Spécifications techniques & Application Guide
This is a 2‑pole, Tapez C, 25UN disjoncteur miniature (MCB) de la série Acti9 de Schneider Electric, with order code A9F18225 and rated breaking capacity 6kA.
It provides overload and short‑circuit protection for lighting, socket, and small motor circuits in AC distribution systems.
Features include 3‑stage current limiting, quick make mechanism, and protection degree IP40 (front) / IP20 (bornes).
It is compatible with iC65 series accessories for functional expansion.
- Model Breakdown
| Code | Signification | Description |
| SCHNEIDER | Marque | Schneider Électrique (France), global electrical equipment manufacturer |
| iC65N | Série | Acti9 iC65 MCB, N‑type breaking capacity (6le) |
| 2P. | Nombre de pôles | 2‑pole, breaks phase and neutral simultaneously, for 230V/400V systems |
| C | Courbe de déclenchement | Tapez C, instantaneous tripping at 5~10×In (5In~10In) |
| 25UN | Courant nominal | 25 amperes continuous at 30°C ambient |
| A9F18225 | Full order code | Official unique identifier |
- Spécifications de base
| Article | Spécification | Remarques |
| Basic | ||
| Taper | Miniature Circuit Breaker (MCB) | Conforme à la CEI 60898-1 / FR 10963.1 |
| Tripping type | Thermique-magnétique | Surcharge (thermal) + short‑circuit (magnetic) protection |
| Pouvoir de coupure | 6le | Max breaking current at rated voltage |
| Rated operational voltage | C.A. 230 V/400 V | For 2‑pole version |
| Tension d'isolement nominale | 500V | Max withstand voltage of insulation |
| Rated impulse withstand voltage | 6kV | Surge voltage immunity |
| Fréquence nominale | 50/60Hz | Global grid compatible |
| Caractéristiques de déclenchement | ||
| Protection contre les surcharges | 1.13Dans (no trip in 1h), 1.45Dans (trip within 1h) | Meets IEC requirements |
| Short‑circuit protection | Instantaneous at 5In~10In | Tapez C, adapté à l'éclairage, charges résistives, petits moteurs |
| Physical & environmental | ||
| Dimensions (L×H×P) | 18mm×86mm×62mm | Standard modular, 2P = 2 modules (18mm/pole) |
| Protection degree | IP40 (front), IP20 (bornes) | Solid object and moisture protection |
| Température de fonctionnement | -35°C ~ +70°C | Suitable for harsh industrial environments |
| Montage | 35mm rail DIN | Standard panel mounting |
| Certifications | CCC, CE, RoHS | Meets Chinese and international safety & environmental standards |
- Caractéristiques
- Protection performance
3‑stage current limiting: Quickly limits peak current during short circuit, reduces thermal stress, protects equipment and cables.
Selective protection: Coordinates with upstream breakers for selective tripping, limits fault area.
Fault indication: Red window shows tripped status for quick diagnosis.
- Structural advantages
Dual‑lock clip: Secures firmly on DIN rail, prevents vibration loosening.
Quick make mechanism: Improves closing speed, reduces arcing, extends life.
Conception modulaire: Accepts auxiliary contacts, alarm contacts, voyage de dérivation, undervoltage trip, etc..
- Safety design
Fonction d'isolement: Safe isolation distance in OFF position, meets electrical safety rules.
Anti‑misoperation: Handle design prevents accidental closing.
Flame‑retardant housing: V0 grade material improves cabinet safety.
- Installation & Entretien
Installation Rules
- Mount vertically (±15°) for proper tripping.
- Câblage: Copper 1.5~35mm², Aluminium 2.5~35mm², torque 1.2~4N·m (depends on cross‑section).
- Environnement: Avoid damp, poussiéreux, corrosive or high‑vibration locations.
- Spacing: Maintain clearance for heat dissipation; follow installation manual.
Maintenance Guide
| Article | Interval | Criterion | Solution |
| Visual inspection | Monthly | No damage, no overheating, tight connections | Clean, tighten loose terminals |
| Function test | Quarterly | Manual ON/OFF smooth, no sticking | Operate 3–5 times, check mechanism |
| Trip test | Annually | Surcharge & short‑circuit protection functional | Test with dedicated equipment or simulate overload |
| Accessory check | Annually | Auxiliary & alarm contacts working | Check contact condition, replace damaged parts |
Troubleshooting
- Déclenchements fréquents: Check overload → short circuit → high ambient temperature → aging.
- Cannot close: Check short circuit → handle position → trip reset → loose wiring.
- Overheating: Check terminal torque → overload → ventilation.
- Mise à niveau & Remplacement
5.1 Same‑series Upgrades
iC65H-2P-C25A (A9F28225): H‑type, 10le, for higher short‑circuit current.
iC65L-2P-C25A (A9F38225): L‑type, 15le, for heavy industrial use.
iC65N-2P-C25A‑Vigi (A9V58225): With residual current protection (RCCB), prevents electric shock.
5.2 Functional Accessories
| Accessoire | Modèle typique | Fonction |
| Contact auxiliaire | A9A26924 | 1NON+1NC, remote status indication |
| Shunt trip | A9X16224 | Remote tripping, par ex., fire alarm |
| Undervoltage trip | A9X16624 | Auto‑trip on low voltage |
| Alarm contact | A9A27924 | Signal when breaker trips |
5.3 Cross‑series Alternatives
| Série | Remplacement | Compatibilité |
| Easy9 | EA9AN 2P C25A | Mêmes dimensions, 6le, economical |
| Acti9 CVS | CVS100B 2P C25A | MCCB, pouvoir de coupure plus élevé (10le), main circuit use |
| Merlin Gerin | C65N 2P C25A | Fully compatible with iC65 |
- Applications
- Commercial buildings: Offices, shops, hotels – lighting & circuits de prise.
- Automatisation industrielle: Control panels, petits moteurs (≤5.5kW), VFD input protection.
- Résidentiel: Home distribution – air conditioners, kitchen appliances.
- Public facilities: Schools, hospitals, stadiums – electrical safety.
- Sélection & Purchasing Tips
- Correspondance de charge: Type C for lighting, prises, petits moteurs (≤5.5kW). Use Type B for pure resistive, Type D for large motors.
- Pouvoir de coupure: Choose N (6le), H (10le), L (15le) based on system short‑circuit current.
- Poteaux: 2P for 230V single‑phase where phase + neutral must be disconnected.
- Accessories: Add aux, shunter, undervoltage for smart systems.
- Authenticity: Buy from authorized Schneider distributors.
- Quick Fault Guide
| Symptom | Cause possible | Solution |
| Trips immediately after closing | Short circuit / surcharge | Locate short, reduce load or upsize breaker |
| Trips after running a while | Surcharge / haute température | Reduce load, improve ventilation, check cable size |
| Handle cannot be pushed to ON | Not reset / wiring fault | Pull to OFF first, then ON; check circuit |
| Terminal overheating | Loose connection | Retorque after power off, check terminals |
| No operation | Thermal‑magnetic unit failed | Replace MCB, check coordination |
SCHNEIDER iC65N-2P-C25A
Cross‑Brand Replacement Guide
Core Summary: The iC65N-2P-C25A (A9F18225) can be directly replaced by equivalent MCBs from major international and domestic brands.
Key matching requirements:
2P., Tapez C, 25UN, 6le, 35mm DIN rail mounting.
- International Brand Direct Replacements
ABB
| Remplacement | Code de commande | Breaking | Compatibilité |
| S202-C25 | 2CDS252001R0254 | 6le | Best match, same dimensions, direct swap |
| S202M-C25 | 2CDS262001R0254 | 10le | Higher breaking capacity |
| S202L-C25 | 2CDS242701R0254 | 4.5le | Economy option |
Siemens
| Remplacement | Série | Breaking | Compatibilité |
| 5SL6225-7 | 5SL | 6le | Remplacement direct, CEI 60898-1 |
| 5SY6225-7 | 5SY | 6le | Economy range |
| 5SN6225-7CN | 5SN | 6le | Classic, fiable |
Eaton
| Remplacement | Série | Breaking | Compatibilité |
| FAZ6-C25/2 | FAZ | 6le | Mêmes dimensions & mounting |
| PL9-C25/2 | PL9 | 6le | High performance, fast limiting |
Moeller
| Remplacement | Série | Breaking | Compatibilité |
| FAZ6-C25/2 | FAZ | 6le | Mêmes dimensions & mounting |
| PL9-C25/2 | PL9 | 6le | High performance, fast limiting |
- Chinese Domestic Brands
| Marque | Remplacement | Breaking | Compatibilité |
| CHINT | NXB-63-2P C25 | 6le | Cost‑effective, direct fit |
| DÉLIXI | CDM3-63C25/2P | 6le | Mêmes dimensions |
| Liangxin | NDM1-63C25/2P | 6le | High quality domestic |
| DROITE | TGM1-63C25/2P | 6le | Protection de base, economical |
- Critical Parameter Matching
| Article | Original (iC65N-2P-C25A) | Doit correspondre | Réglable | Remarques |
| Poteaux | 2P. | 2P. | – | Disconnect phase + neutral |
| Curve | Tapez C (5~ 10 pouces) | Tapez C | – | For lighting & petits moteurs |
| Current | 25UN | 25UN | – | Continuous rating |
| Breaking | 6le | ≥6kA | Can be higher (10le) | Ensure safe short‑circuit interruption |
| Montage | 35mm rail DIN | 35mm rail DIN | – | Standard panel mount |
| Width | 18mm | 18mm | H/D may vary | Fits standard spacing |
| Voltage | C.A. 230 V/400 V | C.A. 230 V/400 V | – | Universal AC system |
- Notes de remplacement & Best Practice
Before Replacement
System short‑circuit current ≤ breaking capacity of replacement.
35mm rail DIN, space, terminal size compatible.
Protection coordination with upstream/downstream devices.
Accessory mounting interface compatible.
Replacement has valid certifications (CCC, CE).
Procedure
- Power off and verify voltage absence.
- Remove wiring and old breaker.
- Clip replacement onto DIN rail.
- Torque terminals correctly.
- Test ON/OFF and tripping.
- Update labeling and drawings.
When NOT to replace
Original uses dedicated Schneider accessories (par ex., Vigi modules).
System short‑circuit current exceeds replacement rating.
Load inrush >10Dans (unsuitable for Type C).
Extreme environment outside replacement specs.
- Recommended Replacement Levels
| Niveau | Modèles recommandés | Application | Advantage |
| 1st | ABB S202-C25 | Industrie, commerce | Full performance, global support |
| Siemens 5SL6225-7 | |||
| 2nd | Eaton FAZ6-C25/2 | Control panels | Good value, easy install |
| Moeller DIL M9-25 C/2 | |||
| 3rd | CHINT NXB-63-2P C25 | Résidentiel, economy | Low cost, fast local supply |
| DELIXI CDM3-63C25/2P |
- Common Issues & Solutions
| Issue | Cause | Solution |
| Frequent tripping after replacement | Wrong curve / surcharge | Confirm Type C, check load, upsize if needed |
| Will not fit | Wrong rail / largeur | Use 35mm DIN rail, 18mm width model |
| Wiring difficult | Incompatible terminals | Use suitable lugs or select compatible model |
| Insufficient breaking capacity | Remplacement < system short鈥慶ircuit current | Use higher version (par ex., ABB S202M-C25, 10le) |
Cross‑brand replacement for SCHNEIDER iC65N-2P-C25A depends on parameter matching + mechanical compatibility + protection coordination.
Top international brands (ABB, Siemens) give identical performance.
Domestic brands (CHINT, DÉLIXI) offer cost savings.
Always verify specifications and follow electrical safety standards.
Contacteur,disjoncteur,onduleur solaire,compteur électrique,batteries solaires




















NH42-63-318x560.png)