Interrupteur de protection de démarreur de moteur Chint NS2-25/4-6,3A

Élément de paramètreSpécification
Tension d'isolation nominale690V
Rated Working VoltageAC 230/240V, 400/415V, 440V, 500V, 690V
Rated Frequency50/60HZ
Setting Current Range4~6.3A
Instantaneous Electromagnetic Trip Current78UN (environ 12 times the setting current)
Capacité de coupure de court-circuitIcu=100kA, Ics=7.5kA (at AC400V)
Classe de protectionIP20 (front side)
Fréquence de fonctionnement≤30 times/hour
Applicable Ambient Temperature-5℃~+40℃
PoidsApproximately 313g

  • Détails du produit

Chint NS2-25/4-6.3A is a starter protection switch specifically designed for three-phase squirrel-cage induction motors. It integrates the functions of a disjoncteur and a thermal relay, providing overload protection, phase failure protection, protection contre les courts-circuits, and infrequent starting control.

Model Interpretation:

NS2: Code de série (N stands for Chint, S stands for Starter)

25: Frame current rating (25UN)

4-6.3UN: Rated current range of the trip unit (adjustable within 4-6.3A)

  1. Paramètres techniques de base
Élément de paramètreSpécification
Tension d'isolation nominale690V
Rated Working VoltageAC 230/240V, 400/415V, 440V, 500V, 690V
Rated Frequency50/60HZ
Setting Current Range4~6.3A
Instantaneous Electromagnetic Trip Current78UN (environ 12 times the setting current)
Capacité de coupure de court-circuitIcu=100kA, Ics=7.5kA (at AC400V)
Classe de protectionIP20 (front side)
Fréquence de fonctionnement≤30 times/hour
Applicable Ambient Temperature-5℃~+40℃
PoidsApproximately 313g

III. Caractéristiques fonctionnelles

  1. Multiple Protection Functions

Protection contre les surcharges: Built-in bimetallic thermal element acts when the current exceeds the setting current for a certain period, preventing motor burnout due to overheating.

Phase Failure Protection: Detects the loss of any phase in the three-phase power supply and immediately cuts off the circuit to protect the motor.

Protection contre les courts-circuits: Instantaneous electromagnetic trip unit operates rapidly (≤100ms) when the current reaches 78A, preventing the expansion of short-circuit faults.

Fonction d'isolement: Can be used as an isolating switch to ensure maintenance safety.

  1. Control Functions

Integrates start/stop button control with a compact structure.

Supports 35mm standard DIN rail mounting for quick deployment.

Optional accessories available: Undervoltage Trip (UV), Déclenchement de dérivation (SH), Auxiliary Contact (AE/AU), Fault Signal Contact (FA).

  1. Scénarios d'application

NS2-25/4-6.3A is suitable for:

Protection and control of three-phase induction motors with a power of approximately 2.2kW (400V).

Control of small and medium-sized motors in factories and workshops, comme les fans, pompes à eau, convoyeurs, compresseurs, and other equipment.

Motor control cabinets in building automation systems.

Can replace the traditional circuit breaker + thermal relay combination scheme, saving space and costs.

  1. Précautions d'utilisation
  2. Exigences d'installation

Install vertically with an inclination angle ≤±5° to ensure reliable operation.

The tightening torque for the terminal screws (M4) is 1.7N·m; avoid over-tightening to prevent thread damage.

Recommended wire cross-sectional area: 1~6mm², wire stripping length: 10mm.

  1. Paramétrage

Setting Current: Should be adjusted to 1.05~1.1 times the motor’s rated current to ensure protection sensitivity and avoid false tripping.

When the ambient temperature deviates significantly from 25℃, adjust the setting current according to the temperature compensation characteristic table.

  1. Operating Restrictions

Do not operate beyond the rated voltage or frequency.

The operating frequency shall not exceed 30 times/hour; frequent operation will shorten the service life.

It is strictly prohibited to disassemble or replace parts with live electricity; the power supply must be cut off first and confirmed to be de-energized.

  1. Référence de sélection

To select the appropriate NS2 series product for your motor:

  1. First determine the motor’s rated current.
  2. Choose a model whose setting current range includes the motor’s rated current.
  3. Motor power reference: NS2-25/4-6.3A is suitable for motors with a power of approximately 2.2kW (400V).
  4. In systems with high-order harmonics such as inverter power supply, it is recommended to select the specification according to 1.3~1.9 times the motor’s rated current.

Résumé

Chint NS2-25/4-6.3A is a reliable-performance motor starter protection switch that integrates protection and control functions. It is particularly suitable for three-phase induction motors of around 2.2kW. Not only can it effectively protect motors from overload, phase failure, and short-circuit damage, but it also simplifies the design of control systems, making it an ideal choice in the field of industrial electrical control.