compressorsInjection molding machines, crushersCooling towers, large motors

Supplementary Selection Tips

  1. Load Matching Priority: Para cargas de motores, select according to rated current under AC-3; for power distribution/lighting loads, select according to rated current under AC-1. The load current shall be ≤80% of the contactor’s rated current to avoid overload.
  2. Coil Voltage Selection: Prioritize voltage consistent with the control loop (p.ej., 220V). DC coils are suitable for industrial scenarios with strong electromagnetic interference to avoid false pull-in.
  3. Auxiliary Contact Expansion: All specifications can be equipped with AX series auxiliary contact sets (2NO/2NC/1NO+1NC) to meet the needs of signal feedback and interlock control.
  4. Reversible Control Configuration: Seleccionar 2 contactors of the same specification and install mechanical interlock module to prevent main circuit short circuit.