chatear: +86-13184948252 Whatsapp: 0086-13811255435 Correo electrónico: kent@bestcontactor.com

Acerca de Contacto |

Schneider Contactor LC1D09BDC - contactor,cortacircuitos,inversor solar,medidor electrico,baterias solares

contactor/

Schneider Contactor LC1D09BDC

Elemento de parámetroDetails
Product ModelLC1D09BDC
SerieSchneider TeSys D (Domestic Version)
Main Contact Configuration3-polo normalmente abierto (3NO), rated current 9A
Tensión de funcionamiento nominalUp to 690V AC
Coil SpecificationDC24V DC coil
Contacto auxiliar1 normalmente abierto + 1 normalmente cerrado (1NO+1NC)
Service CategoryAC-1 (resistive load), AC-3 (squirrel-cage induction motor)
Método de montajeStandard 35mm DIN rail or screw mounting
Vida mecánicaAprox.. 10 millones de operaciones; Electrical life approx. 1 millones de operaciones
CertificacionesCCC, CE, UKCA, RoHS, REACH
Dimensiones generales45milímetros (W.)*77milímetros (h)*95milímetros (D), Weight approx. 0.48kilos

  • Detalles del producto

Schneider LC1D09BDC

Schneider LC1D09BDC is a 3-pole contactor de CA of the TeSys D series, with a rated current of 9A, a coil voltage of DC24V, 3NO main contacts and 1NO+1NC auxiliary contacts. It is suitable for AC-1/AC-3 loads, supports DIN rail mounting, and is commonly used in industrial automation and motor control.

Parámetros principales

Elemento de parámetroDetails
Product ModelLC1D09BDC
SerieSchneider TeSys D (Domestic Version)
Main Contact Configuration3-polo normalmente abierto (3NO), rated current 9A
Tensión de funcionamiento nominalUp to 690V AC
Coil SpecificationDC24V DC coil
Contacto auxiliar1 normalmente abierto + 1 normalmente cerrado (1NO+1NC)
Service CategoryAC-1 (resistive load), AC-3 (squirrel-cage induction motor)
Método de montajeStandard 35mm DIN rail or screw mounting
Vida mecánicaAprox.. 10 millones de operaciones; Electrical life approx. 1 millones de operaciones
CertificacionesCCC, CE, UKCA, RoHS, REACH
Dimensiones generales45milímetros (W.) * 77milímetros (h) *95milímetros (D), Weight approx. 0.48kilos

Model Code Interpretation

LC1D: 3-pole contactor of TeSys D series

09: Rated current 9A

B: DC coil type

D: Coil voltage DC24V

do: Mark for domestic version

Typical Applications and Replacement Selection

  1. Escenarios de aplicación: Suitable for start-stop control of squirrel-cage motors with current ≤9A, as well as control of AC-3/AC-1 loads such as heating equipment, fans and water pumps. It is compatible with DC control circuits of PLC and DCS systems.
  2. Replacement Selection

Intra-series replacement: LC1D09BD (imported version with identical parameters)

Cross-brand replacement: ABB A16-30-01 (CC 24 V), Siemens 3RT2015-1BB41 (CC 24 V), Chint NXC-0910z (CC 24 V)

Installation and Safety Points

  1. Especificaciones de instalación

Ambient temperature: -5℃~+40℃, Altitud ≤2000m, Avoid dust/corrosion/condensation

Reserve heat dissipation clearance, spacing between adjacent devices ≥5mm

Wiring torque: Main circuit 1.7N·m, Control circuit 0.5N·m

  1. Safety Tips

Verify voltage after coil power-off to prevent residual voltage

It is recommended to match a thermal overload relay (p.ej., LRD06C) for motor circuits

Derating is required for frequent start-stop scenarios (recommended ≤80% of rated current)

