 Interchangeability Guide Between WATSNB-32-3 PC Class R-iINT Automatic Transfer Switch and Models of Other Brands

This document provides a complete intra-brand and cross-brand interchange solution for Schneider Wingoal WATSNB-32-3 PC Class, 3P, 32A, R-iINT Controller automatic transfer switch (ATS). It includes detailed interchange compatibility analysis, model comparison tables, and practical operation precautions to ensure seamless replacement and safe, reliable operation of the electrical system.

  1. Core Interchange Benchmark Parameters

The key parameters of WATSNB-32-3 determine that interchangeable products must meet the following requirements:

Parameter CategoryCore IndicatorInterchange Requirement
Electrical ClassPC Class (no overcurrent protection, external circuit breaker required)Must match; PC Class uses a load isolation switch as the executive component, with strong short-circuit withstand capacity
Pole Number/Current3P (3 poles), rated current 32AMust be identical to ensure load matching
Rated Voltage/Frequency380V AC, 50HzCompatible with 400V/50Hz or 415V/60Hz products
Transfer SpeedTotal transfer time ≤ 50msMust be ≤ 50ms to ensure uninterrupted power supply for sensitive equipment
Control FunctionR-iINT intelligent controller (auto-transfer auto-reclose/auto-transfer non-reclose, overvoltage/undervoltage/phase loss monitoring, RS485 communication)Functionally equivalent; at least basic monitoring and automatic transfer functions must be provided
Mechanical/Electrical InterlockingDouble interlocking, zero arc flash designMust be equipped to prevent simultaneous connection of two power supplies
Mounting MethodStandard 35mm DIN rail, width approx. 63mmDimensionally compatible to avoid re-drilling or mounting position modification
  1. Intra-brand Interchange Models of Schneider Wingoal (First Choice for Seamless Replacement)

Intra-brand interchange does not require modification of the installation scheme or control system, featuring the lowest risk and thus recommended as the first choice:

Interchange ModelCore Matching PointsDifference DescriptionInterchange Advantage
WATSNA-32/3PCR3P, 32A, PC Class, R-iINT ControllerSlight differences only in executive components; electrical parameters are completely consistentSame-series product, 100% compatible, no need to adjust control logic
WATSN-100/32/3H3P, 32A, PC Class, H Intelligent ControllerNew-generation product; H controller has richer functions, with mechanical service life increased to 10,000 operationsPerformance upgrade, optimized structure, stable supply
WTSH32-3N23P, 32A, PC Class, End-use Intelligent ControllerMounting dimensions are completely consistent with WATSNB series; supports fire linkageMore cost-effective, low maintenance cost, suitable for end-use load applications
WATSGA-32/3R3P, 32A, PC Class, R-type ControllerAdopts C65 series load switch as the executive component, with mechanical service life of 8,000 operationsHigh market recognition, easy procurement of accessories, outstanding cost performance

III. Cross-brand Interchange Model Comparison Table of Mainstream Brands (By Brand Category)

  1. ABB Brand Interchange Models
ABB ModelKey Matching ParametersFunctional EquivalenceMounting Compatibility
OTM32F3C 21D220C3P, 32A, PC Class, 21D Intelligent Controller (AC220V)Total transfer time ≤ 50ms, overvoltage/undervoltage/phase loss/frequency monitoring, mechanical service life of 10,000 operationsStandard DIN rail, width compatible (approx. 63mm)
DPT160-PC010 R32 3P3P, 32A, PC Class, PC010 ControllerIsolation switch as executive mechanism, double interlocking, supports generator linkageSlightly wider (approx. 75mm); mounting space adjustment may be required

Interchange Note: The parameter setting interface of ABB controller is different from that of Schneider R-iINT; it is necessary to reconfigure overvoltage/undervoltage thresholds and transfer modes.

