Comprehensive Analysis of Schneider C16F2TM160 Disjoncteur
Paramètres de base
Type de produit: ComPacT NSX160F Series Molded Case Circuit Breaker (MCCB)
Frame Current: 160UN (Frame Rating)
Tension nominale: 690V et (Operating Voltage), 415V et (Breaking Capacity Test Voltage)
Capacité de coupure: 18le (415V et, 50/60HZ) Note: Different from the 36kA of 3-pole models
Configuration des poteaux: 2P. (2 Poles) Note: Not 4 poles
Trip Unit: TMD Thermal-Magnetic Type (Thermal Overload + Magnetic Short-Circuit Protection), Rated Current 160A
Applicable System: CA/CC (Universal for Alternating Current and Direct Current)
Detailed Model Coding
C16F2TM160:
C: ComPacT Series
16: Frame Current 160A
F: Breaking Capacity Class (F=18kA, corresponding to F=36kA for 3-pole models)
2: Configuration des poteaux (2P.)
TM: Trip Unit Type (TMD Thermal-Magnetic Type)
160: Rated Current 160A
Detailed Technical Parameters
| Paramètre | Valeur |
| Tension d'isolation nominale | 800V et |
| Durée de vie électrique | 40,000 Operating Cycles (440V et) |
| Durée de vie mécanique | 100,000 Operating Cycles |
| Température de fonctionnement | -5℃ ~ +70℃ (Modèle standard) |
| Protection Degree | IP20 (Front Side) |
| Méthode de montage | Fixed Mounting |
| Compliant Standards | CEI 60947-2, CEI 60898-1 |
Fonctionnalités principales
1. Conception compacte: Saves space in distribution cabinets and improves installation efficiency
2. Dual Protection: TMD thermal-magnetic trip unit provides overload and short-circuit protection
3. AC/DC Universality: Suitable for various power system environments
4. Haute fiabilité: Robust structure with resistance to vibration and impact
5. Easy Maintenance: Front-panel operation for convenient inspection, repair and replacement
Characteristics of TMD Trip Unit
Protection thermique: Bimetallic strip senses overload current, with inverse time-delay characteristic
Protection magnétique: Electromagnetic coil detects short-circuit current, with instantaneous action
Fixed Protection Characteristics: Preset at the factory, no on-site adjustment required
No Communication Function: Only provides basic protection, without fault indication and remote monitoring capabilities
Scénarios d'application
Bâtiments commerciaux: Protection for single-phase 220V/240V power distribution systems such as lighting and air conditioning
Équipement industriel: Power protection for single-phase motors and small production lines
Infrastructure: Single-phase power supply circuits in places like hospitals and schools
Residential Distribution Boxes: Branch protection for high-end residences (par ex., climatiseurs, chauffe-eau, etc.)
DC Systems: DC power protection for some industrial automation and communication equipment
Comparison with Other Models in the NSX160F Series
| Modèle | Configuration des poteaux | Capacité de coupure (le) | Trip Unit Type | Scénario d'application |
| C16F2TM160 | 2P. | 18 | TMD | Single-phase system protection |
| C16F3TM160 | 3P. | 36 | TMD | Three-phase system protection |
| C16F4TM160 | 4P. | 36 | TMD | Three-phase four-wire system protection |
| C16F42D160 | 4P. | 36 | Micrologic 2.2 | Systems requiring intelligent protection and communication functions |
Précautions
Discontinued and Obsolete: Together with the entire NSX160F Series, production was discontinued at the end of 2022, and service support was terminated at the end of 2023
Replacement Models: It is recommended to consider the latest upgraded products of Schneider’s NSX Series (par ex., NSX2 Series)
Canaux d'achat: Most products available on the market currently are stock items; please confirm the product status and quality assurance when purchasing
Résumé
Schneider C16F2TM160 is a 2-pole thermal-magnetic molded case circuit breaker with a breaking capacity of 18kA, specifically designed for single-phase or DC systems, and features a compact and reliable structure.
Contacteur,disjoncteur,onduleur solaire,compteur électrique,batteries solaires


















NH42-63-318x560.png)