| Model Part | Signification |
| ABE | Code de série, Meta-MEC economy MCCB, thermal-magnetic trip, low breaking capacity (economy type) |
| 40 | Frame rating current 400A |
| 4 | 4 poteaux (4P.), suitable for three-phase four-wire system protection |
| B | Breaking capacity class B (10kA@AC380V) |
| 400UN | Rated operational current 400A, set by plug module |
- Paramètres techniques clés
| Article | Spécification | Description |
| Type de produit | Economy Disjoncteur à boîtier moulé (MCCB) | Déclenchement thermomagnétique, fixed mount |
| Tension nominale | AC 600V, Ui 690V | Conforme à la CEI 60947-2 |
| Rated Frequency | 50/60Hz | Universal frequency range |
| Capacité de coupure | Icu=10kA@AC380V | Class B economy breaking capacity |
| Type de voyage | Fixed thermal-magnetic trip | Protection contre les surcharges (inverse time) + protection contre les courts-circuits (instantaneous) |
| Tension d'isolation nominale | Ui=690V | Maximum voltage for insulation performance |
| Mechanical Endurance | 8500 opérations | Standard operating cycles |
| Electrical Endurance | 1000 opérations | Operating cycles at rated current |
| Mounting Type | Type fixe | Standard 35mm DIN rail or panel mount |
| Connexion | Connexion frontale / Connexion arrière | Optional for different installations |
| Applicable Standards | CEI 60947-1/2, DANS 60947-1/2 | International electrical standards |
- Series Model List (400AF Frame)
| Modèle | Poteaux | Capacité de coupure | Rated Current Range |
| ABE402b | 2P. | 10le | 250UN, 300UN, 350UN, 400UN |
| ABE403b | 3P. | 10le | 250UN, 300UN, 350UN, 400UN |
| ABE404b | 4P. | 10le | 250UN, 300UN, 350UN, 400UN |
| ABS402b | 2P. | 25le | 250UN, 300UN, 350UN, 400UN |
| ABS403b | 3P. | 25le | 250UN, 300UN, 350UN, 400UN |
| ABS404b | 4P. | 25le | 250UN, 300UN, 350UN, 400UN |
| ABH402b | 2P. | 35le | 250UN, 300UN, 350UN, 400UN |
| ABH403b | 3P. | 35le | 250UN, 300UN, 350UN, 400UN |
| ABH404b | 4P. | 35le | 250UN, 300UN, 350UN, 400UN |
- Recommended International Brand Replacements
| Marque | Série | Modèle de remplacement | Paramètres de correspondance clés |
| Schneider | EZD Series | EZD400E4400 | 4P., 400UN, 10le, thermal-magnetic trip |
| Siemens | 3VT Series | 3VT8440-1AA03 | 4P., 400UN, 10le, thermal-magnetic trip |
| ABB | Tmax Series | T2N400 TMD 400/400 FF 4P | 4P., 400UN, 10le, thermal-magnetic trip |
| Eaton | Power Defense | LZMN4-A400-I | 4P., 400UN, 10le, thermal-magnetic trip |
| Commutateur Changshu | CM3 Series | CM3-400M/4300B 400A | 4P., 400UN, 10le, thermal-magnetic trip |
- Applications & Notes de sélection
- Applications typiques
End protection in low-voltage distribution systems, par ex., lighting and power distribution in commercial buildings and industrial plants
Three-phase asynchronous motor protection (≤200kW, 380V)
Capacitor bank protection
Small generator outlet protection
- Selection Guidelines
Confirm system voltage (≤600V) and frequency (50/60Hz)
Calculate circuit rated current to ensure 400A meets long‑term operation
Evaluate short-circuit level: if >10le, use higher breaking capacity ABS (25le) or ABH (35le) série
Consider pole requirement: 4P for neutral protection applications
Confirm mounting (fixed/drawout) and connection direction (front/rear)
- Caractéristiques du produit & Avantages
- Économique & Practical: ABE series is cost-effective for budget‑limited projects
- Standard Design: Complies with IEC standards, interchangeable with other brands
- Reliable Protection: Thermal-magnetic trip provides basic overload and short-circuit protection
- Flexible Installation: Supports front/rear wiring and multiple mounting methods
- Complete Accessories: Can be equipped with auxiliary contacts, alarm contacts, déclencheur à minimum de tension, etc..
