Complete Technical Parameters of Siemens 3WL1116/3WL1216 1600A ETU45B-G-LCD-3P

Complete Technical Parameters of Siemens 3WL1116/3WL1216 1600A ETU45B-G-LCD-3P

The parameters cover dimensions including basic electrical characteristics, pouvoir de coupure, trip unit, mechanical & environmental performance, communication and installation, facilitating engineering selection and system matching.

  1. Basic Electrical Parameters
Élément de paramètreSpecification ValueRemarques
Série de produitsSiemens SENTRON 3WLAir Circuit Breaker (PBR)
Taille du cadre3WL1116 (Frame I) / 3WL1216 (Frame II)3WL1116: Standard breaking capacity; 3WL1216: High breaking capacity
Courant nominal (Dans)1600UNFrame size current 1600A, setting range 0.4–1In
Numéro de pôle3P.Three-pole, 3-phase main circuit
Rated Operational Voltage (Ue)690V et50/60HZ, conforme à la CEI 60947-2
Tension d'isolation nominale (Interface utilisateur)1000V etBenchmark value for insulation withstand capability
Tension de tenue aux impulsions nominale (Ump)12kVCompliant with IEC 60947-1
Rated Short-time Withstand Current (Icw)Frame I: 66kA/1s; Frame II: 80kA/1sEnsures short-time thermal stability at 500V
Capacité de coupure (ICU)Frame I: 55/66le; Frame II: 80/100leUltimate breaking capacity at 500V; Frame II offers higher breaking capacity
  1. Parameters of ETU45B-G-LCD Electronic Trip Unit
Function ModuleSpecification ValueDescription
Type de protectionLSIG (L: Overload/Long-time Delay; S: Short-circuit/Short-time Delay; je: Instantaneous Short-circuit; G: Ground Fault)Complete power distribution protection configuration
Protection contre les surcharges (L)Characteristic Curve: I²t/I⁴t selectable; Setting Range: 0.4–1InI⁴t characteristic improves selectivity with downstream devices
Short-time Delay Short-circuit Protection (S)Setting Current: 2–10In; Time Delay: 0.1–0.4sAdjustable inverse/definite time delay to prevent selective tripping
Instantaneous Short-circuit Protection (je)Setting Current: 2–10InRapid short-circuit current interruption without time delay
Ground Fault Protection (G)Setting Current: 0.2–0.8In; Time Delay: 0.1–2sDetects ground faults to avoid equipment damage
Afficher & OperationLCD screen, rotary coding switchReal-time display of current, trip cause and fault records
Méthode de réinitialisationManual/Auto selectableQuick power supply recovery after fault clearance

III. Mechanical & Environmental Parameters

Élément de paramètreSpecification ValueRemarques
Durée de vie mécanique150,000 opérationsNo-load operation, conforme à la CEI 60947-2
Durée de vie électrique10,000 opérations (AC-3, at rated current)On-load breaking life, related to operating frequency
Operating MechanismSpring-loaded energy storage type (manual/electric optional)Electric mechanism suitable for remote control
Contacts auxiliairesStandard: 2NON+2NC, expandable to 4NO+4NCStatus feedback and control circuit interlocking
Température ambiante-25℃~+70℃ (operating); -40℃~+85℃ (stockage)Wide temperature range for industrial applications
Classe de protectionIP30 (body); IP40 (with protective cover)Prevents solid foreign object intrusion
Altitude≤2000m (derating required above 2000m)Rated current derating by 1% for every 100m altitude increase
Méthode de montageFixed type/Drawout typeDrawout type enables maintenance without power outage
  1. Communication & Measurement Parameters
FonctionSpécificationInterface/Protocol
Communication ModuleCOM15 (PROFIBUS DP) / COM16 (MODBUS RTU)Facultatif, supports data upload to monitoring system
Measurement AccuracyCurrent: ±1%; Voltage: ±1.5%; Pouvoir: ±2%Compatible with Plus measurement function for energy management
Data Logging100 fault records (trip type, temps, current value)Fault tracing and system diagnosis
TélécommandeSupports remote opening/closing and parameter settingRealized by electric mechanism + communication module
  1. Installation & Dimension Parameters
Mounting TypeLargeur (W)Height (H)Depth (D)Poids
3WL1116 Fixed Type320mm434mm291mmApprox. 45kg
3WL1116 Drawout Type320mm434mmApprox. 450mmApprox. 55kg
3WL1216 Fixed Type460mm434mm291mmApprox. 56kg
3WL1216 Drawout Type460mm434mmApprox. 450mmApprox. 65kg
Mounting Mode35mm DIN rail/screw mountingFrame I width: 320mm; Frame II width: 460mm; Unified height: 434mm
  1. Key Selection & Application Tips
  2. Breaking Capacity Matching: Select frame size based on the system’s maximum short-circuit current. Frame I is suitable for scenarios ≤66kA, while Frame II is for ≤100kA. UN 20% margin is recommended.
  3. Trip Unit Setting: Enable LSIG protection for motor loads, with the ground fault setting recommended at 0.3–0.5In. LSI protection is sufficient for power distribution loads.
  4. Communication Compatibility: Select COM15/COM16 module for remote monitoring, ensuring protocol compatibility with PLC/SCADA systems (PROFIBUS/MODBUS).
  5. Installation Space: The drawout type occupies approximately 160mm more depth than the fixed type. Reserve sufficient operation and maintenance space during cabinet design.
  6. Replacement & Mise à niveau: The 3WL series has been upgraded to the 3WA series (par ex., 3WA1116-3EG45-4GA4), featuring compatible dimensions and protection functions, plus added Ethernet communication and intelligent diagnosis.

 

 

VII. Conformité & Attestation

Compliant Standards: FR 14048.2, CEI 60947-2, EN 60947-2

Certifications: CE, UL, ASC (for some models), meeting compliance requirements for global industrial applications