Common Troubleshooting

Fenómeno de fallaPosibles causasMétodos de solución de problemas
No power to coilPower circuit break, loose wiringMeasure coil terminal voltage, inspect wires and terminals
High noise after pull-inContaminated iron core contact surface, broken shading ringClean the iron core, replace the shading ring
ablación por contactoSobrecarga, incorrect load matchingCheck load type, replace contact set
Coil burnoutOvervoltage/undervoltage, frequent on-offInstall a surge suppressor, optimize control logic

Procurement and Maintenance

Order Number: LC1D09BDC, Packaging: 1 pc/box, 21 pcs/carton

Período de garantía: 18 meses, It is recommended to inspect contact wear and wiring tightness quarterly

The following are the mainstream cross-brand direct replacement models for Schneider LC1D09BDC (3-polo, 9A, CC 24 V, 3NO main contacts, 1NO+1NC auxiliary contacts), classified by brand with core parameter matching marked for quick selection and replacement.

  1. Key Points for Core Parameter Matching

Ensure the following key parameters are consistent during replacement:

Pole number: 3-polo

Rated current: 9A (at AC-3 400V)

voltaje de la bobina: CC 24 V (corriente continua)

Contactos principales: 3NO (3 normalmente abierto)

Contactos auxiliares: 1NO+1NC (1 normalmente abierto + 1 normalmente cerrado)

Service category: AC-1/AC-3 (suitable for resistive loads and squirrel-cage motors)

  1. Cross-brand Replacement Model Comparison Table
MarcaModeloCore Parameter MatchingObservaciones
Schneider (Intra-series)LC1D09BDFully consistent parametersImported version, replacement for domestic LC1D09BDC
TEJIDOAX09-30-11-80*24VDC3PAG,9A,CC 24 V,3NO+1NO+1NCAX series for motor-specific use, BC series for general use
BC6-30-11-P01
siemens3RT2023-1BB413PAG,9A,CC 24 V,3NO+1NO+1NC3RT2 as standard type, 3RT6 as economic type
3RT6015-1BB41
chintNXC-09M/22/Z DC24V3PAG,9A,CC 24 V,3NO+1NO+1NCNXC as new model, CJX2 as classic model
CJX2-0911Z DC24V
DeliciosoCJX2s-0911Z DC24V3PAG,9A,CC 24 V,3NO+1NO+1NCZ indicates DC coil version
Eaton MoellerDILM9-10(24VCC)3PAG,9A,CC 24 V,3NO+1NO+1NCConfirm auxiliary contact configuration
DILM9-10(24VCC)+auxiliary contact
Changshu SwitchgearCK3-0910Z DC24V3PAG,9A,CC 24 V,3NO+1NO+1NCHigh-quality domestic replacement brand
People’s Electric ApplianceRMK-0910Z DC24V3PAG,9A,CC 24 V,3NO+1NO+1NCCost-effective, suitable for industrial scenarios

III. Notes on Replacement Selection

  1. Installation Compatibility: All recommended models are suitable for 35mm DIN rail mounting, with dimensions close to LC1D09BDC (aprox. 45mm in width), enabling direct replacement of installation positions.
  2. Wiring Matching: Main circuit wiring torque 1.7N·m, control circuit 0.5N·m, consistent with the original contactor.
  3. Thermal Relay Matching: It is recommended to match a thermal overload relay below 9A of the same brand (p.ej., ABB TA25DU06, Siemens 3RB2016, Chint NR2-063) to ensure consistent motor protection.
  4. Surge Protection: It is recommended to install a freewheeling diode or surge suppressor for DC coils to extend service life.
  5. Derating Use: For frequent start-stop scenarios (>1200 times/hour), derate to below 7.2A for use.
  6. Quick Selection Suggestions
  7. Pursue original quality: Select Schneider LC1D09BD
  8. Prioritize cost performance: Select Chint NXC-09M/22/Z or Delixi CJX2s-0911z
  9. System compatibility: Select AX09-30-11-80 for ABB systems, 3RT2023-1BB41 for Siemens systems
  10. Spare part universality: Prioritize mainstream domestic models such as NXC/CJX2s for easier procurement and maintenance