Schneider C10F32D100: Disyuntor de caja moldeada ComPacT NSX100F - contactor,cortacircuitos,inversor solar,medidor electrico,baterias solares

cortacircuitos/

Schneider C10F32D100: Disyuntor de caja moldeada ComPacT NSX100F

Model Interpretation C10F32D100 is the complete order code of Schneider’s new-generation ComPacT NSX series molded case circuit breakers. The meaning of each segment is as follows: Code Segment Meaning Description C10 Frame Size and Breaking Capacity C10 = NSX100F, frame current 100A, breaking capacity Class F (36kA@415VAC) F Breaking Capacity Class F = 36kA@415VAC, suitable ...

  • Detalles del producto
  1. Interpretación del modelo

C10F32D100 is the complete order code of Schneider’s new-generation ComPacT NSX series disyuntores de caja moldeada. The meaning of each segment is as follows:

Code SegmentMeaningDescripción
C10Frame Size and Breaking CapacityC10 = NSX100F, frame current 100A, breaking capacity Class F (36kA@415VAC)
FBreaking Capacity ClassF = 36kA@415VAC, suitable for standard industrial applications
3Number of Poles3 = 3-pole (3P3D, three-phase three-wire system)
2DTipo de unidad de disparo2D = MicroLogic 2.2 electronic trip unit with display function
100Corriente nominal100A, adjustable range 90-100A
  1. Parámetros técnicos básicos

Parámetros básicos

ParámetroValorDescripción
Tipo de productoDisyuntor de caja moldeada (MCCB)New-generation ComPacT NSX100F
Tensión nominal690VAC/50-60HzMaximum operating voltage
Corriente nominal (Iu)100AContinuous operating current
Ultimate Breaking Capacity (uci)36kA@415VACUltimate breaking capacity
Service Breaking Capacity (ics)36kA@415VAC (100%)Service breaking capacity
Mounting TypeFixedStandard mounting, plug-in type optional (C10F32D100P)
Protection CategoryCategory ACumple con IEC 60947-2 estándar

MicroLogic 2.2 Trip Unit Parameters

Función de protecciónCaracterísticaAdjustable Range
Long-time Delay Protection (l)Protección contra sobrecarga, inverse time-lag0.8-1.0脳Iu (90-100A)
Short-time Delay Protection (S)Protección contra cortocircuitos, definite time-lag3-6脳Iu, ajustable
Instantaneous Protection (I)Short-circuit instantaneous tripping, fixed10脳Iu (1000A)
Display FunctionCurrent measurement and status indicationReal-time display of three-phase current

Physical and Electrical Characteristics

ParámetroValor
Power Loss14.1W.
PesoApproximately 2.5kg
Compliance StandardsCEI 60947-2, GB 14048.2
CertificacionesCE, CCC, RoHS

III. Functional Features

  1. Comprehensive Protection: Provides three-stage protection including long-time delay, short-time delay and instantaneous protection, effectively preventing overload and short-circuit faults.
  2. Precise Control: Compared with thermal-magnetic trip units (TM series), electronic trip units offer more accurate protection curves and adjustable parameters.
  3. Status Visualization: MicroLogic 2.2 is equipped with LED display for real-time monitoring of current and fault status.
  4. Modular Design: Supports a variety of accessories (contactos auxiliares, alarm contacts, undervoltage release, etc.) for flexible installation.
  5. Environmental Friendly: Schneider Green Signature design, reducing energy consumption and carbon footprint.
  6. Easy Operation: Ergonomic handle for labor-saving operation; front-mounted accessories reduce wiring time by 40%.
  7. Escenarios de aplicación
  8. Industrial Power Distribution Systems: Used as main switch or branch switch to protect motors, transformers and distribution lines.
  9. Building Electrical Systems: Low-voltage distribution cabinets in commercial buildings and industrial plants.
  10. Motor Control Centers (MCC): Protect three-phase motors from locked rotor and overload conditions.
  11. Centros de datos: Power protection for critical loads to ensure power supply continuity.
  12. New Energy Sector: DC-side protection of photovoltaic inverters and energy storage systems (additional configuration required).
  13. Product Comparison

Comparison with Trip Units of the Same Series

ModeloTipo de unidad de disparoMain DifferencesEscenarios de aplicación
C10F32D100MicroLogic 2.2Electronic trip unit with display, three-stage protectionIndustrial applications requiring precise protection and monitoring
C10F3TM100TM100D Thermal-Magnetic TripThermal-magnetic trip unit, two-stage protection, cost-effectiveSimple power distribution without precise adjustment requirements
C10F33D100MicroLogic 3.2Protección adicional contra fallas a tierra (30-3000mamá)

Comparison with Chint Alternative Models

Schneider ModelChint Alternative ModelSimilaritiesDifferences
C10F32D100NM1-125S/3300 100A3-polo, 100A, 36kA breaking capacityChint adopts thermal-magnetic trip unit without display; Schneider adopts electronic trip unit with display
NM1-125H/3340 100A3-polo, 100A, electronic trip unitChint has 50kA breaking capacity with slightly different protection functions
  1. Selection and Usage Recommendations
  2. Selection Key Points

Select protection curves according to load types: for motor loads, it is recommended to set short-time delay to 5-6×Iu

Breaking capacity should be greater than the expected short-circuit current of the system

Consider future expansion; rated current should be slightly higher than the actual load current

  1. Precauciones de instalación

Ensure the mounting surface is flat and the tightening torque meets requirements (screw torque 25N·m)

Corresponding cable lugs must be used for terminal connections to avoid heating caused by poor contact

Leave sufficient heat dissipation space around and avoid close installation with heat-generating components

  1. Recomendaciones de mantenimiento

Regular inspection (at least once a year): appearance, tightness status, flexibility of operating mechanism

Check contact condition after short-circuit tripping and replace if necessary

Clean with dry compressed air to avoid moisture and dust accumulation

VII. Troubleshooting Guide

Fenómeno de fallaPosibles causasTroubleshooting Steps
Failure to Close1. Undervoltage release without power supply

2. Trip unit malfunction

3. Mechanical lockout

1. Check control power supply (if equipped)

2. Measure trip unit coil resistance

3. Manually reset the trip mechanism

False Tripping1. Sobrecarga

2. Short circuit

3. Improper trip unit parameter setting

1. Check load current

2. Check line insulation

3. Reset trip unit parameters

No Display After Tripping1. Trip unit power supply failure

2. Trip unit damage

1. Check trip unit power supply

2. Replace the trip unit