ABB T6N800-TM800-40000-8000-F-F-3P

This is an ABB SACE Tmax T6N 800A MCCB equipped with a TMA800/4000-8000 adjustable thermomagnetic release, 3-pôle, fixed mount, front connection, with N-type breaking capacity (36kA@400V). It is used as a main switch in industrial main circuits, heavy-duty motor protection, and power distribution systems. Full Model Code Breakdown Section Marking Description Technical Note 1 T6 ...

  • Détails du produit

This is an ABB SACE Tmax T6N 800A MCCB equipped with a TMA800/4000-8000 adjustable thermomagnetic release, 3-pôle, fixed mount, front connection, with N-type breaking capacity (36kA@400V). It is used as a main switch in industrial main circuits, heavy-duty motor protection, and power distribution systems.

  1. Full Model Code Breakdown
SectionMarkingDescriptionTechnical Note
1T6Frame sizeTmax T series MCCB, max frame current 800A, conception compacte (depth 103.5mm)
2NClasse de pouvoir de coupureN‑type standard breaking capacity: 36kA@400V/415V, 25kA@500V, 20kA@600V
3800Frame rated currentMaximum rated current of the disjoncteur frame: 800UN
4TM/TMARelease typeThermomagnetic Adjustable release – both overload (thermal) and short‑circuit (magnetic) protection are adjustable
5800Courant nominal (Dans)Continuous operating current: 800UN
640000‑8000Instantaneous trip rangeI3 = 4000–8000A, adjustable short‑circuit instantaneous protection
7FMounting typeFixé (non‑withdrawable)
8FConnection typeConnexion frontale
93P.Poteaux3‑pole circuit breaker for three‑phase systems
  1. Paramètres techniques clés
ArticleValeurRemarques
Product typeSACE Tmax T6N 800A MCCBFactory code: 1SDA060214R1
Tension d'isolement nominale (Interface utilisateur)1000VMaximum continuous voltage for insulation parts
Rated impulse withstand voltage (Ump)8kVCapability to withstand transient high voltage
Rated operating voltage (Ue)690V etMax operating voltage
Fréquence50/60HzFor standard mains systems
Caractéristique du voyageAdjustable thermomagneticSurcharge (inverse time), short‑circuit (instantaneous)
Ultimate breaking capacity (ICU)36kA@400VN class
25kA@500V
20kA@600V
Service breaking capacity (Ics)100% ICUReusable after tripping
Courant nominal (Dans)800UNMaximum continuous current
Instantaneous trip range4000–8000AI3 = 5–10In, réglable
Dimensions (mm)H×L×P: 268×210×103.5Uniform depth for panel layout
Poidsenviron. 9kilosStandard
Protection degreeIP30CEI 60529
  1. Applications typiques
  2. Industrial power distribution

Main or sub-switch for 3-phase 800A circuits in factories, workshops, data centers.

  1. Large motor protection

Three-phase induction motors up to approx. 400kW (380V)

Critical motor circuits requiring adjustable overload and short-circuit protection

  1. Building electrical

Main switchboards in commercial and high-rise buildings

Power circuits for HVAC, pompes, and large equipment

  1. Renewable energy

Main switches in combiner boxes for PV and wind power systems

DC-side protection for energy storage (DC version required)

  1. Other heavy industries

Mining, ports, railways, and applications requiring high reliability and adjustable protection.

  1. Replacement Models

4.1 ABB Upgrades / Replacements

Modèle de remplacementDifférence principaleApplication
T6S800 TMA800/4000‑8000 FF 3PBreaking capacity upgraded to S class (50kA@400V)Systems with higher short‑circuit current near transformers
T6L800 TMA800/4000‑8000 FF 3PBreaking capacity upgraded to L class (70kA@400V)Heavy industrial grids and large plants
T6N800 PR221DS‑LSI 800 FF 3PElectronic LSI release (Long / Short / Instantané)Complex systems requiring precise grading and selectivity
XT6N800 TMA800/4000‑8000 FF 3PNew‑generation Tmax XT, same dimensions, performances amélioréesSystem upgrades and new installations

4.2 Cross-Brand Equivalents

MarqueModèleParamètres de correspondance clésRemarques
SchneiderNSX630N TM800D 3PIn=800A, Icu = 36 kA, thermomagneticNSX max frame 630A; 800A is special rating
Siemens3VA6880‑6EL32‑0AA0In=800A, Icu = 36 kA, 3P., thermomagnetic3VA series, performances similaires
MitsubishiNF800‑CW 3PIn=800A, Icu = 35 kA, thermomagneticJapanese standard, suitable for Japanese equipment
DeltaPM800H‑3PIn=800A, Icu = 36 kA, thermomagneticCost‑effective industrial MCCB
  1. Sélection & Application Notes
  2. Breaking capacity matching

Ensure short-circuit current ≤ 36kA@400V; otherwise use T6S/T6L.

Icu is only 20kA at 600V – use with caution.

