The following is a detailed technical analysis and application guide for Disjoncteurs CC série NB1-63DC de Chint. It is compiled in combination with official materials and industry standards, covering core performance, selection key points, and typical scenarios:
- Paramètres techniques de base
- Spécifications de base
| Item | Paramètre |
| Tension nominale | DC 250V, 500V, 1000V (Breaking capacity varies with voltage level) |
| Courant nominal | 1~63A (1P/2P/4P optional, Courbe de déclenchement: Type C 5-10In, Type D 10-14In) |
| Capacité de coupure | – DC 250V: 10le (Tapez C) |
| – DC 500V: 8le (Tapez C) | |
| – DC 1000V: 6le (Tapez C) | |
| Arc Extinguishing Method | Air arc extinguishing + magnetic blowout technology (Accelerates arc extinguishing through the magnetic field, suitable for DC highly inductive loads) |
| Tripping Characteristics | Protection contre les surcharges: Inverse time-limit characteristic, in line with IEC 60947-2 standard. |
| Short-circuit Protection: Instantaneous tripping, Tapez C (5-10Dans), Tapez D (10-14Dans) |
- Environmental and Mechanical Performance
| Item | Paramètre |
| Température de fonctionnement | -35℃~+70℃ (Wide temperature design, adaptable to harsh environments) |
| Niveau de protection | IP20 (Front protection) |
| Méthode d'installation | 35mm standard rail installation (Supports DIN EN 50022) |
| Wiring Specification | Circuit principal: 2.5~16mm² single-core/stranded wire (M4 screw) |
- Certifications and Standards
Certifications internationales: CCC, CE, EAC, TÜV, CB, SEMKO.
Standards Compliance: GB/T 14048.2, CEI 60947-2, RoHS environmental protection directive.
- Analysis of Key Features
- DC-specific Design
Arc Extinguishing Optimization: Adopts magnetic blowout arc extinguishing technology, which quickly stretches and cools the arc through the magnetic field to solve the problem of difficult arc extinguishing in DC circuits.
Polarity Protection: No built-in reverse connection protection, and anti-reverse connection function needs to be achieved through an external diode or MOS tube circuit.
- Intelligent Tripping and Protection
Protection contre les surcharges: Bimetallic inverse time-limit tripping, the larger the current, plus le temps de déclenchement est court (Par exemple: it will act within 2 minutes at 1.5 fois le courant nominal).
Short-circuit Protection: The electromagnetic trip unit responds instantaneously. Type C is suitable for conventional loads (such as LED lighting), and Type D is suitable for high-impact loads (comme les moteurs).
- Extended Functions
Contacts auxiliaires: Supports external connection of OF (contact auxiliaire) and SD (contact d'alarme) to achieve indication of opening and closing states or remote monitoring.
Compatibilité des accessoires: Can be equipped with shunt trip units (XF9), undervoltage trip units (MN), etc.. for extended functions.
III. Selection and Application Scenarios
- Selection Guide
- Correspondance de tension: Select the corresponding model according to the system voltage (Par exemple, choose NB1-63DC/500V for DC 500V).
- Current Calculation:
Continuous Load: Rated current ≥ 1.2 times the load current.
Impact Load: Type D tripping curve, rated current ≥ (Load starting current / 10).
- Capacité de coupure: Ensure that the breaking capacity (ICU) of the circuit breaker ≥ the system short-circuit current.
- Applications typiques
| Scénario | Model Recommendation | Configuration Description |
| Photovoltaic String Protection | NB1-63DC/500V C16A | Suitable for 1500V photovoltaic systems (Needs to be derated for use), protects the string from overload and short-circuit |
| Energy Storage System | NB1-63DC/1000V D25A | High short-circuit breaking capacity, protects the battery pack and inverter interface |
| Industrial DC Motor | NB1-63DC/250V D32A | Type D tripping curve, can withstand the starting impact current of the motor |
| Communication Base Station | NB1-63DC/48V C6A | Low voltage and high reliability, protects the power supply of communication equipment |
- Installation et entretien
- Points clés de l'installation
Wiring Specification: The main circuit wiring needs to be tightened to a torque of 6N·m to avoid loose connection and heat generation.
Polarity Confirmation: Connect the positive and negative poles strictly according to the markings to avoid damage to the circuit breaker due to reverse connection.
Exigences environnementales: Avoid using in environments with high humidity (>90%RH) or corrosive gases.
- Maintenance Suggestions
Inspection régulière: Clean the contacts every quarter and check the flexibility of the tripping mechanism.
Life Management: Mechanical life ≥ 200,000 fois, electrical life ≥ 100,000 fois (DC-21A load).
Dépannage: After tripping, confirm the cause of the fault, and manually disconnect the power supply before resetting.
- Comparison and Alternative Solutions
| Modèle | Plage de tension | Capacité de coupure | Caractéristiques |
| NB1-63DC | DC 250~1000V | 6~10kA | Magnetic blowout arc extinguishing, supports wide temperature environment, suitable for highly inductive loads |
| NB1Z-63 | AC/DC 220~400V | 6le (CA) | Suitable for both AC and DC, an economical choice with lower breaking capacity |
| NSX400N(Schneider) | DC 1000V | 50le | High short-circuit breaking capacity, suitable for large-scale energy storage systems, with a higher price |
- Précautions
- Derating for Use: When the ambient temperature exceeds 40℃, select the rated current according to derating 5% for every 10℃ increase.
- Short-circuit Withstand: The breaking capacity needs to match the system short-circuit current, otherwise it may lead to damage to the circuit breaker or the risk of fire.
- Modèles alternatifs: If a higher breaking capacity is required, Chint’s NB1-63H (CA) or NB1-DC (DC-specific, breaking capacity 15kA) peut être sélectionné.
For detailed technical manuals or customized solutions, you can visit Chint’s official web siteor contact local technical support.