CHINT NM1LE800S-4300-800A MCCB

This is a CHINT NM1LE series 800A moulded case earth leakage circuit breaker with triple protection: sobrecarga, short-circuit and earth leakage. It has S-class breaking capacity (36kA@400V), 4-pole fixed installation, and adjustable rated residual operating current (30–500mA). It is widely used for personal electric shock protection and earth fault protection in industrial power distribution, high-power ...

  • Detalles del producto

This is a CHINT NM1LE series 800A moulded case earth leakage cortacircuitos with triple protection: sobrecarga, short-circuit and earth leakage. It has S-class breaking capacity (36kA@400V), 4-pole fixed installation, and adjustable rated residual operating current (30–500mA). It is widely used for personal electric shock protection and earth fault protection in industrial power distribution, high-power motor circuits and building electrical systems.

  1. Full Model Code Breakdown
SectionMarkingDescripciónTechnical Note
1NM1LESerie de productosMCCB with earth leakage protection (LE = Leakage) based on CHINT NM1 series
2800Frame rated currentMaximum frame current: 800A
3SClase de capacidad de rupturaS-class standard breaking capacity, 36kA@400V, for general distribution
44300Número de polo + trip type4 polos (3Ph+N), thermomagnetic trip (300 = no undervoltage release)
5800ACorriente nominal (En)Continuous operating current: 800A
  1. Parámetros técnicos clave
ArtículoValorObservaciones
Product typeNM1LE series MCCB with earth leakage protectionClassic CHINT series with international advanced technology
Tensión nominal de aislamiento (interfaz de usuario)800VMaximum continuous voltage for insulation parts
Tensión de funcionamiento nominal (Ue)400V y (50Hz)Standard for three-phase four-wire systems
Rated impulse withstand voltage (Uimp)8kVWithstand capability against transient high voltage
Ultimate breaking capacity (uci)36kA@400VS-class, suitable for general industrial & commercial use
Service breaking capacity (ics)50% uciReusable after fault operation (ES 14048.2 compliant)
Corriente nominal (En)800AMaximum continuous current
Trip characteristicThermomagnetic (inverse time overload + instantaneous short-circuit)Sobrecarga: 0.8–1.0In adjustable; Instantáneo: 5–10In
Earth leakage parametersCorriente de funcionamiento residual nominal (IΔn): 30/100/200/300/500mA optionalProvides both personal shock protection and earth fault protection
Residual non-operating current (IΔn0): 0.5IΔn
tiempo de funcionamiento: ≤0.3s (≤30mA), ≤0,1 s (>30mamá)
polacos4PAG (3Ph+N)N pole for leakage detection only (not for short-circuit breaking except special versions)
Mounting typeFijadoStandard rail or bolt mounting; withdrawable not supported
Connection typeFront connection (estándar)Rear or plug-in connection optional
Degree of protectionIP30CEI 60529, protects against finger and solid foreign objects
Temperatura ambiente-5℃ a +40℃Derate required beyond this range
Dimensiones (milímetros)Alto×Ancho×Profundidad: 360×240×180Standard industrial size for panel installation
PesoAprox.. 18kilosIncludes leakage module; ~3kg heavier than standard NM1
  1. Aplicaciones típicas
  2. Industrial power distribution systems

Main or sub-switch for three-phase four-wire 800A high-current circuits

Control circuits for large motors (p.ej., 400kW induction motors) with full protection

Factories, centros de datos, mines requiring personal safety protection

  1. Building electrical systems

Main switchboards and emergency power circuits in commercial and high-rise buildings

Public buildings such as hospitals and schools with high safety requirements

Power circuits for HVAC, pump rooms and large equipment to prevent electrical fires

  1. Special safety applications

Ambientes hostiles: wet, polvoriento, corrosive locations (chemical, textile plants)

Locations requiring high-level fire protection: warehouses, power distribution rooms

Heavy-duty equipment with frequent starts: grúas, compresores, to detect insulation failure

  1. Modelos de reemplazo

4.1 CHINT Upgrades / Replacements

Modelo de reemplazoMain DifferenceSolicitud
NM1LE800H-4300-800ABreaking capacity upgraded to H-class (50kA@400V)Systems with high short-circuit current near transformers
NM1LE800S-4308-800AWith motorized operatorRemote control, unattended automation systems
NXMLE800S-4300-800ANew Kunlun Series, smaller size, improved performanceSystem upgrades, new installations
NM1LE800S-4310-800AWith undervoltage releaseCritical circuits requiring undervoltage protection (p.ej., fire power)

