Wechat: +86-13184948252 WhatsApp: 0086-13811255435 E-mail: kent@bestcontactor.com

À propos Contact |

Principle and Wiring Guide for the Start-Hold-Stop Circuit (Self-Locking Circuit) - Contacteur,disjoncteur,onduleur solaire,compteur électrique,batteries solaires

Nouvelles

Principle and Wiring Guide for the Start-Hold-Stop Circuit (Self-Locking Circuit)

The start-hold-stop circuit is the most fundamental self-locking control circuit in industrial electrical control. Its core function is to trigger equipment operation via a start button, cut off operation via a stop button, and enable the equipment to keep running even after the start button is released. It is widely used in the standalone control of devices such as motors, pompes, and fans. Combined with the previously mentioned Schneider LC1E180M5N contactor, this document provides a complete circuit design, wiring, and commissioning solution.

  1. Composition of Core Components

Taking three-phase motor control as an example, the start-hold-stop circuit needs to be equipped with the following components:

Component NameModel/SpecificationFonction
Air Circuit BreakerTriphasé, courant nominal > 1.2 times the motor’s rated currentShort-circuit and overload protection for the main circuit; main power switch
AC ContactorSchneider LC1E180M5N (coil voltage: 220V et)Controls the on-off of the main circuit; realizes low-voltage control of high-voltage
Thermal Overload RelaySchneider LR-E series (matched with the contactor)Motor overload protection; prevents winding burnout
Start ButtonLA series normally open (NON) buttonTriggers contactor pull-in; starts the motor
Stop ButtonLA series normally closed (Caroline du Nord) buttonCuts off the contactor coil circuit; stops the motor
Three-Phase MotorSquirrel-cage asynchronous motorControlled load
  1. Principe de fonctionnement
  2. Core Logic

Start and Self-Locking: Press the start button → the contactor coil is energized → the main contacts close and the motor runs; at the same time, the contactor auxiliary normally open contacts close, replacing the start button to keep the coil energized (self-locking), so the motor continues to run after the start button is released.

Stop and Unlocking: Press the stop button → the coil circuit is disconnected → the main contacts and auxiliary normally open contacts open simultaneously, the motor stops, and the self-locking is released; the motor can only restart by pressing the start button again.

  1. Protection Logic

Protection contre les courts-circuits: When the current in the main circuit is excessively high, the air circuit breaker trips instantaneously.

Protection contre les surcharges: When the motor is overloaded, the normally closed contacts of the thermal overload relay open, cutting off the coil circuit, the contactor releases, and the motor shuts down.

III. Étapes de câblage (Taking LC1E180M5N Contactor as an Example)

  1. Câblage du circuit principal (Three-Phase High-Voltage Circuit)

The main circuit is responsible for supplying power to the motor. Wiring sequence: Power Supply → Circuit Breaker → Contactor Main Contacts → Thermal Overload Relay → Motor

Component TerminalConnection RelationshipOperation Points
Circuit Breaker Outlet TerminalsL1, L2, L3Connect three-phase power supply; ensure correct phase sequence
Contactor Main Contact InletsL1, L2, L3 (upper end of the contactor)Connect one-to-one with the circuit breaker outlet terminals
Contactor Main Contact OutletsT1, T2, T3 (lower end of the contactor)Connect to the inlet terminals of the thermal overload relay
Thermal Overload Relay Outlet TerminalsCorresponding terminalsConnect to the three-phase wiring terminals (U, V, W) of the motor
Motor HousingPE grounding wireMust be reliably grounded to prevent leakage
  1. Control Circuit Wiring (220V AC Low-Voltage Circuit)

The control circuit is responsible for controlling the on-off of the contactor coil. The coil voltage is 220V AC (coil parameter of LC1E180M5N). Wiring sequence: Control Power Supply → Stop Button → Start Button → Thermal Overload Relay Normally Closed Contacts → Contactor Coil → Self-Locking Contacts → Power Supply Neutral Line

