Schneider Electric MCB A9P52606

Schneider Electric A9P52606 is a disjoncteur miniature (MCB) of the Acti9 iC40 series, featuring 1P+N pole configuration, 6A rated current, and C-type tripping curve. It is designed for overload and short-circuit protection of conventional distribution circuits such as lighting and socket systems, with a rated breaking capacity of 6kA (IEC 60947‑2)/4.5le (EN 60898). It adopts DIN rail mounting and has an IP20 protection rating.

  1. Interprétation du modèle
ItemDetails
ModèleA9P52606
SérieActi9 iC40
TaperMiniature Circuit Breaker (MCB)
Configuration des poteaux1P+N (1 poteau de protection, N pole for switching only)
Courant nominal6UN
Courbe de déclenchementTapez C
Capacité de coupure6le (IEC 60947‑2), 4.5le (EN 60898‑1)
Méthode de montageDIN Rail
Indice de protectionIP20
  1. Paramètres techniques de base
ParamètreValeurStandard
Rated Operational Voltage (Ue)230V AC 50/60HzEN/IEC 60947‑2
Courant nominal (Dans)6UNEN/IEC 60947‑2
Tripping CharacteristicTapez C (instantaneous tripping at 5In‑10In)EN/IEC 60898‑1
Ultimate Breaking Capacity (ICU)6le (230V et)EN/IEC 60947‑2
Service Breaking Capacity (Icn)4.5le (230V et)EN/IEC 60898‑1
Tension de tenue aux impulsions nominale (Ump)4kVEN/IEC 60947‑2
Overvoltage CategoryEN/IEC 60947‑2
Pollution Degree3EN/IEC 60947‑2
Température de fonctionnement-25℃~70℃EN/IEC 60947‑2
Durée de vie électrique20,000 opérationsEN/IEC 60947‑2
Durée de vie mécanique20,000 opérationsEN/IEC 60947‑2
Dimensions (W×D×H)1 module (18mm) × 44mm × 91mmSchneider Electric Technical Manual
Neutral Pole PositionLeft SideSchneider Electric Technical Manual
Tripping Unit TypeThermal-magneticSchneider Electric Technical Manual
  1. Caractéristiques fonctionnelles
  2. 1P+N Design: Live wire protection plus synchronous neutral wire switching, suitable for single-phase distribution systems, with clear wiring and convenient maintenance.
  3. Type C Tripping Curve: Suitable for conventional loads such as lighting and sockets, balancing overload time-delay and short-circuit instantaneous tripping, with strong resistance to inrush current.
  4. Capacité de coupure élevée: 6le (IEC 60947‑2)/4.5le (EN 60898‑1), capable of handling severe short-circuit faults and ensuring distribution safety.
  5. Standard Mounting: DIN rail mounting with 1-module width, saving switchgear space, and compatible with Acti9 series accessories (par ex., contacts auxiliaires, alarm contacts).
  6. Adaptabilité environnementale: IP20 protection rating, resistant to temperatures ranging from -25℃ to 70℃, meeting the requirements of industrial and civil distribution environments.
  7. Champ d'application

Overload and short-circuit protection for single-phase distribution circuits of lighting, prises, petits moteurs, etc., in commercial buildings and industrial plants.

Places with high requirements for power supply reliability, such as office buildings, hôtels, and hospitals.

Compatible with Acti9 series distribution boxes, used in scenarios such as terminal power distribution and branch circuit protection.