4.2 Cross‑Brand Equivalents

MarcaModeloParámetros clave de coincidenciaNotas
TEJIDOT6N800 PR221DS-LSI+RCD 800 4PAGIn=800A, Icu=36kA, 4PAG, fuga a tierraElectronic trip + leakage module, mayor precisión
SchneiderNSX800F TM800D+Vigi 4PIn=800A, Icu=36kA, 4PAG, thermomagnetic + leakageIdentical breaking capacity, reliable Vigi module
siemens3VA6880-6EL32-0AA0+3VA9180-0AA00In=800A, Icu=36kA, 3P+N, leakage add-on3VA series with leakage kit, similar performance
MitsubishiNF800-CW+leakage module 4PIn=800A, Icu=35kA, 4PAG, thermomagnetic + leakageJapanese brand, suitable for Japanese-equipped systems
  1. Selección & Application Notes
  2. Breaking capacity matching

Ensure short-circuit current ≤ 36kA@400V; otherwise use NM1LE800H (50el).

S-class breaking capacity decreases at higher voltages; recheck for 690V systems.

  1. Earth leakage current selection

Personal protection / wet areas: IΔn = 30mA

Equipment & fire protection: IΔn = 100–300mA

Motor & high-power loads: IΔn = 300–500mA to avoid nuisance tripping during startup.

  1. Poles and N‑pole configuration

4-pole for three-phase four-wire systems only; N wire must be connected.

N pole only detects leakage; it does not break short-circuit current (except special versions).

For interruptible N pole, select a special model with “N-pole breaking”.

  1. Instalación & wiring

Fixed mounting; allow ≥180mm depth for heat dissipation.

Use copper busbar/cable rated for 800A: ≥240mm² cable or 40×10mm busbar recommended.

Debe instalarse verticalmente, tilt ≤15°.

  1. Mantenimiento & replacement

Test leakage function monthly using the TEST button.

Inspect contacts after short-circuit operation; replace if necessary.

For upgrades, prefer CHINT NXMLE Kunlun Series (compatible dimensions, better performance).

Leakage module can be replaced separately.

CHINT NM1LE800S-4300-800A is a reliable 800A earth leakage MCCB with triple protection, standard breaking capacity and 4-pole design, ideal for industrial automation and building electrical systems. Selection should consider short-circuit level, leakage requirements and installation space. For better performance and safety, use higher-breaking versions or the new Kunlun series when applicable.

CHINT NM1LE800S-4300-800A – Key Selection Notes

  1. Breaking Capacity Check

This model: S-class = 36kA@400V

If short-circuit current >36el (near transformer, main incomer), use NM1LE800H (50el).

  1. Current Rating

Frame current 800A, rated current 800A

For continuous loads ≤800A only; do not overload.

  1. polacos & Tipo de sistema

4300 = 4P (3Ph+N) + thermomagnetic trip

For three-phase four-wire (380V+N) systems only; N wire must be connected.

N pole does not break short-circuit current, only for leakage detection.

  1. Earth Leakage Selection

Available settings: 30/100/200/300/500mamá

Personal safety / wet areas: 30mamá

Equipment / fire protection: 100–300mA

motores / high-power loads: 300–500mA (prevents startup nuisance tripping)

  1. Trip Characteristics

Thermomagnetic: sobrecarga + instantaneous short-circuit protection

Instantaneous range: 5–10In

Set higher for motors to avoid tripping during startup.

  1. Instalación & Environment

Must be vertical, tilt ≤15°

Ambient: -5℃ a +40℃; derate at high temperature

IP20 open type; install in enclosure for dusty, wet or oily areas.

  1. Alambrado & Heat Dissipation

Use 800A-rated conductors:

≥240mm² copper cable or 40×10mm copper busbar

Terminations must be tightly torqued to avoid overheating.

  1. Mantenimiento & Seguridad

Press TEST button monthly to verify leakage function.

Leakage module replaceable separately.

Not recommended for three-phase three-wire systems without neutral.

  1. Upgrade Recommendation

New CHINT NXMLE800S series: better performance, smaller size

Preferred for replacement or upgrade (dimensions nearly compatible).