chatear: +86-13184948252 Whatsapp: 0086-13811255435 Correo electrónico: kent@bestcontactor.com

Acerca de Contacto |

Disyuntor de caja moldeada Schneider EZD100E3060N - contactor,cortacircuitos,inversor solar,medidor electrico,baterias solares

cortacircuitos/

Disyuntor de caja moldeada Schneider EZD100E3060N

Model Interpretation EZD100E3060N = EZD (Serie) + 100 (Frame Current 100A) + E (Breaking Capacity Class 25kA) + 3 (3 polacos) + 060 (Rated Current 60A) + norte (Configuración estándar) Alternative Names: EZD100E TM60D 3P/3d, EZD100E3P3T60A Order Code: M2b05502 Core Technical Parameters Parameter Value Standard Basis Frame Current 100A@40℃ IEC60947-2/GB14048.2 Rated Current 60A IEC60947-2/GB14048.2 Number ...

  • Detalles del producto
  1. Interpretación del modelo

EZD100E3060N = EZD (Serie) + 100 (Frame Current 100A) + E (Breaking Capacity Class 25kA) + 3 (3 polacos) + 060 (Rated Current 60A) + norte (Configuración estándar)

Alternative Names: EZD100E TM60D 3P/3d, EZD100E3P3T60A

Order Code: M2b05502

  1. Parámetros técnicos básicos
ParámetroValorStandard Basis
Marco actual100A@40℃IEC60947-2/GB14048.2
Corriente nominal60AIEC60947-2/GB14048.2
Number of Poles3PAG (3 Poles with 3 Protections)IEC60947-2/GB14048.2
Capacidad de ruptura25kA@415VIEC60947-2/GB14048.2
Rated Operational Voltage500V AC@50/60HzIEC60947-2/GB14048.2
Tensión nominal de aislamiento690VIEC60947-2/GB14048.2
Rated Impulse Withstand Voltage6kVIEC60947-2/GB14048.2
Release TypeTMD (Thermomagnetic Type D)IEC60947-2/GB14048.2
Método de montajeFixed Type (Base Mounting)IEC60947-2/GB14048.2
Método de cableadoFront WiringIEC60947-2/GB14048.2
Método de operaciónDirect Handle OperationIEC60947-2/GB14048.2
Protección contra fugas a tierraNinguno (Tipo estándar)IEC60947-2/GB14048.2
Vida mecánica≥10,000 OperationsIEC60947-2/GB14048.2
Vida eléctrica≥5,000 OperationsIEC60947-2/GB14048.2
  1. Product Features and Protection Functions
  2. Características de protección: The TMD thermomagnetic release provides long-time delay protection for overload (inverse time characteristic) and instantaneous protection for short circuit (Type D characteristic, 10-14En), suitable for the protection of distribution lines and motor circuits.
  3. Función de aislamiento: Compliant with IEC60947-3 standard, it has safe isolation capability and can be used as an isolation device during equipment maintenance.
  4. Fácil instalación: It supports standard 35mm DIN rail or base mounting, with a front wiring design that saves space and facilitates construction and maintenance.
  5. Safe and Reliable: The rated insulation voltage of 690V meets higher insulation requirements; the optimized arc extinguishing system ensures stable breaking capacity; the operating handle provides clear on/off indication.
  6. Modular Design: It supports the installation of accessories such as shunt release and auxiliary contact for flexible function expansion.
  7. Application Scenarios and Scope

Aplicación principal: Power distribution and line protection for secondary distribution systems, applicable to scenarios such as civil buildings, industrial plants, electromechanical equipment.

Protection Objects: Protect electrical equipment such as cables, transformers and motors from overload, short circuit and other faults, improving power supply continuity.

Condiciones ambientales: Operating temperature from -5℃ to +40℃ (derating required when the temperature exceeds 40℃); relative humidity ≤95% (sin condensación); altitud ≤2000m.

  1. Key Points for Installation and Wiring
  2. Pre-installation Inspection: Verify that the model and rated parameters are consistent with system requirements; check for no appearance damage and flexible operating mechanism.
  3. Método de montaje: Adopt fixed mounting with the tightening torque in accordance with the instruction manual; ensure sufficient electrical clearance and creepage distance from other components.
  4. Especificación de cableado: Front screw wiring with matched wire cross-section (16-25mm² copper wire is recommended for 60A), and the wiring terminals are fastened securely.
  5. Operation Notes: The handle has a clear operating direction (closingup, openingdown); the open position can be locked to prevent misoperation.
  6. Consejos de mantenimiento: Conduct regular inspections (at least once a year), quitar el polvo, check the tightness of wiring, and test the normal function of the release.
  7. Selection and Substitution Reference
  8. Intra-series Substitution:

EZD100M3060N (36kA capacidad de corte, suitable for occasions with larger short-circuit current)

EZD100S3060N (50kA capacidad de corte, suitable for distribution systems with important loads or large short-circuit current)

  1. Upgraded Substitution: CVS100E3060N (improved performance and stronger accessory compatibility)
  2. Downgraded Substitution: EZD100N3060N (18kA capacidad de corte, suitable for civil buildings with smaller short-circuit current)
  3. Cumplimiento de estándares

Fully compliant with the requirements of IEC60947-2 (Low-voltage switchgear and controlgearPart 2: Circuit-breakers) and GB14048.2 (Low-voltage switchgear and controlgearPart 2: Circuit-breakers), and has passed relevant certifications. It can be safely used in various low-voltage distribution systems.

