Wechat: +86-13184948252 WhatsApp: 0086-13811255435 E-mail: kent@bestcontactor.com

À propos Contact |

A9F18325-IC65N-3P-C25A Schneider Circuit Breaker - Contacteur,disjoncteur,onduleur solaire,compteur électrique,batteries solaires

disjoncteur/

A9F18325-IC65N-3P-C25A Schneider Circuit Breaker

Model Breakdown Code Description A9F18325 Official order number for Schneider Electric Acti9 iC65N Miniature Circuit Breaker IC65N Product series: Acti9 iC65 series, N-type breaking capacity (6le), thermal-magnetic trip unit 3P Number of poles: 3 poteaux (3-phase 3-wire), can switch off three phases simultaneously C25A C-curve tripping, rated current 25A (at 30°C) Key Technical Parameters Item ...

  • Détails du produit
  1. Model Breakdown
CodeDescription
A9F18325Official order number for Schneider Electric Acti9 iC65N Miniature Circuit Breaker
IC65NProduct series: Acti9 iC65 series, N-type breaking capacity (6le), thermal-magnetic trip unit
3P.Nombre de pôles: 3 poteaux (3-phase 3-wire), can switch off three phases simultaneously
C25AC-curve tripping, rated current 25A (at 30°C)
  1. Paramètres techniques clés
ArticleSpécification
MarqueSchneider Électrique
Série de produitsActi9 iC65N
TaperMiniature Circuit Breaker (MCB), thermal-magnetic trip
Courant nominal25UN (at 30°C)
Poteaux3P. (3 protective poles)
Courbe de déclenchementC-curve (instantaneous trip at 5–10In, for distribution and lighting circuits)
Capacité de coupure6le (compliant with IEC/EN 60898-1)
Tension nominale400V et (3-phase), 230V et (monophasé)
Rated Frequency50/60Hz
Montage35Montage sur rail DIN standard de mm
Ambient ConditionsTemp: -25°C ~ +40°C, altitude ≤2000m, humidity ≤95% (non-condensing)
ProtectionProtection contre les surcharges (voyage thermal) et protection contre les courts-circuits (magnetic trip)
  1. Caractéristiques du produit
  2. Haute fiabilité: Thermal-magnetic tripping provides accurate overload and short-circuit protection
  3. Conception modulaire: Taille compacte, saves panel space, easy installation and maintenance
  4. Wide Application: For all low-voltage distribution systems: residential, commercial and industrial
  5. Certifications: Conforme à la norme CEI/EN 60898-1, GB10963.1 and other international & national standards
  6. Longue durée de vie: Mechanical life ≥20,000 operations, electrical life ≥5,000 operations
  7. Applications

3‑phase distribution systems: Overload and short-circuit protection for 3‑phase circuits

Circuits d'éclairage: 3‑phase lighting protection in large commercial buildings and industrial plants

Power equipment: Control and protection of small 3‑phase motors, pompes, les fans, etc..

Distribution boards / cabinets: Main or branch switch for low-voltage distribution systems

  1. Modèles de remplacement & Cross-Brand Comparison

5.1 Schneider Same-Series Replacements

ModèleDifferenceApplication Change
A9F1832020UN, C-curve, 3P.For lower load current
A9F1833232UN, C-curve, 3P.For higher load current
A9F1932525UN, D-curve, 3P.For inductive loads such as motors
A9F1822525UN, C-curve, 2P.Single-phase circuit protection
  1. Installation & Usage Notes
  2. Avant l'installation, confirm model matches system parameters: check rated current, poles and tripping curve
  3. Must be mounted on standard 35mm DIN rail for secure installation
  4. Ensure terminals are tightly connected to avoid overheating
  5. Inspect breaker status regularly to ensure proper tripping mechanism
  6. After a fault trip, eliminate the cause before manually resetting
  7. Recommandations de sélection
  8. C-curve is suitable for distribution and lighting circuits; not recommended for frequent-start motors (use D-curve)
  9. 3P breakers are for 3-phase 3-wire systems; use 4P if neutral protection is required
  10. 6kA breaking capacity is for general industrial & bâtiments commerciaux; use higher-rated types (par exemple. H-type 10kA) for high short-circuit current

Recommended Replacements for A9F18325-IC65N-3P-C25A

  1. Direct Replacements (Schneider Électrique)
Modèle de remplacementOrder No.Paramètres clésDifferenceApplication
IC65N 3P C25AA9F183253P., C25A, 6leIdentical, originalSame distribution protection
IC65N 3P C20AA9F183203P., C20A, 6le20UN (lower)3-phase lighting / distribution with lower load
IC65N 3P C32AA9F183323P., C32A, 6le32UN (higher)3-phase lighting / distribution with higher load
IC65N 3P D25AA9F193253P., D25A, 6leD-curve (10–14In trip)3-phase motors, compressors and inductive loads
IC65H 3P C25AA9F283253P., C25A, 10le10le (pouvoir de coupure plus élevé)Industrial environments with high short-circuit current
IC65L 3P C25AA9F383253P., C25A, 15le15le (highest level)Critical power systems with very high fault current
IC65N 4P C25AA9F184254P., C25A, 6le4 poteaux (includes neutral protection)3-phase 4-wire systems
  1. Upgraded Replacements (New Schneider Series)
SérieModèleOrder No.Upgrade AdvantageApplication
Acti9 IC60NIC60N 3P C25AA9F58325Plus compact, higher short-circuit withstandNew projects with limited panel space
Acti9 IC40NIC40N 3P C25AA9P58325Ultra-slim (18mm/pole), space-savingSmall distribution boards, residential / commercial
  1. Cross-Brand Equivalent Replacements
MarqueModèleParamètres clésMatchCost
ABBS203-C253P., C25A, 6le★★★★★Moyen, reliable quality
Siemens5SY6325-7CC3P., C25A, 6le★★★★★Moyen, German quality
CHINTNXB-63-3P C253P., C25A, 6le★★★★☆Lower, high-quality domestic
DélicieuxCDM30s-63C25/33003P., C25A, 6le★★★★☆Lower, rentable
Commutateur ChangshuCH1-63C25/3P3P., C25A, 6le★★★★☆Lower, well-known domestic brand
LiangxinNDM1-63C25/3P3P., C25A, 6le★★★★☆Lower, suitable for industry

Key Selection Advice for Replacements

  1. Direct equivalent: Prefer IC65N 3P C25A (A9F18325) to match original protection characteristics
  2. Courbe de déclenchement:

C-curve (5–10In): distribution & éclairage

D-curve (10–14In): moteurs, transformers to avoid nuisance tripping

  1. Pouvoir de coupure:

6le (N-type): general commercial & residential

10le (H-type): industriel & large commercial

15le (L-type): critical systems with high fault current

  1. Poteaux:

3P.: 3-phase 3-wire (no neutral protection)

4P.: 3-phase 4 fils (phase + protection neutre)

  1. Brand choice:

International (ABB, Siemens): stable, for critical equipment & export projects

Domestique (CHINT, Délicieux): rentable, for general industrial & civil projects

Précédent: