Schneider MT08N1 3P 800A is a fixed 3-pole intelligent disjoncteur pneumatique (ACB) belonging to the Masterpact MT series. It has a frame current and rated current of 800A, with an N1-class breaking capacity (50kA@400V). Suitable for incoming line/bus tie protection and power distribution in power distribution systems, it is commonly used in primary/secondary power distribution of industrial plants, large buildings and data centers. Below are the complete specifications and core details:
Paramètres techniques de base
| Item | Paramètre | Remarks |
| Modèle | MT08N1 3P 800A (Order Code: MT08N1) | MT series; 08=800A frame; N1=50kA breaking capacity |
| Série | Masterpact MT (Air Circuit Breaker) | Intelligent type, zero arcing, compatible with Micrologic control units |
| Numéro de pôle | 3P. | Three-phase power distribution, no neutral protection (4P optional) |
| Courant nominal (In) | 800UN (at 40℃) | Long-term continuous current-carrying capacity |
| Frame Current (Iu) | 800UN | Maximum current adaptable to the breaker body |
| Rated Operational Voltage (Ue) | 690V AC 50/60Hz | Insulation Voltage (Ui) = 1000V |
| Short-circuit Breaking Capacity (ICU) | 50le (400V et) | N1 class, compliant with IEC 60947-2 |
| Short-time Withstand Current (Icw) | 42kA/1s (400V) | Ability to withstand short-circuit impact |
| Making Capacity (Icm) | 105le (440V et) | Ability to close short-circuit current |
| Impulse Withstand Voltage (Uimp) | 12kV | Strong surge resistance |
| Control Unit | Compatible with Micrologic 2.0/5.0/6.0, etc.. | Long-time delay/short-time delay/instantaneous/earth fault protection |
| Méthode de montage | Fixé (F) / Drawout (D) | Standard dimensions for fixed 3P model: 301×276×196mm |
| Méthode de câblage | Front/back panel screw clamping terminals | Suitable for top/bottom cable entry |
| Operation Method | Electric + manual (for maintenance) | Equipped with closing/opening buttons and status indicators |
| Mechanical/Electrical Service Life | 10,000 mechanical operations; 2,000 electrical operations (AC-3) | High durability |
| Certifications | CCC, IEC, UL, CSA, EAC | Green Premium compliant |
Fonctions principales & Protection Features
- Full Intelligent Protection: Realizes long-time delay (surcharge), short-time delay (short circuit), instantaneous (heavy short circuit) and earth fault protection via the Micrologic control unit. Parameters can be precisely set to adapt to cascade coordination in multi-level power distribution systems.
- Measurement & Monitoring: Displays real-time electrical parameters such as current, voltage and power, with fault memory and alarm output functions. Supports Modbus and other communication protocols, and can be integrated into SCADA systems.
- Zero Arcing Design: Optimized arc extinguishing chamber with zero arcing distance, improving cabinet safety and space utilization.
- Fonction d'isolement: Compliant with IEC 60947-2, can be used as an isolating switch (without controller).
Scénarios d'application & Selection Key Points
– Scénarios typiques: Primary/secondary power distribution links such as incoming line cabinets of industrial plants, power distribution of large buildings, UPS output of data centers, photovoltaic/energy storage combiner boxes, etc.. It is used for power distribution and short-circuit, surcharge, earth fault protection of lines/equipment.
– Key Selection Tips:
– Control Unit: 2.0 for basic protection; 5.0/6.0 with added measurement and communication functions, select according to requirements.
– Mounting Type: Fixed type is cost-effective; drawout type facilitates maintenance and allows breaker replacement without power outage.
– Capacité de coupure: N1 (50le) meets general power distribution needs; upgrade to N2/H1/H2 class if short-circuit current is high.
Procurement & Replacement Recommendations
- Complete Order Specification: Must specify MT08N1 + control unit model + mounting method + numéro de pôle, par ex., MT08N1 F MIC 2.0 3P..
- Replacement Compatibility: Can directly replace MT08N2/H1 and other models with the same frame size. Dimensions differ from the NW series; verify cabinet installation space before replacement.
- Price Reference (December 2025): Domestic fixed type with MIC 2.0 control unit is approximately RMB 14,500-16,000 per unit; drawout type is priced higher.
Breaking Capacity Comparison Table of Schneider Masterpact MT08 Series (800UN)
| Item | MT08N1 3P 800A | MT08N2 3P 800A | MT08H1 3P 800A | MT08H2 3P 800A | Remarks |
| Breaking Capacity Class | N1 | N2 | H1 | H2 | N=Standard type; H=High breaking type |
| Rated Ultimate Short-circuit Breaking Capacity (ICU) @400V AC | 50le | 70le | 100le | 150le | Compliant with IEC 60947-2 |
| Rated Service Short-circuit Breaking Capacity (Ics) @400V AC | 50le (100% ICU) | 70le (100% ICU) | 100le (100% ICU) | 150le (100% ICU) | Can carry rated current continuously after breaking |
| Short-time Withstand Current (Icw) @400V AC/1s | 42le | 50le | 85le | 120le | Ability to withstand short-circuit impact |
| Making Capacity (Icm) @440V AC | 105le | 147le | 210le | 315le | Ability to close short-circuit current |
| Rated Operational Voltage (Ue) | 690V et | 690V et | 690V et | 690V et | Insulation Voltage (Ui) = 1000V |
| Courant nominal (In) | 800UN (at 40℃) | 800UN (at 40℃) | 800UN (at 40℃) | 800UN (at 40℃) | Frame Current (Iu) = 800A |
| Optional Pole Number | 3P/4P | 3P/4P | 3P/4P | 3P/4P | 4P with neutral protection |
| Méthode de montage | Fixed/Drawout | Fixed/Drawout | Fixed/Drawout | Fixed/Drawout | Drawout type requires additional chassis |
| Compatible Control Units | Micrologic 2.0/5.0/6.0/7.0 | Micrologic 2.0/5.0/6.0/7.0 | Micrologic 2.0/5.0/6.0/7.0 | Micrologic 2.0/5.0/6.0/7.0 | 7.0 is a high-end measurement and control unit, supporting power quality analysis |
| Dimensions (Fixed 3P, L×H×P) | 301×276×196mm | 301×276×196mm | 301×276×210mm | 301×276×225mm | High breaking types have slightly increased depth due to optimized arc extinguishing chambers |
| Mechanical Service Life | 10,000 opérations | 10,000 opérations | 10,000 opérations | 10,000 opérations | Electrical service life: 2,000 opérations (AC-3) |
| Price Reference (December 2025, Fixed Type + Micrologic 2.0) | RMB 14,500-16,000/unit | RMB 17,000-19,000/unit | RMB 22,000-25,000/unit | RMB 28,000-32,000/unit | Drawout type: 30%-40% price increase; imported model: about 50% price increase |
| Scénarios d'application typiques | General industrial plants, incoming line/bus tie of building power distribution | Medium-voltage distribution outgoing terminals, industrial scenarios with high short-circuit current | Heavy industrial plants, data centers, photovoltaic/energy storage combiner systems | Power grids with high short-circuit current, supporting large generator sets | Select according to grid short-circuit current level |
Complete Order Code Examples & Stocking Recommendations
- Complete Order Code Specification (4 Core Elements Required)
Ordering Schneider MT series requires specifying frame size + breaking capacity class + mounting method + control unit + numéro de pôle. Examples are as follows:
– MT08N1 F MIC 2.0 3P.: 800A N1 class, fixed type, Micrologic 2.0 control unit, 3-pole
– MT08H1 D MIC 5.0 4P.: 800A H1 class, drawout type, Micrologic 5.0 control unit, 4-pole
- Stocking & Recommandations de sélection
- Select by Short-circuit Current
– First calculate the expected short-circuit current at the distribution point: choose N1 class (highest cost-performance) if ≤50kA; N2 class if 50-70kA; H1/H2 class if >70le.
– For industrial plants close to substations with high short-circuit current, prioritize H1 class.
- Select by Operation & Maintenance Requirements
– Choose fixed type for general power distribution scenarios, featuring low cost and small space occupation;
– Choose drawout type for scenarios where power outage for maintenance is not allowed (par ex., data centers, hospitals), enabling live replacement of the breaker body.
- Select by Functional Requirements
| Control Unit Model | Fonctions principales | Scénarios applicables |
| Micrologic 2.0 | Protection de base (long-time delay/short-time delay/instantaneous) | General power distribution without measurement and control requirements |
| Micrologic 5.0 | Protection + electrical parameter measurement (current/voltage/power) | Buildings and factories requiring energy consumption monitoring |
| Micrologic 6.0 | Protection + measurement + communication (Modbus/Profibus) | Intelligent power distribution systems requiring SCADA integration |
| Micrologic 7.0 | Full functions + power quality analysis (harmonics/unbalance) | Data centers, precision manufacturing workshops |
- Stocking Recommendations
– For regular trade stocking, prioritize MT08N1 F MIC 2.0 3P., which adapts to 80% of general power distribution scenarios and ensures fast inventory turnover;
– For heavy industry customers, stock a small quantity of MT08H1 F MIC 5.0 3P to meet high short-circuit current requirements;
– Customize drawout models on demand; large-scale stocking is not recommended (high capital occupation and strong model specificity).