  1. Release settings

Surcharge (thermal): set to 1.0–1.1 × load rated current

Instantané (magnetic): set to 5–10 × In to avoid nuisance tripping while maintaining selectivity.

  1. Montage & wiring

Fixé, front connection; allow depth ≥ 103.5mm.

Use copper busbar/cable rated for 800A; ≥240mm² copper recommended.

  1. Entretien & replacement

Regularly verify release settings.

Inspect contacts after short-circuit tripping; replace if needed.

For upgrades, prefer T6S/T6L or XT6N to keep dimensions compatible.

  1. Conclusion

ABB T6N800-TM800-40000-8000-F-F-3P is a high-performance 800A MCCB with compact size, adjustable thermomagnetic protection, and standard breaking capacity. It is ideal for high-current three-phase circuits in industrial automation. Selection should consider system short-circuit current, protection requirements, and installation space. For better accuracy and selectivity, use higher-breaking versions or electronic releases.

Schneider Replacement for ABB T6N800-TM800-40000-8000-F-F-3P

Key Summary: The ABB T6N800 is an MCCB; Schneider’s NSX series is the best match. If you require an MT air circuit breaker (PBR), suitable models are also available. Full solutions and technical comparisons below.

  1. Product Type Comparison
TaperABBSchneider Corresponding SeriesDifférence principale
MCCBT6N800NSX SeriesCompact, 36–150kA, for sub‑circuits
PBRNo equivalent in Tmax T6MT SeriesLarger, 50–200kA, for main incomers
  1. Schneider MT ACB Replacement

2.1 Recmmended Model: MT08N1 3P F MIC2.0+LR 800A

Model explanation:

MT08: Frame size 800A

N1: Breaking capacity 50kA@400V (higher than T6N 36kA)

3P.: 3-pôle

F: Fixed mount

MIC2.0+LR: Thermomagnetic protection (Long + Instantané)

800UN: Courant nominal

Parameter matching:

ArticleABB T6N800Schneider MT08N1Match Level
Courant nominal (Dans)800UN800UNPerfect
MontageFixéFixéPerfect
Poteaux3P.3P.Perfect
Pouvoir de coupure (ICU)36kA@400V50kA@400VHigher
Release typeThermomagnetic (TMA)Thermomagnetic (LR)Functional match
Instantaneous range4000–8000A (5–10In)5–10In adjustablePerfect

Order No: 63006 (MT08N1 3P F MIC2.0 800A)

2.2 Alternatives (Higher Breaking)

MT08N2 3P F MIC2.0+LR 800A: 50kA@400V, wider current range

MT08H1 3P F MIC2.0+LR 800A: 65kA@400V for heavy short-circuit systems

  1. Better Schneider NSX MCCB Replacement

3.1 Modèle recommandé: NSX800F TMD 800 3P3D F

Model explanation:

NSX800: Frame 800A

F: 36kA@400V (identical to T6N)

TMD: Thermomagnetic release (type de distribution)

800: Rated current 800A

3P3D: 3-pôle

F: Fixé, front connection

Parameter matching:

ArticleABB T6N800Schneider NSX800FMatch Level
TaperMCCBMCCBPerfect
Dans800UN800UNPerfect
ICU36kA@400V36kA@400VPerfect
MontageFixéFixéPerfect
ConnexionFrontFrontPerfect
Poteaux3P.3P.Perfect
LibérerTMATMDPerfect
Instantané5–10In5–10InPerfect

Order No: C80F3TM800

3.2 Higher-Breaking Alternatives

NSX800N TMD 800 3P3D F: 50kA@400V, order No C80N3TM800

NSX800H TMD 800 3P3D F: 70kA@400V for heavy industry

  1. Replacement Selection Notes
  2. Product type choice

For direct replacement of an MCCB, choose NSX for identical form factor.

For upgrading to a main incomer, use MT ACB (note larger dimensions).

  1. Release settings

Long-delay (Ir): 1.0–1.1 × rated current

Instantané (Ii): 5–10 × In (4000–8000A) to match original ABB behavior.

  1. Pouvoir de coupure

MT08N1, NSX800N/H exceed 36kA for improved safety.

NSX800F is sufficient if Isc ≤ 36kA.

  1. Mounting space

MT ACB depth ~300mm (much larger than T6N 103.5mm)

NSX matches T6 dimensions for easy retrofit.

  1. Résumé

Top Recommendation: Schneider NSX800F TMD 800 3P3D F (order No C80F3TM800).

Perfectly matches the ABB T6N800 in type, actuel, mounting, pouvoir de coupure, and characteristics, with near-identical dimensions for easy replacement.

Alternative: If ACB is required, use MT08N1 3P F MIC2.0+LR 800A (order No 63006), which provides higher breaking capacity but requires more space.

Let me know if you want a simplified 1-page English datasheet version for customers or bidding.

Précédent:

Suivant:

Laisser une réponse

Laisser un message