Complete Technical Parameters of Siemens 3WL1116/3WL1216 1600A ETU45B-G-LCD-3P

Complete Technical Parameters of Siemens 3WL1116/3WL1216 1600A ETU45B-G-LCD-3P

The parameters cover dimensions including basic electrical characteristics, potere di interruzione, trip unit, mechanical & environmental performance, communication and installation, facilitating engineering selection and system matching.

  1. Parametri elettrici di base
Elemento parametroValore delle specificheOsservazioni
Serie di prodottiSiemens SENTRON 3WLInterruttore automatico dell'aria (ACB)
Dimensioni del telaio3WL1116 (Frame I) / 3WL1216 (Frame II)3WL1116: Standard breaking capacity; 3WL1216: High breaking capacity
Corrente nominale (In)1600UNFrame size current 1600A, setting range 0.4–1In
Numero di poli3PTripolare, 3-phase main circuit
Rated Operational Voltage (Ue)690V e50/60Hz, conforme alla CEI 60947-2
Rated Insulation Voltage (Ui)1000V eBenchmark value for insulation withstand capability
Rated Impulse Withstand Voltage (Uimp)12kVCompliant with IEC 60947-1
Rated Short-time Withstand Current (Icw)Frame I: 66kA/1s; Frame II: 80kA/1sEnsures short-time thermal stability at 500V
Capacità di interruzione (terapia intensiva)Frame I: 55/66IL; Frame II: 80/100ILUltimate breaking capacity at 500V; Frame II offers higher breaking capacity
  1. Parameters of ETU45B-G-LCD Electronic Trip Unit
Function ModuleValore delle specificheDescrizione
Tipo di protezioneLSIG (l: Overload/Long-time Delay; S: Short-circuit/Short-time Delay; IO: Instantaneous Short-circuit; G: Ground Fault)Complete power distribution protection configuration
Protezione da sovraccarico (l)Characteristic Curve: I²t/I⁴t selezionabile; Setting Range: 0.4–1InI⁴t characteristic improves selectivity with downstream devices
Short-time Delay Short-circuit Protection (S)Setting Current: 2–10In; Time Delay: 0.1–0.4sAdjustable inverse/definite time delay to prevent selective tripping
Instantaneous Short-circuit Protection (IO)Setting Current: 2–10InRapid short-circuit current interruption without time delay
Protezione dai guasti a terra (G)Setting Current: 0.2–0.8In; Time Delay: 0.1–2sDetects ground faults to avoid equipment damage
Display & OperationLCD screen, rotary coding switchReal-time display of current, trip cause and fault records
Metodo di ripristinoManual/Auto selectableQuick power supply recovery after fault clearance

III. Mechanical & Environmental Parameters

Elemento parametroValore delle specificheOsservazioni
Vita meccanica150,000 operazioniNo-load operation, conforme alla CEI 60947-2
Vita elettrica10,000 operazioni (AC-3, alla corrente nominale)On-load breaking life, related to operating frequency
Operating MechanismSpring-loaded energy storage type (manual/electric optional)Electric mechanism suitable for remote control
Contatti ausiliariStandard: 2NO+2NC, expandable to 4NO+4NCStatus feedback and control circuit interlocking
Temperatura ambiente-25℃~+70℃ (operativo); -40℃~+85℃ (magazzinaggio)Wide temperature range for industrial applications
Classe di protezioneIP30 (body); IP40 (with protective cover)Prevents solid foreign object intrusion
Altitudine≤2000m (derating required above 2000m)Rated current derating by 1% for every 100m altitude increase
Metodo di montaggioFixed type/Drawout typeDrawout type enables maintenance without power outage
  1. Comunicazione & Measurement Parameters
FunzioneSpecificaInterface/Protocol
Communication ModuleCOM15 (PROFIBUS DP) / COM16 (MODBUS RTU)Opzionale, supports data upload to monitoring system
Measurement AccuracyCurrent: ±1%; Voltage: ±1.5%; Power: ±2%Compatible with Plus measurement function for energy management
Data Logging100 fault records (trip type, time, current value)Fault tracing and system diagnosis
TelecomandoSupports remote opening/closing and parameter settingRealized by electric mechanism + modulo di comunicazione
  1. Installazione & Dimension Parameters
Mounting TypeLarghezza (W)Altezza (H)Profondità (D)Peso
3WL1116 Fixed Type320mm434mm291mmApprox. 45kg
3WL1116 Drawout Type320mm434mmApprox. 450mmApprox. 55kg
3WL1216 Fixed Type460mm434mm291mmApprox. 56kg
3WL1216 Drawout Type460mm434mmApprox. 450mmApprox. 65kg
Mounting Mode35mm DIN rail/screw mountingFrame I width: 320mm; Frame II width: 460mm; Unified height: 434mm
  1. Key Selection & Application Tips
  2. Abbinamento del potere di interruzione: Select frame size based on the system’s maximum short-circuit current. Frame I is suitable for scenarios ≤66kA, while Frame II is for ≤100kA. UN 20% si consiglia il margine.
  3. Trip Unit Setting: Enable LSIG protection for motor loads, with the ground fault setting recommended at 0.3–0.5In. LSI protection is sufficient for power distribution loads.
  4. Communication Compatibility: Select COM15/COM16 module for remote monitoring, ensuring protocol compatibility with PLC/SCADA systems (PROFIBUS/MODBUS).
  5. Installation Space: The drawout type occupies approximately 160mm more depth than the fixed type. Reserve sufficient operation and maintenance space during cabinet design.
  6. Replacement & Aggiornamento: The 3WL series has been upgraded to the 3WA series (per esempio., 3WA1116-3EG45-4GA4), featuring compatible dimensions and protection functions, plus added Ethernet communication and intelligent diagnosis.

 

 

VII. Conformità & Certificazione

Compliant Standards: GB 14048.2, CEI 60947-2, IN 60947-2

Certifications: CE, UL, CSA (per alcuni modelli), meeting compliance requirements for global industrial applications