Wechat: +86-13184948252 WhatsApp: 0086-13811255435 E-mail: kent@bestcontactor.com

À propos Contact |

Disjoncteur NM1-400S/3000 400A - Contacteur,disjoncteur,onduleur solaire,compteur électrique,batteries solaires

disjoncteur/

Disjoncteur NM1-400S/3000 400A

NM1: CHINT NM1 series molded case circuit breaker

400: Frame size rated current of 400A (the maximum current rating in this series)

S: Breaking capacity characteristic code (standard type with a breaking capacity of 50kA)

3000: Pole number + release type + accessory configuration

First digit "3": 3-pole (three-phase) design

"000": Indicates no accessories (no auxiliary contacts, no alarm contacts, no shunt release)

400UN: Rated operating current of 400A (the maximum current for long-term stable operation)

  • Détails du produit

The NM1-400S/3000 400A is a 3-pole disjoncteur à boîtier moulé manufactured by CHINT Electric. As a standard type (S) product in the NM1 series, it has a rated current of 400A and is designed for overload, short-circuit, and undervoltage protection in power distribution systems.

  1. Model Designation Explanation

NM1: CHINT NM1 series molded case circuit breaker

400: Frame size rated current of 400A (the maximum current rating in this series)

S: Breaking capacity characteristic code (standard type with a breaking capacity of 50kA)

3000: Pole number + release type + accessory configuration

First digit “3”: 3-pole (three-phase) design

“000”: Indicates no accessories (no auxiliary contacts, no alarm contacts, no shunt release)

400UN: Rated operating current of 400A (the maximum current for long-term stable operation)

  1. Core Parameters and Performance
Parameter ItemValeurDescription
Tension d'isolation nominale800VMaximum withstand voltage for insulation
Tension de fonctionnement nominale690V (AC 50Hz)Standard voltage suitable for three-phase systems
Courant nominal400UNMaximum current for long-term stable operation
Capacité de coupure50leMaximum short-circuit current that can be safely interrupted
Arc Flash Distance≤100mmArc ejection distance during short-circuit breaking
Release TypeThermal-magneticProvides both thermal protection (surcharge) and magnetic protection (short-circuit)
Fonctions de protectionOverload, short-circuit, sous-tensionComprehensive circuit protection
Operation MethodManual (configuration standard)Electric operating mechanism is optional
Protection RatingIP20Prevents intrusion of solid foreign objects larger than 12mm
Méthode de montageFront/back panel wiring (optional)Flexible installation methods
WeightApproximately 6.8kg (4-pole reference)Net weight of the product

 

III. Appearance and Structural Features

Housing Material: High-strength thermoplastic with properties of impact resistance, self-extinguishing, and heat resistance

Operating Handle: Located in the center of the front face of the circuit breaker; red indicates open position, green indicates closed position

Terminal Blocks: 3 sets of input/output terminals (corresponding to three phases), equipped with M12 hexagon socket screws (torque: 26N·m)

Dimension Reference:

Width: Approximately 128mm (3-pole)

Height: Approximately 257mm (reference to similar products)

Depth: Approximately 150mm (reference to similar products)

Internal Structure:

Arc Extinguishing Chamber: Adopts multi-stage arc extinguishing technology to quickly extinguish arcs and protect equipment safety

Thermal-magnetic Release: Composed of thermal elements (bimetallic strips) and electromagnetic elements (coils), which detect overload and short-circuit currents respectively

  1. Scénarios d'application typiques
  2. Industrial Power Distribution Systems:

Main switch of power distribution boxes in factory workshops

Power supply protection for large-scale equipment (par ex., motors, fans, water pumps)

  1. Commercial Buildings:

Floor power distribution boxes in shopping malls and office buildings

Power supply protection for large electrical equipment such as air conditioning systems and elevators

  1. Infrastructure Facilities:

Power distribution systems in public buildings like hospitals and schools

UPS output protection in data centers

  1. Précautions d'utilisation
  2. Exigences d'installation:

Install vertically and reserve sufficient heat dissipation space (≥10cm)

Install arc baffles (configuration standard) to prevent phase-to-phase short circuits

Ensure the conductor cross-sectional area is ≥400mm² (for copper busbars) or ≥370mm² (for copper wires) during wiring

  1. Operation and Maintenance:

Regularly check for overheating and deformation of contacts

Clean internal dust every six months (operate after power-off)

Periodically test protection functions with professional testing equipment

  1. Safety Tips:

Inspect contact conditions after interrupting fault currents; replace if necessary

Strictly prohibit wiring or replacement operations under load conditions

Confirm that the circuit is completely de-energized before conducting maintenance after the circuit breaker is opened

  1. Optional Accessories for Function Expansion

The functions of the NM1-400S/3000 circuit breaker can be expanded by installing accessories:

Accessory TypeFunction Expansion
Auxiliary ContactsProvide circuit breaker status signals (open/closed) for remote monitoring
Alarm ContactsSend alarm signals when the circuit breaker trips due to faults
Shunt ReleaseEnable remote control of circuit breaker opening (par ex., for fire protection linkage)
Undervoltage ReleaseAutomatically trip when the power supply voltage drops below the set value
Electric Operating MechanismRealize electric closing/opening, suitable for remote control or frequent operation scenarios

The NM1-400S/3000 400A is a reliable 3-pole molded case circuit breaker with a high breaking capacity of 50kA and thermal-magnetic release protection. It is suitable for various industrial and commercial power distribution systems. Its standard configuration (without accessories) meets basic protection needs, and it can achieve function expansion by selecting different accessories to satisfy more complex system protection and monitoring requirements.

Précédent:

Suivant:

Laisser une réponse

Laisser un message