- Entretien & Troubleshooting
- Inspection régulière: Inspect appearance and tighten terminals quarterly to avoid looseness or overheating
- Trip Test: Perform manual trip test annually to verify mechanical reliability
- Troubleshooting:
Frequent overload tripping: Check load or replace with higher rated model
Short-circuit tripping: Locate and repair short circuit before closing
Failure to close: Check mechanical jam or replace damaged parts
LS ELECTRIC ABE404B-4P-400A is an economy 4-pole MCCB with 400A rated current and 10kA breaking capacity, suitable for low-voltage distribution systems with moderate breaking requirements. Pour un pouvoir de coupure plus élevé, use ABS (25le) or ABH (35le) série.
Applications of LS ELECTRIC ABE404B-4P-400A MCCB
Core Positioning:
This 4-pole economy MCCB (4P., 400UN, 10le) is mainly used for end protection in low‑voltage distribution systems, especially where neutral protection is required, short-circuit current ≤10kA, and budget is limited.
- Commercial Building Distribution
| Application | Suitability | Conseil de sélection |
| Main distribution board main breaker | 4P protects 3-phase 4-wire; 400A fits small‑to‑medium commercial buildings | Total load ≤320A (80% duty), short-circuit ≤10kA |
| Main A/C protection | 400A for large central A/C units (≤200kW, 380V) | Match compressor inrush; recommend undervoltage release |
| Emergency lighting | 4P ensures neutral continuity for reliable emergency operation | Use with EPS/UPS; front connection for easy maintenance |
| Elevator room power | 400A for multiple elevators; 4P prevents neutral faults | Install in dedicated cabinet; ensure ventilation |
Typical Cases:
3–5 story office buildings, chain supermarkets, hotels as main or important branch breaker.
- Industrial Plant Applications
- General Machinery
Main breaker for small‑medium production lines: 400A covers multiple branches; 10kA suits general industrial short-circuit levels
Motor group protection: Total power ≤200kW, used with thermal relays for precise protection
Auxiliary equipment: Ventilateurs, pompes, compresseurs; 4P for control circuits with neutral
- Specific Industries
Food processing: Cost-effective for light industry; 4P ensures safety and quality
Electronic assembly: 400A for multiple lines; 4P avoids neutral drift affecting precision equipment
Warehouse power: Main breaker for lighting and forklift charging
Warning:
If short-circuit current >10le, upgrade to LS ABS (25le) or ABH (35le).
- Public & Residential Buildings
- Education & Medical
School main distribution: 4P protects lighting, A/C, salles informatiques; 400A for whole building
Community hospital: 4P for medical equipment with neutral; economy for primary care
Stadium auxiliary systems: Éclairage, audio, seats; 400A for local zones
- Infrastructure
Small wastewater treatment: 400A for pumps and blowers; 4P prevents control system failure
Urban landscape lighting: Main breaker for multi-loop lighting with reliable neutral
Small waste transfer station: 400A for compressors and conveyors; low operating cost
- Applications spéciales
- Capacitor Bank Protection
For capacitor banks ≤100kvar; 4P prevents inrush and short-circuit during switching
Recommend adding SPD for surge protection
- Small Generator Systems
Main breaker for generators ≤300kVA; 4P ensures safe isolation from grid
Used with synchronizing equipment for smooth switch between mains and generator
- Temporary Power
Construction site temporary power main breaker; 400A for cranes, welders
4P suitable for harsh site conditions; prevents electric shock from broken neutral
- Key Selection & Application Criteria
| Facteur | Recommandé | Not Suitable For |
| Short-circuit level | ≤10kA: suitable; >10le: use ABS/ABH | High-risk areas (chemical, mining) avec >10le |
| Load type | Resistive & charges inductives (éclairage, moteurs) | Large rectifiers, arc furnaces, high nonlinear loads |
| Earthing system | TN-S, TT systems (4P neutral protection) | IT systems (operating rooms, mines) |
| Environnement | Indoor dry, ≤40°C | Outdoor, damp, explosive areas (needs special enclosure) |
| Operation frequency | Infrequent operation (≤12/day) | Frequent duty (cranes, elevator main circuits) |
- Application Advantages
- Économique: High cost-performance for budget projects
- Full protection: 4P design covers 3-phase + neutral for modern distribution
- Standard compliance: CEI 60947-2, interchangeable with major brands
- Flexible installation: Front/rear wiring + 35mm rail DIN
- Reliable: Mécanique 8500, électrique 1000 opérations
Best Combination:
Use ABE404B-4P-400A as main breaker + LS MCBs for branch protection to form a reliable two‑stage system.
For higher performance or electronic protection, upgrade to ABS (25le), ABH (35le), or ABN (electronic trip) série.
Contacteur,disjoncteur,onduleur solaire,compteur électrique,batteries solaires


















NH42-63-318x560.png)