Schneider A9DA2616

Schneider A9DA2616 (Acti9 Idd40t 1p+N C16 30mA et) Disjoncteur à courant résiduel with Overcurrent Protection (RCBO)

  1. Model Interpretation

A9DA2616 = Acti9 Series iDD40T Product Type 1P+N Pole Configuration C-type Tripping Curve 16A Rated Current 30mA Residual Current AC-type Residual Current Detection

  1. Paramètres techniques de base (Compliant with IEC 61009-1/GB 16917.1)
ParamètreSpécification
Type de produitResidual Current Operated Circuit Breaker with Overcurrent Protection (RCBO, integrating three protections: surcharge, short-circuit, and residual current)
Configuration des poteaux1P+N (1 Pole + Neutral, phase line breaks, neutral line remains conducting permanently)
Courant nominal (In)16UN
Courbe de déclenchementC-type (instantaneous tripping at 5~10 In), adapté à l'éclairage, socket, and general motor loads
Courant de fonctionnement résiduel nominal (JeΔn)30mA (personal safety protection level)
Residual Current TypeAC-type (detects sinusoidal AC leakage current, suitable for conventional environments)
Tension nominale (Ue)230V et (1P+N), 50/60HZ
Short-circuit Breaking Capacity (Icn)6le (400V) / 4500UN (230V)
Rated Residual Operating Time (at IΔn)≤0.3s
Durée de vie mécanique10,000 opérations
Electrical Service Life5,000 opérations
Méthode de montage35mm rail DIN (18mm largeur)
Wiring SpecificationSolid wire: 1~25 mm²; Flexible wire: 1~16 mm² (with cable lugs)
Terminal Torque2.0 N·m
Température de fonctionnement-25℃ ~ +70℃
Classe de protectionIP20 (for use inside distribution boxes)
Tension de tenue aux impulsions nominale (Ump)4kV
  1. Functions & Applications

Fonctions principales

Protection contre les surcharges: Realizes inverse-time protection via the thermal bending of bimetallic strips.

Short-circuit Protection: Achieves instantaneous protection through electromagnetic release.

Residual Current Protection: Rapidly trips within ≤0.3s when detected residual current exceeds 30mA, preventing electric shock accidents.

Scénarios d'application typiques

  1. Branch circuit protection for residential/commercial buildings (par ex., lighting and socket circuits)
  2. Electrical safety protection for crowded places such as offices and shops
  3. Power supply protection for small household appliances and office equipment
  4. Replacement for traditional MCB + RCCB combinations, saving distribution box space

Conseils de sélection

AC-type is suitable for pure AC load environments, such as traditional lighting and resistive loads.

For loads containing DC components (par ex., switching power supplies, LED lighting), A-type or B-type residual current circuit breakers are recommended.

30mA is the standard value for personal safety protection and shall not be used for equipment protection (300mA is usually selected for equipment protection).

  1. Installation & Points clés de l'entretien
  2. Spécifications de câblage: Top-in bottom-out (bidirectional wiring with bottom-in top-out supported). Connect phase line to L pole and neutral line to N pole; reverse connection is strictly prohibited.
  3. Residual Current Test: Après l'installation, press the test button (T button) to confirm the normal operation of the residual current protection function.
  4. Inspection régulière: Press the test button once a quarter to verify the effectiveness of the residual current protection function.
  5. Fault Handling:

Overload/Short-circuit Tripping: Troubleshoot load or line faults before closing the breaker directly.

Residual Current Tripping: First disconnect all loads, check for leakage points one by one, and close the breaker only after repairs; forced closing with faults is strictly prohibited.

  1. Spacing Requirement: Maintain a gap of ≥3mm from adjacent components to ensure heat dissipation and wiring space.
  2. Corresponding Chint Product & Replacement Comparison

Chint Equivalent Model: NXBLE-63 1P+N C16 30mA AC

Catégorie de paramètreSchneider A9DA2616Chint NXBLE-63 1P+N C16 30mAReplacement Compatibility
Core ProtectionSurcharge + Short-circuit + Residual Current (RCBO)Surcharge + Short-circuit + Residual Current (RCBO)✅ Fully Matched
Pole Configuration/Tripping Curve/In1P+N/C-type/16A1P+N/C-type/16A✅ Fully Matched
IΔn/IΔ Type30mA/AC30mA/AC✅ Fully Matched
Capacité de coupure6le6le✅ Fully Matched
Dimensions d'installation18mm (largeur) × 91mm (height) × 65mm (depth)18mm (largeur) × 91mm (height) × 65mm (depth)✅ Identical Dimensions
Wiring SpecificationSolid wire: 1~25 mm²Solid wire: 10~16 mm²⚠️ Schneider Terminals Have Larger Capacity
Température de fonctionnement-25℃ ~ +70℃-30℃ ~ +70℃✅ Chint Has Better Low-temperature Adaptability
Additional FunctionsVisiTrip Fault IndicationRed-Green Window Indication (Red for Closed, Green for Open)⚠️ Different Indication Methods
Période de garantie24 Months18 Months⚠️ Warranty Difference

Key Replacement Precautions

  1. ✅ Installation Compatibility: Both are mounted on 35mm DIN rails with 18mm width, enabling direct interchange.
  2. ✅ Protection Characteristics: C-type curve, 16A rated current, and 30mA residual current protection are fully consistent; no load adjustment is required.
  3. ⚠️ Wiring Adaptation: Schneider terminals support larger wire diameters; keep the original wire diameter during replacement to avoid loose connections.
  4. ⚠️ Function Identification: The VisiTrip indication window of Schneider shows red after tripping; it is necessary to train operators to recognize the new marks.
  5. Résumé & Recommandations de sélection

Schneider A9DA2616 is a 1P+N 16A RCBO in the Acti9 series iDD40T product line. It integrates triple protection functions and is suitable for personal safety protection in conventional environments.

Recommandations de sélection:

For international brand reputation and reliable performance: Choose Schneider A9DA2616, which provides more comprehensive fault indication and bidirectional wiring functions.

For cost-effectiveness: Choose Chint NXBLE-63 1P+N C16 30mA, which features more favorable pricing and performance meeting national standards.

For special environments (par ex., low temperature < -25): Prioritize Chint products for their better low-temperature adaptability.