Specific Wiring Steps

  1. Take one phase of live wire (par ex., L1) and neutral line N from the three-phase power supply as the control circuit power supply (220V et).
  2. Connect the live wire end to one end of the stop button’s normally closed contact (Caroline du Nord), and connect the other end of the stop button to one end of the start button’s normally open contact (NON).
  3. Connect the other end of the start button to one end of the thermal overload relay’s normally closed contact, and connect the other end of the thermal overload relay’s normally closed contact to the contactor coil terminal A1.
  4. Connect the contactor auxiliary normally open contacts (par ex., 13-14) in parallel across the start button terminals (to achieve self-locking): connect auxiliary normally open contact 13 to the common terminal of the stop button and start button, and connect contact 14 to the common terminal of the thermal overload relay normally closed contact and A1.
  5. Connect the contactor coil terminal A2 to the power supply neutral line N.
  6. Safety Precautions
  7. Power-Off Operation: Before wiring, must disconnect the power supply of the main circuit and control circuit, and use a test pencil to confirm no voltage exists.
  8. Button Selection: The stop button must adopt normally closed contacts, and priority should be given to red mushroom-head buttons (emergency stop), which should be installed in an easily accessible position.
  9. Self-Locking Contacts: Must use the contactor’s own auxiliary normally open contacts; it is prohibited to use other components as substitutes, otherwise self-locking cannot be achieved.
  10. Wire Diameter Selection: The cross-sectional area of the control circuit wire should be ≥1.0mm²; the main circuit wire should be selected according to the motor current (par ex., select 4mm² copper core wire for an 18A motor).
  11. Grounding Protection: The motor housing and contactor metal frame must be reliably grounded to prevent leakage and electric shock.
  12. Commissioning Steps
  13. Wiring Inspection

Check whether the phase sequence of the main circuit is correct, and whether the control circuit wiring conforms to the sequence ofStop → Start → Thermal Overload Relay → Coil → Self-Locking”.

Use a multimeter to measure the control circuit: when the start button is pressed, there should be continuity between A1 and A2 (220V et); continuity should remain after releasing the button (self-locking is effective); the circuit should disconnect when the stop button is pressed.

  1. No-Load Test (Disconnect Motor Wiring)

Close the circuit breaker; the power indicator light turns on.

Press the start button → the contactor pulls in (with a “cliquez” sound), the auxiliary contacts realize self-locking, and the contactor remains pulled in.

Press the stop button → the contactor releases, and the motor stops.

Simulate overload test: manually press the test button of the thermal overload relay → the contactor should release immediately.

  1. Load Test

Connect the motor wiring properly and close the circuit breaker.

Press the start button; the motor starts smoothly without abnormal noise; it continues to run after releasing the button.

Press the stop button; the motor stops; it can start normally again.

  1. Common Fault Troubleshooting
Phénomène de défautCauses possiblesSolutions
Contactor does not pull in when the start button is pressed1. No power supply in the control circuit1. Check whether the live wire and neutral line are connected
2. Poor contact of the stop button/thermal overload relay contacts2. Short-circuit the stop button/thermal overload relay contacts for testing
3. Coil damage3. Use a multimeter to measure the coil resistance (normally about several hundred ohms)
Contactor releases immediately after releasing the start button1. Poor connection of auxiliary normally open contacts1. Check whether the wiring of self-locking contacts is loose
2. Damage to auxiliary contacts2. Replace the contactor auxiliary contact module
Motor cannot stop when the stop button is pressed1. Short circuit of the stop button1. Replace the stop button
2. Welding of self-locking contacts2. Overhaul or replace the contactor main contacts/auxiliary contacts
Thermal overload relay trips frequently after the motor starts1. Motor overload1. Check whether the motor load is too heavy
2. Excessively low setting current of the thermal overload relay2. Adjust the setting current of the thermal overload relay to 1.1 times the motor’s rated current

Précédent:

Suivant:

Laisser une réponse

Laisser un message