Cross-brand Model Comparison for Schneider EZD100E3060N Disyuntor de caja moldeada

  1. Core Parameter Benchmark (EZD100E3060N)

Marco actual: 100A (40℃)

Corriente nominal: 60A

Number of Poles: 3PAG (3 Poles with 3 Protections)

Capacidad de ruptura: 25kA@415V

Release Type: TMD (Thermomagnetic Type D, instantaneous tripping at 10-14In)

Método de montaje: Fixed Type (Base Mounting)

Método de cableado: Front Wiring

Tensión nominal: 500V y, Rated Insulation Voltage 690V

  1. Cross-brand Direct Substitution Model Comparison Table
MarcaSerieSubstitution ModelCore Matching ParametersMounting/Wiring CompatibilityObservaciones
TEJIDOTmax XT1XT1N100 TMD60 3P FF3PAG, 60A, 100A Frame, 25el, TMD Release, Front WiringSimilar dimensions, direct substitutionOrder Code: 10152538
siemens3VA13VA1106-1EL31-0AA03PAG, 60A, 100A Frame, 25el, TM-D Release, Fixed TypeCompatible mounting dimensions, universal accessoriesSubstitute for the old model 3VL1706-1DC31-0AA0
chintNXMNXM-125S/3300 60A3PAG, 60A, 125A Frame, 25el, Thermomagnetic Type D ReleaseFront Wiring, Fixed MountingKunlun Series, high cost performance
DeliciosoCDM3CDM3-100C/3300 60A3PAG, 60A, 100A Frame, 25el, Thermomagnetic Type D ReleaseMatched mounting dimensions, consistent wiring methodTipo estándar, rich accessories
Changshu SwitchCM3CM3-100C/3300 60A3PAG, 60A, 100A Frame, 25el, Thermomagnetic Type D ReleaseFully compatible mounting and wiringHigh-quality domestic substitution
TEJIDOTmax T1T1N100 TMD60 3P3PAG, 60A, 100A Frame, 25el, TMD ReleaseTraditional series, stable and reliable; old model with partial stock
Schneider (Upgraded)CVSCVS100E3060N3PAG, 60A, 100A Frame, 25el, TMD ReleaseFull compatibility for same-brand upgradeImproved performance and more abundant accessories
  1. Key Technical Points for Substitution

3.1 Parameter Matching Priority

  1. Number of Poles and Protection Type: Must be 3P with 3 protections; avoid 4P models without N-pole protection.
  2. Corriente nominal: Strictly 60A; 63A cannot be used as a substitute (due to differences in protection characteristics).
  3. Capacidad de ruptura: ≥25kA to ensure system short-circuit safety.
  4. Release Type: Tipo D (10-14En), suitable for motor or inductive loads.
  5. Mounting and Wiring: Fixed type + front wiring to ensure consistent installation space and wiring method.

3.2 Substitution Notes

ArtículoKey PointsRisk Reminder
Electrical ClearanceSlight dimensional differences exist between products of different brands; verify the installation distance.Insufficient clearance may cause insulation faults.
Compatibilidad de accesoriosAccessories such as shunt release and auxiliary contact must match the corresponding brand.Incompatible accessories make remote control unavailable.
Operating MechanismThe handle operating direction and locking function must be consistent with the original system.Prevent safety accidents caused by misoperation.
Derating UseDerating is required according to the manufacturer’s requirements in environments above 40℃ (generalmente 1% derating for each 1℃ rise).Insufficient derating may cause misoperation of the release.
Certification ComplianceThe substituted model must pass IEC60947-2/GB14048.2 certification.Uncertified products have potential safety hazards.
  1. Scenario-adapted Selection Suggestions
  2. Industrial Motor Circuits: Prioritize ABB Tmax XT1 or Siemens 3VA1 series for stable short-circuit breaking capacity, suitable for frequently starting and stopping loads.
  3. Civil Building Distribution: Chint NXM or Delixi CDM3 series for high cost performance, meeting the requirements of secondary distribution.
  4. Important Load Protection: Schneider CVS series for same-brand upgrade with strong accessory compatibility, facilitating system expansion.
  5. Budget-sensitive Projects: Changshu Switch CM3 series for high-quality domestic manufacturing with reliable performance and price advantage.
  6. Quick Selection Check List
  7. Confirm the system voltage ≤500V AC and short-circuit current ≤25kA.
  8. The load type is motor or inductive load (suitable for Type D release).
  9. The installation space meets the dimensional requirements of the selected substituted model.
  10. The wiring method is front screw wiring with 16-25mm² copper wire.
  11. Verify the consistency between the certification certificate and technical parameter sheet of the substituted model.

Anterior:

Deja una respuesta

Dejar un mensaje