  1. Recommandations de sélection
  2. Correspondance de charge: Type C curve is suitable for non-inductive loads (par ex., éclairage, prises); avoid selecting Type D (pour charges de puissance) or Type B (for electronic equipment) curves.
  3. Circuit Matching: With a rated current of 6A, it is suitable for 1.5mm² copper core cables (long-term current-carrying capacity ≥ 10A), and the circuit length should be ≤ 100m.
  4. Capacité de coupure: The 6kA breaking capacity is suitable for terminal distribution; the front-end should be equipped with molded case circuit breakers with higher breaking capacity (par ex., 15kA and above).
  5. Accessory Selection: According to monitoring requirements, select accessories such as auxiliary contacts (par ex., A9A26924) and alarm contacts (par ex., A9A26934).
  6. Troubleshooting
Phénomène de défautCauses possiblesTroubleshooting Methods
Déclenchements fréquentsSurcharge, line grounding/short-circuit, mismatched tripping curveCheck load current and insulation resistance; replace MCB with a matching tripping curve
Failure to CloseUnreset tripping mechanism, line short-circuit, ablation par contactManually reset the trip lever, locate the short-circuit point, replace damaged contacts
Excessive Temperature RiseCâblage lâche, contact oxidation, high ambient temperatureTighten wiring terminals, polish contacts, improve ventilation and heat dissipation
Insufficient Breaking CapacityLack of front-end protection, excessive short-circuit current in the lineUpgrade front-end protection, select MCB with higher breaking capacity
  1. Solutions alternatives

Intra-series Alternatives: A9P52610 (1P+N, 10UN, Tapez C), A9P52616 (1P+N, 16UN, Tapez C), etc., maintaining mounting and accessory compatibility.

Cross-series Alternatives: Schneider Electric IDPN series (par ex., A9D18606, 1P+N, 6UN, Tapez C) or ABB S200 series (par ex., S201M‑C6, 1P+N, 6UN, Tapez C). It is necessary to verify the matching of mounting dimensions and breaking capacity.

Complete Guide to Other Models of Schneider Electric Acti9 iC40 Series

Schneider Electric Acti9 iC40 series is a miniature circuit breaker (MCB) specially designed for single-phase/three-phase distribution systems. With 1P+N as the core product, it also provides multiple pole configurations including 2P, 3P., 4P., and 3P+N. The tripping curves cover Type B/C/D, and the breaking capacity is divided into standard type (4.5kA Icn/6kA Icu) and Type N (6kA Icn/10kA Icu), with rated current covering the full range of 1A~63A. The following is a structured and complete list of models:

  1. Model Naming Rules (A9PXXXXXX)
PositionCodeSignification
1-2A9Acti9 Series Identifier
3P.Exclusive Code for iC40 Series
42-4Capacité de coupure: 2 = Standard Type (4.5kA/6kA), 4 = Type N (6kA/10kA)
56/2/3/4/7Configuration des poteaux: 6 = 1P+N, 2 = 2P, 3 = 3P, 4 = 4P, 7 = 3P+N
6-701~63Courant nominal: 01 = 1A, 02 = 2A, 04 = 4A, 06 = 6A, 10 = 10A, 16 = 16A, 20 = 20A, 25 = 25A, 32 = 32A, 40 = 40A, 50 = 50A, 63 = 63A
Curve IdentifierB/C/D: Type B (3In-5In), Tapez C (5In-10In), Tapez D (10In-14In)
  1. Classified List of Full Series Models
  2. 1P+N (Most Commonly Used)
    Courbe de déclenchementCapacité de coupureCourant nominalModèle
    Type BModèle standard2A/4A/6A/10A/16A/20A/25A/32A/40AA9P22602/A9P22604/A9P22606/A9P22610/A9P22616/A9P22620/A9P22625/A9P22632/A9P22640
    Type N2A/4A/6A/10A/16A/20A/25A/32A/40AA9P42602/A9P42604/A9P42606/A9P42610/A9P42616/A9P42620/A9P42625/A9P42632/A9P42640
    Tapez CModèle standard2A/4A/6A/10A/16A/20A/25A/32A/40A/50A/63AA9P22602/A9P22604/A9P52606/A9P22610/A9P22616/A9P22620/A9P22625/A9P22632/A9P22640/A9P22650/A9P22663
    Type N2A/4A/6A/10A/16A/20A/25A/32A/40A/50A/63AA9P42602/A9P42604/A9P54606/A9P42610/A9P42616/A9P42620/A9P42625/A9P42632/A9P42640/A9P42650/A9P42663
    Tapez DModèle standard10A/16A/20A/25A/32A/40A/50A/63AA9P62610/A9P62616/A9P62620/A9P62625/A9P62632/A9P62640/A9P62650/A9P62663
    Type N10A/16A/20A/25A/32A/40A/50A/63AA9P64610/A9P64616/A9P64620/A9P64625/A9P64632/A9P64640/A9P64650/A9P64663

    2P. (Two-pole)

Courbe de déclenchementCapacité de coupureCourant nominalModèle
Tapez CModèle standard6A/10A/16A/20A/25A/32A/40AA9P52206/A9P52210/A9P52216/A9P52220/A9P52225/A9P52232/A9P52240
Type N6A/10A/16A/20A/25A/32A/40AA9P54206/A9P54210/A9P54216/A9P54220/A9P54225/A9P54232/A9P54240
Tapez DModèle standard16A/20A/32A/40AA9P62216/A9P62220/A9P62232/A9P62240
Type N16A/20A/32A/40AA9P64216/A9P64220/A9P64232/A9P64240
  1. 3P. (Three-pole)
Courbe de déclenchementCapacité de coupureCourant nominalModèle
Tapez CModèle standard6A/10A/16A/20A/25A/32A/40AA9P52306/A9P52310/A9P52316/A9P52320/A9P52325/A9P52332/A9P52340
Type N6A/10A/16A/20A/25A/32A/40AA9P54306/A9P54310/A9P54316/A9P54320/A9P54325/A9P54332/A9P54340
Tapez DModèle standard16A/20A/32A/40A/50AA9P62316/A9P62320/A9P62332/A9P62340/A9P62350
Type N16A/20A/32A/40A/50AA9P64316/A9P64320/A9P64332/A9P64340/A9P64350
  1. 4P. (Four-pole)
Courbe de déclenchementCapacité de coupureCourant nominalModèle
Tapez CModèle standard6A/10A/16A/20A/32A/40AA9P52406/A9P52410/A9P52416/A9P52420/A9P52432/A9P52440
Type N6A/10A/16A/20A/32A/40AA9P54406/A9P54410/A9P54416/A9P54420/A9P54432/A9P54440
  1. 3P+N (Three-pole + Neutral)
Courbe de déclenchementCapacité de coupureCourant nominalModèle
Tapez CModèle standard16A/20A/32A/40AA9P52716/A9P52720/A9P52732/A9P52740
Type N16A/20A/32A/40AA9P54716/A9P54720/A9P54732/A9P54740
Tapez DModèle standard20A/32A/40AA9P62720/A9P62732/A9P62740
Type N20A/32A/40AA9P64720/A9P64732/A9P64740
  1. Key Features and Selection Points
  2. Avantages principaux:

1P+N Design: Live wire protection plus synchronous neutral wire switching, suitable for 230V single-phase systems, saving installation space (1 module = 18mm).

Graded Breaking Capacity: Standard type is suitable for terminal distribution, while Type N is suitable for front-end circuits close to distribution transformers.

Tripping Curve Adaptability: Type B (for electronic equipment), Tapez C (for lighting/sockets), Tapez D (for motors/power loads).

  1. Comparison with the Original Model:

The model you queried: A9P52606: 1P+N, 6UN, Tapez C, standard breaking capacity (4.5kA/6kA).

Upgraded Type N version: A9P54606 (breaking capacity upgraded to 6kA/10kA).

Same current with different curves: A9P42606 (Type B), A9P62606 (Tapez D).

  1. Compatibilité des accessoires: The full series is compatible with Acti9 standard accessories, such as auxiliary contacts (A9A26924) and alarm contacts (A9A26934).
  2. Scénarios d'application typiques
Model ExampleScénario d'application
A9P52606 (1P+N, 6UN, Tapez C)Residential/commercial lighting circuits, sockets for small electronic devices
A9P54616 (1P+N, 16UN, Tapez C, Type N)Kitchen appliances, air conditioner sockets (requiring higher breaking capacity)
A9P64232 (2P., 32UN, Tapez D, Type N)Power equipment such as single-phase water pumps and compressors
A9P54340 (3P., 40UN, Tapez C, Type N)Industrial equipment such as three-phase fans and small air compressors

 