Core Parameter Comparison Table: Schneider MT08 Series vs. Chint NA8G-800 Series
(Both are 800A frame, 3-pole, fixed type, basic protection type, suitable for general power distribution scenarios)
| Comparison Item | Schneider MT08N1 3P 800A (Micrologic 2.0) | Chint NA8G-800-3P-800A (Basic Trip Unit) | Core Difference Summary |
| Product Series Positioning | Masterpact MT series intelligent air circuit breaker | NA8G series air circuit breaker | Schneider focuses on intelligent measurement & control + high reliability; Chint focuses on high cost-performance + localized adaptation |
| Rated Ultimate Short-circuit Breaking Capacity (ICU) @400V | 50le | 40le | Schneider’s breaking capacity is 25% higher, suitable for scenarios with high short-circuit current |
| Rated Service Short-circuit Breaking Capacity (Ics) @400V | 50le (100% ICU) | 40le (100% ICU) | Both support continuous operation after breaking; Schneider has higher redundancy |
| Short-time Withstand Current (Icw) @400V/1s | 42le | 31.5le | Schneider has stronger short-circuit impact resistance, suitable for heavy-duty industrial scenarios |
| Fonctions de protection | Long-time delay/short-time delay/instantaneous three-stage protection; expandable earth fault protection | Long-time delay/short-time delay/instantaneous three-stage protection; earth fault protection requires customization | Basic protection is consistent; Schneider offers more flexible expansion functions |
| Measurement & Control Capability | Supports electrical parameter display (current/voltage); can be equipped with communication modules for SCADA integration | Basic protection only, no measurement and control functions; measurement supported only by upgraded models (NA8G-800M) | Schneider has higher intelligence level, suitable for intelligent power distribution needs |
| Méthode de montage | Fixed/drawout optional; drawout type with standard mechanical interlock | Fixed/drawout optional; drawout interlock is optional | Similar structural design; Schneider’s standard interlock offers higher safety |
| Dimensions (Fixed 3P, W脳H脳D) | 301脳276脳196mm | 320脳285脳210mm | Schneider is more compact, saving cabinet space |
| Mechanical/Electrical Service Life | 10,000 mechanical operations; 2,000 electrical operations (AC-3) | 8,000 mechanical operations; 1,500 electrical operations (AC-3) | Schneider has better durability, suitable for high-frequency operation scenarios |
| Normes de certification | CCC, IEC, UL, CSA, EAC | CCC, IEC | Schneider has broader certification coverage, suitable for export projects |
| Price Reference (December 2025, Fixed Type) | RMB 14,500-16,000/unit | RMB 6,500-7,500/unit | Chint’s price is about 45%-50% of Schneider’s, with outstanding cost-performance |
| Scénarios d'application typiques | Industrial plant incoming lines, data centers, high-end buildings, export projects | Civil building power distribution, small and medium-sized factories, localized power distribution renovation projects | Select according to project budget and reliability requirements |
| After-sales Service | Nationwide warranty, extensive overseas network; spare parts supply cycle: about 7 jours | Nationwide warranty, fast localized service response; spare parts supply cycle: about 3 jours | Chint’s after-sales service is more suitable for domestic small and medium-sized customers |
Selection Decision Recommendations
- Scenarios for Prioritizing Schneider MT08 Series
– Export projects (par ex., overseas markets such as Algeria), power distribution projects requiring international certifications;
– Scenarios with high requirements for short-circuit breaking capacity and reliability, such as data centers and heavy industrial plants;
– Intelligent power distribution systems requiring energy consumption monitoring and remote control.
- Scenarios for Prioritizing Chint NA8G-800 Series
– Domestic civil buildings, small and medium-sized factories and other general power distribution scenarios with limited budgets;
– Localized renovation projects requiring fast delivery and after-sales response;
– Power distribution circuits with only basic short-circuit and overload protection needs, no intelligence requirements.
- Replacement Compatibility Notes
– The two series have slightly different mounting dimensions; verify cabinet installation space before replacement;