  1. Chint Electric Interchange Models
Chint ModelKey Matching ParametersFunctional EquivalenceMounting Compatibility
NH40-32/3SZ PC Class3P, 32A, PC Class, Intelligent ControllerThree-stage transfer mechanism, transfer time ≤ 50ms, fire linkage, mechanical service life of 8,000 operationsFully compatible with 35mm DIN rail, consistent width
NXZN-63/32/3 PC Class3P, 32A, PC Class, Intelligent ControllerAC-33B utilization category, flexible contact, RS485 communicationMounting dimensions consistent with Schneider products, direct replacement available

Interchange Advantage: Priced at only 60%-70% of Schneider products; a leading domestic brand with short supply cycle.

  1. Delixi Electric Interchange Models
Delixi ModelKey Matching ParametersFunctional EquivalenceMounting Compatibility
CDQ0s-80/3-32D PC Class3P, 32A, PC Class, D-type Intelligent ControllerAuto-transfer auto-reclose/auto-transfer non-reclose, overvoltage/undervoltage/phase loss monitoring, transfer time ≤ 50msStandard DIN rail, dimensionally compatible
CDQ1F0632P032A23P, 32A, PC Class, Intelligent ControllerTwo-stage transfer mechanism, power-off time ≤ 0.1s, modular contactConsistent mounting dimensions, better heat dissipation performance

Interchange Advantage: Comprehensive after-sales service network, suitable for projects with limited budgets.

  1. Siemens Brand Interchange Models
Siemens ModelKey Matching ParametersFunctional EquivalenceMounting Compatibility
5TR1324-7CC32 PC Class3P, 32A, PC Class, Intelligent ControllerThree operating modes (auto-transfer auto-reclose/auto-transfer non-reclose/mutual backup), double interlockingStandard DIN rail, width approx. 63mm, direct replacement available

Interchange Advantage: Good compatibility with Siemens PLC, frequency converter and other equipment, suitable for large-scale industrial projects.

  1. In-depth Interchange Compatibility Analysis
  2. Electrical Parameter Compatibility
ParameterWATSNB-32-3 SpecificationInterchange Product RequirementCommon Differences & Solutions
Rated Short-time Withstand CurrentIcw≥1500A (1s)≥1500ASelect PC Class products to ensure short-circuit withstand capacity
Control VoltageAC220V/DC24V optionalMatch the control voltage of the original systemIf controller voltage differs, replace the control power supply or use an adapter
Utilization CategoryAC-33B/AC-33iBAt least AC-33BEnsure ability to withstand motor load impact
Communication ProtocolModBus RTU (RS485)Support ModBus or provide protocol conversionEnsure communication compatibility if integration with BMS is required
  1. Mechanical and Mounting Compatibility
ItemWATSNB-32-3 SpecificationInterchange Product RequirementMounting Precautions
WidthApprox. 63mm (2 modules)Within ±5mm rangeIf exceeding the range, adjust mounting position or replace busbar
HeightApprox. 100mmNo interference with adjacent equipmentEnsure ≥15mm heat dissipation space above the device
DepthApprox. 120mmNo protrusion beyond the distribution box depthAvoid interference with rear terminal blocks
Terminal BlockSuitable for wire cross-sectional area 1.5-16mm²Compatible with the same wire diameterEnsure firm wiring with torque complying with specifications
  1. Functional and Control Compatibility
FunctionWATSNB-32-3 FeatureMinimum Requirement for Interchange ProductsConfiguration Key Points
Transfer ModeAuto-transfer auto-reclose (default)/auto-transfer non-recloseAt least two modes availableSet according to original system requirements; auto-transfer non-reclose is recommended for generator backup power supply systems
Fault MonitoringOvervoltage, undervoltage, phase loss, frequency anomalyMust be equipped with basic monitoring functionsSet thresholds consistent with the original system (e.g., undervoltage ≤ 85%Un, overvoltage ≥ 110%Un)
Fire LinkageForced neutral position functionSupport passive contact inputEnsure correct connection of fire signals to the controller
Manual OperationEmergency manual transfer + padlocking functionMust be equippedEnsure the position of the operating mechanism is consistent with the original system
  1. Interchange Implementation Steps and Safety Precautions
  2. Preparation Work
  3.  Confirm that the technical parameters of the interchange product are completely matched with the original product (focus on checking PC Class, 3P, 32A, and transfer time ≤ 50ms)
  4.  Prepare tools: screwdriver, multimeter, insulating gloves, voltage tester, terminal crimping tool
  5.  Back up original system parameters: record overvoltage/undervoltage thresholds, transfer delay time, communication address, etc., of the R-iINT controller
  6.  Apply for power outage permission and formulate an emergency response plan
  7. Replacement Operation Process
  8.  Power Off and Voltage Testing: Disconnect the main and backup power supplies; after verifying no voltage, hang grounding wires and warning signs
  9.  Remove the Original Equipment: Mark the terminal blocks (normal power supply L1/L2/L3, backup power supply L1/L2/L3, load L1/L2/L3, control power supply, communication lines), then remove the old ATS
  10.  Install the New Equipment: Fix it in the original position, ensuring firm clamping on the DIN rail and stable installation
  11.  Wiring: Wire according to the marked correspondence, ensuring correct phase sequence and torque complying with specifications (1.5-2.5N·m)
  12.  Parameter Configuration: Set the new controller according to the original system parameters and test the communication function (if applicable)
  13.  Function Test:

Manual transfer test: Confirm normal switching between normal → backup → normal power supply without jamming

Automatic transfer test: Simulate main power supply undervoltage/phase loss to verify transfer action and time (≤ 50ms)

Interlocking test: Ensure no simultaneous connection of two power supplies and zero arc flash

Fire linkage test: Trigger the forced neutral position function to confirm disconnection of both power supplies

  1. Key Safety Points
  2.  Live Operation is Strictly Prohibited: PC Class ATS has no overcurrent protection and must be installed in a completely power-off state
  3.  Phase Sequence Consistency: The phase sequence of normal power supply, backup power supply and load side must be completely consistent to avoid equipment reverse rotation
  4.  Double Interlocking Verification: After installation, it is necessary to test the electrical and mechanical interlocking functions to eliminate potential safety hazards
  5.  Independent Control Power Supply: It is recommended to power the controller with an uninterruptible power supply (UPS) to ensure normal operation of monitoring and control functions
  6.  Label Update: Replace equipment identification and record the new equipment model, serial number and replacement date
  7. Interchange Selection Decision Matrix (Quick Selection Guide)
Application ScenarioRecommended Interchange ModelSelection Reason
Medical Equipment/Data Center (High Reliability)Schneider WATSN-100/32/3H or ABB OTM32F3C 21D220CLong mechanical service life (10,000 operations), fast transfer speed, complete communication functions
Industrial Automation (Motor Load)Chint NXZN-63/32/3 or Delixi CDQ1F0632P032A2AC-33B utilization category, capable of withstanding starting impact, moderate price
Commercial Building (Limited Budget)Chint NH40-32/3SZ or Delixi CDQ0s-80/3-32DHigh cost performance, basic functions meet requirements, excellent after-sales service
Generator Backup Power Supply SystemSchneider WATSNA-32/3PCR or ABB DPT160-PC010 R32Supports auto-transfer non-reclose mode, suitable for generator linkage
Fire Protection System (Forced Neutral Position Requirement)Schneider WTSH32-3N2 or Siemens 5TR1324-7CC32Complete fire linkage functions, complying with specification requirements

Summary

There is a wide range of interchangeable products for WATSNB-32-3 PC Class R-iINT. Intra-brand interchange (e.g., WATSNA-32/3PCR) is the most reliable option, while cross-brand interchange (e.g., ABB OTM32F3C, Chint NH40-32/3SZ) requires focused verification of electrical parameters, mounting dimensions and functional compatibility. Regardless of the selected scheme, the three core principles of power-off operation, double interlocking verification, and parameter matching must be followed to ensure the safe and reliable operation of the electrical system.