chatear: +86-13184948252 Whatsapp: 0086-13811255435 Correo electrónico: kent@bestcontactor.com

Acerca de Contacto |

 Siemens DC Contactor 3RT1024-1BB40 - contactor,cortacircuitos,inversor solar,medidor electrico,baterias solares

contactor/

Siemens DC Contactor 3RT1024-1BB40

ArtículoDetails
Complete Model3RT1024-1BB40
Serie de productosSiemens SIRIUS 3RT1 Series (Discontinued, Replacement Model: 3RT2024-1BB40)
Structural Specification3-polo, Size S0, Screw Termination, IP20 Protection Class
Voltaje de la bobinaCC 24 V (24 Volt DC)
Main Contact Configuration3 Normalmente abierto (3NO)
Application CategoryAC-3 (Three-Phase Motor Load) 12A, 5.5kW/400V

  • Detalles del producto
  1. Model Interpretation and Basic Information
ArtículoDetails
Complete Model3RT1024-1BB40
Serie de productosSiemens SIRIUS 3RT1 Series (Discontinued, Replacement Model: 3RT2024-1BB40)
Structural Specification3-polo, Size S0, Screw Termination, IP20 Protection Class
Voltaje de la bobinaCC 24 V (24 Volt DC)
Main Contact Configuration3 Normalmente abierto (3NO)
Application CategoryAC-3 (Three-Phase Motor Load) 12A, 5.5kW/400V
  1. Core Parameters of Thermal Current (Ith)
  2. Thermal Current of Main Contacts
Current TypeValor nominalApplicable ConditionsObservaciones
AC-1 (Resistive Load) Thermal Current40A690V y, 50/60HzMaximum allowable current for long-term operation
AC-3 (Motor Load) Corriente nominal12A400V y, 50/60HzCorresponding to 5.5kW three-phase motor
DC-1 (DC Resistive Load) Thermal Current12A24En DCLong-term operating current for DC circuits
DC-3 (DC Motor Load) Corriente nominal8A24En DCStarting and operating current for DC motors
  1. Thermal Current of DC24V Coil
ParámetroValorCalculation Basis
Rated Coil Power5.9W.Siemens official data
Coil Thermal Current0.246AI = P/U = 5.9W/24V
Coil ResistanceAprox.. 97.5R = U/I = 24V/0.246A
Coil Pick-Up/Holding Power5.9W for bothDC coil has the same pick-up and holding power

III. Key Technical Characteristics

  1. Load Adaptation: Suitable for controlling ≤12A resistive load or ≤8A DC motor load in DC24V circuits
  2. Temperatura de funcionamiento: -25°C ~ 60°C, adaptable to industrial environments
  3. Vida mecánica: 3×10⁷ operations, Vida eléctrica (AC-3): 1×10⁶ operations
  4. Voltaje de aislamiento: 690V, reliable electrical isolation performance
  5. Replacement Models and Compatibility

Preferred Replacement Model: 3RT2024-1BB40 (Siemens SIRIUS 3RT2 Series)

Identical main contact and coil parameters, with an additional 1NO+1NC auxiliary contact

Compatible mounting dimensions for direct replacement

Other Compatible Models:

Schneider: LC1D12BD (CC 24 V, 12A, 3NO)

TEJIDO: A12-30-0124VDC (12A, 3NO, CC 24 V)

  1. Usage Notes
  2. DC Circuit Application: When controlling DC24V circuits, derate the main contacts for use (≤12A resistive load) and install a surge suppressor (freewheeling diode) to protect the contacts
  3. Heat Management: Ensure adequate ventilation for the contactor, avoid enclosed installation, and further derate the load when the ambient temperature exceeds 40°C (10% derating for every 10°C rise)
  4. Coil Protection: For the DC24V coil, pay attention to power supply fluctuations (allowable range: 21.6V~26.4V DC) to avoid burnout due to overvoltage
  5. Método de montaje: Supports 35mm standard DIN rail mounting or panel mounting, with no restriction on mounting direction

Resumen

For Siemens 3RT1024-1BB40 in DC24V circuits, the thermal current of the main contacts is 12A (resistive load) and the thermal current of the DC24V coil is approximately 0.246A. This model has been discontinued, and it is recommended to use the replacement model 3RT2024-1BB40 as the first choice, which features better performance and an added auxiliary contact function.

Siemens 3RT1024-1BB40 Selection Quick Reference Table (DC24V/Thermal Current Special)

Escenarios aplicables: Procurement Verification / On-Site Installation / Model Replacement / Parameter Review

ModuleArtículoRated Parameter/Core InformationRemarks/Applicable Conditions
Información básicaProduct Model3RT1024-1BB40Siemens SIRIUS 3RT1 Series (Discontinued)
Voltaje de la bobinaCC 24 V (Direct Current)Consistent pick-up/holding power
Configuración de contacto3-contactos principales de polo (3NO), no auxiliary contactsIP20 protection, screw termination
Structural SpecificationSize S0, 35mm standard DIN rail mountingNo mounting direction restriction, panel/rail mountable
Main Contact Current ParametersAC-1 (Resistive Load) Thermal Current40A@690V AC/50/60HzMaximum allowable current for AC long-term operation
AC-3 (Motor Load) Corriente nominal12A@400V AC/50/60Hz (5.5kW three-phase motor)Rated for AC motor starting/operation
DC-1 (Resistive Load) Thermal Current12A@24V DCCore parameter for DC24V long-term operation (Key Point)
DC-3 (Motor Load) Corriente nominal8A@24V DCAdapted for DC24V motor load
DC24V Coil ParametersRated Power5.9W.Siemens official rating
Coil Thermal Current0.246ACalculation formula: I=P/U=5.9W/24V
Coil ResistanceAprox.. 97.5ΩCalculation formula: R=U/I=24V/0.246A
Allowable Voltage Range21.6V~26.4V DC (±10%)Avoid coil burnout from over/undervoltage
Life/InsulationVida mecánica3×10⁷ operationsIndustrial-grade durability
AC-3 Electrical Life1×10⁶ operationsAdapted for frequent motor start/stop
Voltaje de aislamiento690V AC/DCReliable electrical isolation performance
Preferred Replacement ModelModelo3RT2024-1BB40 (Siemens 3RT2 Series)Original factory upgraded model, direct compatible replacement
Core Compatibility PointsSame main contact/coil/mounting dimensions as 3RT1024-1BB40No rewiring cost, direct replacement
Upgrade PointsAdded 1NO+1NC auxiliary contacts, improved protection/durabilityFirst choice for cost performance
Cross-Brand Compatible ModelsSchneiderLC1D12BDCC 24 V, 3NO main contacts, 12A@400V AC-3
TEJIDOA12-30-01*24VDCCC 24 V, 3NO main contacts, 12A@400V AC-3
Installation/Usage Key PointsRequisitos de instalación35mm standard DIN rail, ventilated installation, avoid enclosureReduce temperature rise, ensure heat dissipation
DC ProtectionInstall a freewheeling diode on main contacts when controlling DC24V circuitsSuppress surges, prevent contact erosion
Temperature Derating10% load current derating for every 10°C rise when ambient temperature >40℃p.ej., DC24V resistive load ≤10.8A at 50℃
Temperatura de funcionamiento-25℃ ~ 60℃Adapted for industrial high/low temperature environments

Key Highlighted Points: DC24V resistive load thermal current 12A, coil thermal current 0.246A, preferred replacement model 3RT2024-1BB40